background image

Page 10

Brazing Connection Procedure

 1 − Cut ends of the refrigerant lines square (free from nicks

or dents). Debur the ends. The pipe must remain
round, do not pinch end of the line.

 2 − Before making line set connections, use dry nitrogen to

purge the refrigerant piping. This will help to prevent
oxidation and the introduction of moisture into the sys-
tem.

 3 − Use silver alloy brazing rods (5 or 6 percent minimum

silver alloy for copper−to−copper brazing or 45 percent
silver alloy for copper−to−brass or copper−to−steel braz-
ing) which are rated for use with HCFC22 refrigerant.
Wrap a wet cloth around the valve body and the copper
tube stub. Braze the line set to the service valve.

 4 − Wrap a wet cloth around the valve body and copper

tube stub to protect it from heat damage during braz-
ing. Wrap another wet cloth underneath the valve body
to protect the base paint.

NOTE − The tube end must stay bottomed in the fitting
during final assembly to ensure proper seating, sealing
and rigidity.

 5 − Install a field−provided thermal expansion valve (ap-

proved for use with HCFC22 refrigerant) in the liquid
line at the indoor coil.

Refrigerant Metering Device

10HPB units are used in check expansion valve systems
only. See the Lennox Engineering Handbook for approved
TXV match-ups and application information.

Check expansion valves equipped with either Chatleff or
flare−type fittings are available from Lennox. Refer to the
Engineering Handbook for applicable expansion valves
for use with specific match-ups. See table 2 for applicable
check expansion valve kits.

If you install a check expansion valve with an indoor
coil that includes a fixed orifice, remove the orifice be-
fore the check expansion valve is installed.

IMPORTANT

Failure to remove RFC orifice when installing an ex-
pansion valve on the indoor coil will result in improp-
er operation and damage to the system.

Table 2

Indoor Check And Expansion Valve Kits

Model

Kit Number

10HPB18
10HPB24
10HPB30
10HPB36

LB−85759F

10HPB42
10HPB48
10HPB60

LB−85759G

See figure 11 for installation of the check expansion valve.

Metering Device Installation

expansion 

valve

o−ring

o−ring

strainer

liquid line 

stub

distributor

Figure 11

Manifold Gauge Set

When checking the unit charge, use a manifold gauge set
that is equipped with low loss" hoses. Do not use a man-
ifold gauge set with anything other than a low loss" hose.
See figure 12 for manifold gauge connections.

Содержание 10HPB18

Страница 1: ...h 5 tons 504 828M 06 04 Supersedes 02 04 Table of Contents 10HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Re...

Страница 2: ...8 111 6 3 8 162 6 3 8 162 Top View Base Section 3 4 19 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 coil drain outlets around perimeter of base optional unit stand off kit 4 field installed liqu...

Страница 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Страница 4: ...2 Ground unit at unit disconnect switch or to an earth ground NOTE To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box us ing a proper conduit fitting N...

Страница 5: ...Y1 O Outdoor Unit Figure 5 power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor R C W1 Y1 O G R C W1 W2 W3 G 10HPB and Blower Unit Thermostat Designations with auxi...

Страница 6: ...Refrigerant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Installing Refrigerant Line During the installation of any heat pump or a c s...

Страница 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Страница 10: ...he indoor coil Refrigerant Metering Device 10HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application information Check e...

Страница 11: ...erant lines have been leak tested and evacuated All precautions should be exercised to keep the system free from dirt moisture and air To Access Schrader Port 1 Remove service port cap with an adjusta...

Страница 12: ...mixture check the high and low pressures before unbrazing WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered responsibly Failure to follow this warning may res...

Страница 13: ...sure 6 When the absolute pressure reaches 23 000 microns 29 01 inches of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum...

Страница 14: ...ng mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line temperature 5 The outdoor temperature will determine which charg ing method to...

Страница 15: ...ns Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the system is...

Страница 16: ...n the outdoor unit control circuit is isolated from power and field provided relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that he is...

Страница 17: ...ill lock out the unit if the optional high pressure switch opens The diagnostic LEDs will display a pattern for an open high pressure switch See table 8 The unit will re main locked out until the swit...

Страница 18: ...Clean or change filters 2 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Отзывы: