background image

Page 11

Figure 12

10HPB Manifold Gauge Connections (Cooling Cycle)

outdoor

coil

defrost thermostat

expansion/

check valve

biflow

filter / drier

to

HCFC−22

drum

low

pressure

high

pressure

compressor

reversing valve

vapor

line

valve

muffler

Note − Arrows indicate the direction of refrigerant flow.

vapor

service

port

expansion/check

valve

Indoor Unit

Outdoor Unit

liquid line

service

port

gauge manifold

distributor

indoor

coil

Service Valves

The liquid line and vapor line service valves (figures 13 and
14) and gauge ports are used for leak testing, evacuating,
charging and checking charge. See table 3 for torque re-
quirements.

Each valve is equipped with a service port which has a fac-
tory−installed Schrader valve. A service port cap protects
the Schrader valve from contamination and serves as the
primary leak seal.

Table 3

Torque Requirements

Part

Recommended Torque

Service valve cap

8 ft.− lb.

11 NM

Sheet metal screws

16 in.− lb.

2 NM

Machine screws #10

28 in.− lb.

3 NM

Compressor bolts

90 in.− lb.

10 NM

Gauge port seal cap

8 ft.− lb.

11 NM

IMPORTANT

Service valves are closed to the outdoor unit and
open to line set connections. Do not open the valves
until refrigerant lines have been leak tested and
evacuated. All precautions should be exercised to
keep the system free from dirt, moisture and air.

To Access Schrader Port:

 1 − Remove service port cap with an adjustable wrench.

 2 − Connect gauge to the service port.

 3 − When  testing  is  completed,  replace  service  port  cap.

Tighten finger tight, then an additional 1/6 turn.

To Open Liquid or Vapor Line Service Valve:

 1 − Remove stem cap with an adjustable wrench.

 2 − Use a service wrench with a hex head extension to back

the stem out counterclockwise as far as it will go.

NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.

 3 − Replace stem cap. Tighten finger tight, then tighten an

additional 1/6 turn.

To Close Liquid Line Service Valve:

 1 − Remove stem cap with an adjustable wrench.

 2 − Use a service wrench with a hex head extension to turn

the stem clockwise to seat the valve. Tighten firmly.

NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.

 3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

Ball−Type Vapor Line Service Valve

Vapor line service valves function the same way as the oth-
er valves, the difference is in the construction. These
valves are not rebuildable. If a valve has failed, you must
replace it. A ball valve valve is illustrated in figure 14.

Содержание 10HPB18

Страница 1: ...h 5 tons 504 828M 06 04 Supersedes 02 04 Table of Contents 10HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Re...

Страница 2: ...8 111 6 3 8 162 6 3 8 162 Top View Base Section 3 4 19 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 coil drain outlets around perimeter of base optional unit stand off kit 4 field installed liqu...

Страница 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Страница 4: ...2 Ground unit at unit disconnect switch or to an earth ground NOTE To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box us ing a proper conduit fitting N...

Страница 5: ...Y1 O Outdoor Unit Figure 5 power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor R C W1 Y1 O G R C W1 W2 W3 G 10HPB and Blower Unit Thermostat Designations with auxi...

Страница 6: ...Refrigerant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Installing Refrigerant Line During the installation of any heat pump or a c s...

Страница 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Страница 10: ...he indoor coil Refrigerant Metering Device 10HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application information Check e...

Страница 11: ...erant lines have been leak tested and evacuated All precautions should be exercised to keep the system free from dirt moisture and air To Access Schrader Port 1 Remove service port cap with an adjusta...

Страница 12: ...mixture check the high and low pressures before unbrazing WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered responsibly Failure to follow this warning may res...

Страница 13: ...sure 6 When the absolute pressure reaches 23 000 microns 29 01 inches of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum...

Страница 14: ...ng mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line temperature 5 The outdoor temperature will determine which charg ing method to...

Страница 15: ...ns Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the system is...

Страница 16: ...n the outdoor unit control circuit is isolated from power and field provided relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that he is...

Страница 17: ...ill lock out the unit if the optional high pressure switch opens The diagnostic LEDs will display a pattern for an open high pressure switch See table 8 The unit will re main locked out until the swit...

Страница 18: ...Clean or change filters 2 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Отзывы: