Page 4

If unit coil cannot be mounted away from prevailing winter
winds, a wind barrier should be constructed. Size barrier at
least the same height and width as outdoor unit. Install bar-
rier 24 inches (610 mm) from the sides of the unit in the di-
rection of prevailing winds.

wind barrier

inlet air

inlet air

inlet air

inlet air

prevailing winter winds

Rooftop Application

Wind Barrier Construction

Figure 3

Electrical

WARNING

Unit must be grounded in accordance with national
and local codes.
Electric Shock Hazard.
Can cause injury or death.

 1 − Install line voltage power supply to unit from a properly

sized disconnect switch.

 2 − Ground unit at unit disconnect switch or to an earth

ground.

NOTE − To facilitate conduit, a hole is in the bottom of 
the control box. Connect conduit to the control box us
ing a proper conduit fitting.

NOTE − Units are approved for use only with copper 
conductors.

24V, Class II circuit connections are made in the low 
voltage junction box. Refer to figure 4 for field wiring 
diagram.

NOTE − A complete unit wiring diagram is located in
side the unit control box cover.

 3 − Install room thermostat (ordered separately) on an in-

side wall approximately in the center of the conditioned
area and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be effected
by sunlight, drafts or vibrations.

 4 − Install voltage wiring from outdoor to indoor unit and

from thermostat to indoor unit. See figures 5 and 6.

Содержание 10HPB18

Страница 1: ...h 5 tons 504 828M 06 04 Supersedes 02 04 Table of Contents 10HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Re...

Страница 2: ...8 111 6 3 8 162 6 3 8 162 Top View Base Section 3 4 19 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 coil drain outlets around perimeter of base optional unit stand off kit 4 field installed liqu...

Страница 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Страница 4: ...2 Ground unit at unit disconnect switch or to an earth ground NOTE To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box us ing a proper conduit fitting N...

Страница 5: ...Y1 O Outdoor Unit Figure 5 power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor R C W1 Y1 O G R C W1 W2 W3 G 10HPB and Blower Unit Thermostat Designations with auxi...

Страница 6: ...Refrigerant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Installing Refrigerant Line During the installation of any heat pump or a c s...

Страница 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Страница 10: ...he indoor coil Refrigerant Metering Device 10HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application information Check e...

Страница 11: ...erant lines have been leak tested and evacuated All precautions should be exercised to keep the system free from dirt moisture and air To Access Schrader Port 1 Remove service port cap with an adjusta...

Страница 12: ...mixture check the high and low pressures before unbrazing WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered responsibly Failure to follow this warning may res...

Страница 13: ...sure 6 When the absolute pressure reaches 23 000 microns 29 01 inches of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum...

Страница 14: ...ng mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line temperature 5 The outdoor temperature will determine which charg ing method to...

Страница 15: ...ns Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the system is...

Страница 16: ...n the outdoor unit control circuit is isolated from power and field provided relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that he is...

Страница 17: ...ill lock out the unit if the optional high pressure switch opens The diagnostic LEDs will display a pattern for an open high pressure switch See table 8 The unit will re main locked out until the swit...

Страница 18: ...Clean or change filters 2 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Отзывы: