background image

Page 9

10ACE SERIES

Charge Using Approach Method (TXV Systems)
− Outdoor Temperature >65°F (18°C)

The following procedure is intended as a general guide and
is for use on expansion valve (TXV) systems only. For best
results, indoor temperature should be 70°F (21°C) to 80°F
(26°C). Monitor system pressures while charging.

1. Record outdoor ambient temperature using a digital

thermometer.

2. Attach high pressure gauge set and operate unit for

several minutes to allow system pressures to stabilize.

3. Compare stabilized pressures with those provided in

table 7, Normal Operating Pressures."

IMPORTANT

Use table 7 to help perform maintenance checks.
Table 7 is not a procedure for charging the system.

Minor variations in these pressures may be due to
differences in installations. Significant deviations
could mean that the system is not properly charged
or that a problem exists with some component in the
system.

Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
listed indicate that the system is undercharged.
Verify adjusted charge using the approach method.

NOTE − For best results, use the same digital ther-
mometer to check both outdoor ambient and liquid
temperatures.

4. Check the liquid line temperature. The difference be-

tween the ambient and liquid temperatures should
match values given in table 6. Loss of charge results
in low capacity and efficiency.

5. If the values do not agree with the those in table 6, add

refrigerant to lower the approach temperature, or re-
cover refrigerant from the system to increase the ap-
proach temperature.

Table 6

Approach Values

10ACE Model

−024

−036

−048

−060

Temp. °F (°C)

18 (10)

11 (6)

8 (4.5)

13 (7)

Approach Value is the Liquid Line Temperature minus Outdoor Ambi-
ent Temperature [ºF (ºC) +

 

1ºF (0.5ºC)]

Table 7

Normal Operating Pressures*

Temp

5

F

10ACE−024

10ACE−036

10ACE−048

10ACE−060

Temp

5

F

(

5

C)**

Liq.

Suc.

Liq.

Suc.

Liq.

Suc.

Liq.

Suc.

Expansion Valve

65 (18)

163

70

162

70

159

71

170

74

75 (24)

193

71

187

74

188

72

201

76

85 (29)

225

72

219

75

220

73

234

77

95 (35)

260

73

253

77

251

76

270

79

105 (41)

298

74

291

79

290

77

309

79

110 (43)

318

75

310

80

309

78

331

80

115 (45)

338

75

329

81

328

79

351

81

Fixed Orifice

65 (18)

165

63

168

67

163

68

189

72

75 (24)

194

67

195

71

190

71

203

74

85 (29)

224

70

224

75

220

74

233

77

95 (35)

257

73

255

78

251

77

265

79

105 (41)

293

76

289

82

288

79

301

82

110 (43)

313

78

305

83

307

80

319

83

115 (45)

332

79

324

84

325

82

339

84

*

Values shown are typical pressures (in. psig +2psig); indoor unit
match up, indoor air quality equipment, and indoor load will cause
the pressures to vary.

** Temperature of the air entering the outside coil.

Содержание 10ACE Series

Страница 1: ...ox Industries Inc P O Box 799900 Dallas TX 75379 9900 INSTALLATION INSTRUCTIONS 10ACE Series Units CONDENSER UNITS 505 128M 03 06 Supersedes 01 06 Table of Contents 10ACE Outdoor Units 1 Shipping Pack...

Страница 2: ...16 24 1 4 565 048 33 838 32 1 4 819 24 1 4 616 060 33 940 32 1 4 921 24 1 4 718 General Information These instructions are intended as a general guide and do not supersede national or local codes in a...

Страница 3: ...l installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltage power sup...

Страница 4: ...es square free from nicks or dents Debur the ends The pipe must remain round do not pinch end of the line 2 Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage d...

Страница 5: ...he stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Страница 6: ...valve on the high side of the manifold gauge set which will pressurize line set and indoor unit 7 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be det...

Страница 7: ...ig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the HCFC 22 cylinder and remove the manifold gauge set Start Up IMPORTANT If unit is equipped with crankca...

Страница 8: ...iate charging procedure Charge Using Weigh in Method Fixed Orifice TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient temperature is cool use the weigh i...

Страница 9: ...eratures 4 Check the liquid line temperature The difference be tween the ambient and liquid temperatures should match values given in table 6 Loss of charge results in low capacity and efficiency 5 If...

Страница 10: ...ight out to extract the push pins along one side of the coil If necessary remove the push pins along the back of the unit it is usually unnecessary to fully re move the inner mesh screen Drape the mes...

Страница 11: ...cklist Job Name Job no Date Job Location City State Installer City State Unit Model No Serial No Service Technician Nameplate Voltage Rated Load Ampacity Compressor Outdoor Fan Maximum Fuse or Circuit...

Страница 12: ......

Отзывы: