The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak−
free seal.

Service Valve

(Valve Closed)

Schrader valve open

to line set when valve is

closed (front seated)

service

port

service

port cap

stem cap

insert hex

wrench here

(valve front seated)

to outdoor coil

to indoor coil

Service Valve

(Valve Open)

Schrader

valve

service

port

service port

cap

insert hex

wrench here

to indoor coil

to outdoor coil

stem cap

Figure 13

Vapor Line (Ball Type) Service Valve 

(Valve Open)

Schrader

valve

stem cap

To open:  rotate stem counter-clockwise 90

To close:  use adjustable wrench and

rotate stem clockwise 90

.

ball

(shown open)

service port

cap

service

port

field side

unit side

stem

Figure 14

Leak Testing

After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks. 

 

WARNING

Danger of fire. Bleeding the refrigerant
charge from only the high side may re-
sult in the low side shell and suction
tubing being pressurized. Appplication
of a brazing torch while pressurized
may result in ignition of the refrigerant
and oil mixture − check the high and low
pressures before unbrazing.

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.

Failure to follow this warning may result in personal
injury or death.

 

WARNING

Danger of explosion:  Can cause equip-
ment damage, injury or death. Never
use oxygen to pressurize a refrigera-
tion or air conditioning system. Oxygen
will explode on contact with oil and
could cause personal injury.

WARNING

Danger of explosion:  Can cause equipment damage,
injury or death. When using a high pressure gas
such as dry nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator that can
control the pressure down to 1 or 2 psig (6.9 to 13.8
kPa).

Using an Electronic Leak Detector or Halide

 1 − Connect a cylinder of HCFC-22 to the center port of the

manifold gauge set.

 2 − With both manifold valves closed, open the valve on

the HCFC-22 cylinder (vapor only).

 3 − Open the high pressure side of the manifold to allow

the HCFC-22 into the line set and indoor unit. Weigh in
a trace amount of HCFC-22.

 

[A trace amount is a maxi-

mum of 2 ounces (57 g) or 3 pounds (31 kPa) pres-
sure.]

 

Close the valve on the HCFC-22 cylinder and the

valve on the high pressure side of the manifold gauge
set. Disconnect the HCFC-22 cylinder.

 4 − Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

Содержание 10HPB18

Страница 1: ...h 5 tons 504 828M 06 04 Supersedes 02 04 Table of Contents 10HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Re...

Страница 2: ...8 111 6 3 8 162 6 3 8 162 Top View Base Section 3 4 19 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 coil drain outlets around perimeter of base optional unit stand off kit 4 field installed liqu...

Страница 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Страница 4: ...2 Ground unit at unit disconnect switch or to an earth ground NOTE To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box us ing a proper conduit fitting N...

Страница 5: ...Y1 O Outdoor Unit Figure 5 power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor R C W1 Y1 O G R C W1 W2 W3 G 10HPB and Blower Unit Thermostat Designations with auxi...

Страница 6: ...Refrigerant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Installing Refrigerant Line During the installation of any heat pump or a c s...

Страница 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Страница 10: ...he indoor coil Refrigerant Metering Device 10HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application information Check e...

Страница 11: ...erant lines have been leak tested and evacuated All precautions should be exercised to keep the system free from dirt moisture and air To Access Schrader Port 1 Remove service port cap with an adjusta...

Страница 12: ...mixture check the high and low pressures before unbrazing WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered responsibly Failure to follow this warning may res...

Страница 13: ...sure 6 When the absolute pressure reaches 23 000 microns 29 01 inches of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum...

Страница 14: ...ng mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line temperature 5 The outdoor temperature will determine which charg ing method to...

Страница 15: ...ns Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the system is...

Страница 16: ...n the outdoor unit control circuit is isolated from power and field provided relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that he is...

Страница 17: ...ill lock out the unit if the optional high pressure switch opens The diagnostic LEDs will display a pattern for an open high pressure switch See table 8 The unit will re main locked out until the swit...

Страница 18: ...Clean or change filters 2 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Отзывы: