 5 − Compare the subcooling value with those in table 5. If

subcooling is greater than shown, recover some refrig-
erant. If subcooling is less than shown, add some re-
frigerant.

Table 

5

Subcooling Values

Model

Subcooling Temp. 

_

F (

_

C)

10HPB18

5 (2.8)

10HPB24

7 (3.9)

10HPB30

9 (5)

10HPB36

11 (6.1)

10HPB42

7 (3.9)

10HPB48

8 (4.4)

10HPB60

10 (5.6)

Charging Using Normal Operating Pressures 

and the Approach Method

Outdoor Temp. > 65

_

F (18

_

C)

The following procedure is intended as a general guide and

is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C).
Monitor system pressures while charging.
 1 − Record outdoor ambient temperature using a digital

thermometer.

 2 − Attach high pressure gauge set and operate unit for

several minutes to allow system pressures to stabilize.

 3 − Compare stabilized pressures with those provided in

table 6, Normal Operating Pressures." Minor varia-
tions in these pressures may be expected due to differ-
ences in installations. Significant differences could
mean that the system is not properly charged or that a
problem exists with some component in the system.
Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
listed indicate that the system is undercharged. Verify
adjusted charge using the approach method.

Table 6

Normal Operating Pressures

Outdoor

Coil Air

10HPB18

10HPB24

10HPB30

10HPB36

10HPB42

10HPB48

10HPB60

Mode

Coil Air

Entering

 Temp.

F (

C)

liq.

+10

psig

vap.

+5

psig

liq.

+10

psig

vap.

+5

psig

liq.

+10

psig

vap.

+5

psig

liq.

+10

psig

vap.

+5

psig

liq.

+10

psig

vap.

+5

psig

liq.

+10

psig

vap.

+5

psig

liq.

+10

psig

vap.

+5

psig

65 (18)

148

71

156

70

165

73

171

68

173

69

163

74

166

71

Cooling

75 (24)

171

74

182

72

204

70

192

70

205

72

196

74

195

73

Cooling

TXV

O l

85 (29)

200

76

210

74

236

71

222

71

252

73

229

75

227

74

TXV

Only

95 (35)

230

78

241

75

268

73

258

73

278

74

261

77

261

76

y

105 (41)

263

81

275

78

302

74

295

74

315

78

295

78

302

78

20 (−7)

166

33

170

28

178

24

194

26

182

28

178

26

190

27

Heating

30 (−1)

177

42

184

36

190

32

208

35

190

36

188

34

204

35

Heating

40 (4)

 188

51

 194

42

202

39

221

42

202

44

196

42

217

43

50 (10)

200

61

212

56

214

47

236

54

212

54

206

50

234

53

Содержание 10HPB18

Страница 1: ...h 5 tons 504 828M 06 04 Supersedes 02 04 Table of Contents 10HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Re...

Страница 2: ...8 111 6 3 8 162 6 3 8 162 Top View Base Section 3 4 19 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 coil drain outlets around perimeter of base optional unit stand off kit 4 field installed liqu...

Страница 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Страница 4: ...2 Ground unit at unit disconnect switch or to an earth ground NOTE To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box us ing a proper conduit fitting N...

Страница 5: ...Y1 O Outdoor Unit Figure 5 power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor R C W1 Y1 O G R C W1 W2 W3 G 10HPB and Blower Unit Thermostat Designations with auxi...

Страница 6: ...Refrigerant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Installing Refrigerant Line During the installation of any heat pump or a c s...

Страница 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Страница 10: ...he indoor coil Refrigerant Metering Device 10HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application information Check e...

Страница 11: ...erant lines have been leak tested and evacuated All precautions should be exercised to keep the system free from dirt moisture and air To Access Schrader Port 1 Remove service port cap with an adjusta...

Страница 12: ...mixture check the high and low pressures before unbrazing WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered responsibly Failure to follow this warning may res...

Страница 13: ...sure 6 When the absolute pressure reaches 23 000 microns 29 01 inches of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum...

Страница 14: ...ng mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line temperature 5 The outdoor temperature will determine which charg ing method to...

Страница 15: ...ns Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the system is...

Страница 16: ...n the outdoor unit control circuit is isolated from power and field provided relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that he is...

Страница 17: ...ill lock out the unit if the optional high pressure switch opens The diagnostic LEDs will display a pattern for an open high pressure switch See table 8 The unit will re main locked out until the swit...

Страница 18: ...Clean or change filters 2 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Отзывы: