background image

506318-03

Page 2 of 18

Issue 1946

Installation

NOTE: 

In some cases, noise in the living area has been 

traced to gas pulsations from improper installation of 

equipment.

•  Locate unit away from windows, patios, decks, etc. 

where unit operation sounds may disturb customer.

•  Leave some slack between structure and unit to 

absorb vibration.

•  Place a sound-absorbing material, such as Isomode, 

under the unit if it will be installed in a location or 

position that will transmit sound or vibration to the 

living area or adjacent buildings.

•  Install the unit high enough above the ground or roof to 

allow adequate drainage of defrost water and prevent 

ice buildup.

•  In heavy snow areas, do not locate the unit where 

drifting snow will occur. The unit base should be 

elevated above the depth of average snows.

NOTE: 

Elevation of the unit may be accomplished 

by constructing a frame using suitable materials. If a 

support frame is constructed, it must not block drain 

holes in unit base.

•  When installed in areas where low ambient 

temperatures exist, locate unit so winter prevailing 

winds do not blow directly into outdoor coil.

•  Locate unit away from overhanging roof lines which 

would allow water or ice to drop on, or in front of, coil 

or into unit.

When outdoor unit is connected to factory-approved indoor 

unit, outdoor unit contains system refrigerant charge for 

operation with matching indoor unit when connected by 15 

ft. of field-supplied tubing. For proper unit operation, check 

refrigerant charge using charging information located on 

control box cover.

Outdoor Section

Zoning ordinances may govern the minimum distance the 

condensing unit can be installed from the property line. 

Install on a Solid, Level Mounting Pad

The outdoor section is to be installed on a solid foundation. 

This foundation should extend a minimum of 2” (inches) 

beyond the sides of the outdoor section. To reduce the 

possibility of noise transmission, the foundation slab 

should NOT be in contact with or be an integral part of the 

building foundation. See Figure 1.

If conditions or local codes require the unit be attached to 

pad or mounting frame, tie down bolts should be used and 

secured to unit base pan.

When servicing or repairing HVAC components, ensure 

the fasteners are appropriately tightened. Table 1 shows 

torque values for fasteners.

Fastener

Torque

Stem Caps

8 ft. lbs.

Service Port Caps

8 ft. lbs.

Sheet Metal Screws

16 in. lbs.

#8 Machine Screws

16 in. lbs.

#10 Machine Screws

28 in. lbs.

Compressor Bolts

90 in. lbs.

Table 1. Torque Table

Inspection of Shipment

Upon receipt of equipment, carefully inspect it for possible 

shipping damage. If damage is found, it should be noted 

on the carrier’s freight bill. Take special care to examine 

the unit inside the carton if the carton is damaged. Any 

concealed damage discovered should be reported to the 

last carrier immediately, preferably in writing, and should 

include a request for inspection by the carrier’s agent.

If any damages are discovered and reported to the carrier 

DO NOT INSTALL THE UNIT

, as claim may be denied.

Check the unit rating plate to confirm specifications are as 

ordered.

Safety Precautions

Follow all safety codes. Wear safety glasses and work 

gloves. Use quenching cloth for brazing operations. 

Have fire extinguisher available. Read these instructions 

thoroughly and follow all warning or cautions attached to 

the unit.
1.  Always wear proper personal protection equipment.
2.  Always disconnect electrical power before removing 

panel or servicing equipment.

3.  Keep hands and clothing away from moving parts.
4.  Handle refrigerant with caution; refer to proper MSDS 

from refrigerant supplier.

5.  Use care when lifting, avoid contact with sharp edges. 

Содержание 4HP14

Страница 1: ...alified personnel and do not supersede any national or local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or Cana...

Страница 2: ...nstalled on a solid foundation This foundation should extend a minimum of 2 inches beyond the sides of the outdoor section To reduce the possibility of noise transmission the foundation slab should NO...

Страница 3: ...l or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and top of unit...

Страница 4: ...8 042 3 8 3 8 7 8 7 8 048 3 8 3 8 7 8 7 8 060 3 8 3 8 7 8 1 1 8 Field supplied 7 8 x 1 1 8 connector required on both ends of vapor tubing Table 3 Recommended Liquid Vapor Tube Diameters in Be extra c...

Страница 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Страница 6: ...il Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR...

Страница 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Страница 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Страница 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Страница 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Страница 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Страница 12: ...the low voltage field wiring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a...

Страница 13: ...or varying lengths of line set refer to Table 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustme...

Страница 14: ...for 90 seconds following the start up of the compressor during test mode High Pressure Switch HI PS When the high pressure switch trips the defrost board will cycle off the compressor and the strike c...

Страница 15: ...ition at power up the control will ignore the test pins When the jumper is placed across the TEST pins for 2 seconds the control will enter the defrost mode If the jumper is removed before an addition...

Страница 16: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Страница 17: ...he defrost cycle In case of extended power outage If the outdoor temperature is below 50 F and power to your outdoor unit has been interrupted for one hour or longer observe the following when restori...

Страница 18: ...506318 03 Page 18 of 18 Issue 1946 Figure 8 14 15 SEER Wiring Diagram...

Отзывы: