background image

Page 5

10ACE SERIES

If you install a expansion valve with an indoor coil that
includes a fixed orifice, remove the orifice before the
expansion valve is installed.

IMPORTANT

Failure to remove the fixed orifice when installing an
expansion valve on the indoor coil will result in im-
proper operation and damage to the system.

Manifold Gauge Set

When checking the unit charge, use a manifold gauge set
that is equipped with low loss" hoses. Do not use a man-
ifold gauge set with anything other than a low loss" hose.

Service Valves

The service valves (liquid line − figure 6, vapor line − figures
7 and 8) and gauge ports are used for leak testing, eva-
cuating, charging and checking charge. Each valve is
equipped with a service port which has a factory−installed
Schrader valve. A service port cap protects the Schrader
valve from contamination and serves as the primary leak
seal.

To Access Schrader Port:

1. Remove service port cap with an adjustable wrench.
2. Connect gauge to the service port.
3. When testing is complete, replace service port cap.

Tighten finger tight, then torque per table 1 (Page 2) .

To Open Front-Seated Service Valves:

1. Remove stem cap with an adjustable wrench.
2. Use a service wrench with a hex−head extension

(3/16" for liquid-line valve sizes; 5/16" for vapor-line
valve sizes) to back the stem out counterclockwise as
far as it will go.

3. Replace the stem cap. Tighten finger tight, then torque

per table 1 (Page 2) .

To Close Front-Seated Service Valves:

1. Remove the stem cap with an adjustable wrench.
2. Use a service wrench with a hex−head extension

(3/16" for liquid-line valve sizes; 5/16" for vapor-line
valve sizes) to turn the stem clockwise to seat the
valve. Tighten it firmly.

3. Replace the stem cap. Tighten finger tight, then torque

per table 1 (Page 2) .

Vapor Line Ball Valve

Ball-type service valve (10ACE−060 only, figure 8) func-
tions the same way as the other valves but cannot be re-
built; if one fails, replace with a new valve. The ball valve is
equipped with a service port with a factory−installed
Schrader valve. A service port cap protects the Schrader
valve from contamination and assures a leak−free seal.

Front-Seated Liquid Line Service Valve

Figure 6

INSERT HEX
WRENCH HERE

SERVICE
PORT CAP

STEM
CAP

(VALVE FRONT-SEATED)

TO 
OUT-
DOOR
COIL

SCHRADER
VALVE [OPEN TO
LINE SET WHEN
VALVE IS CLOSED
(FRONT SEATED)]

TO 
INDOOR
COIL

Valve in closed position

Valve in open position

Front-Seated Vapor Line Service Valve

Figure 7

Valve in closed position

INSERT
HEX
WRENCH
HERE

SERVICE PORT

SERVICE
PORT CAP

STEM CAP

(VALVE
FRONT-SEATED)

TO 
OUTDOOR
COIL

SCHRADER VALVE
[OPEN TO LINE SET
WHEN VALVE IS
CLOSED (FRONT
SEATED)]

TO
INDOOR
COIL

Valve in open position

SERVICE PORT

BALL (SHOWN
CLOSED)

STEM
CAP

SCHRADER VALVE

SERVICE
PORT CAP

TO
INDOOR
COIL

TO
OUTDOOR
COIL

STEM

USE ADJUSTABLE WRENCH

TO OPEN:  ROTATE STEM
COUNTER-CLOCKWISE 90°.
TO CLOSE:  ROTATE STEM
CLOCKWISE 90°.

Ball−Type Vapor Valve (Valve Closed)

Figure 8

Содержание 10ACE Series

Страница 1: ...ox Industries Inc P O Box 799900 Dallas TX 75379 9900 INSTALLATION INSTRUCTIONS 10ACE Series Units CONDENSER UNITS 505 128M 03 06 Supersedes 01 06 Table of Contents 10ACE Outdoor Units 1 Shipping Pack...

Страница 2: ...16 24 1 4 565 048 33 838 32 1 4 819 24 1 4 616 060 33 940 32 1 4 921 24 1 4 718 General Information These instructions are intended as a general guide and do not supersede national or local codes in a...

Страница 3: ...l installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltage power sup...

Страница 4: ...es square free from nicks or dents Debur the ends The pipe must remain round do not pinch end of the line 2 Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage d...

Страница 5: ...he stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Страница 6: ...valve on the high side of the manifold gauge set which will pressurize line set and indoor unit 7 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be det...

Страница 7: ...ig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the HCFC 22 cylinder and remove the manifold gauge set Start Up IMPORTANT If unit is equipped with crankca...

Страница 8: ...iate charging procedure Charge Using Weigh in Method Fixed Orifice TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient temperature is cool use the weigh i...

Страница 9: ...eratures 4 Check the liquid line temperature The difference be tween the ambient and liquid temperatures should match values given in table 6 Loss of charge results in low capacity and efficiency 5 If...

Страница 10: ...ight out to extract the push pins along one side of the coil If necessary remove the push pins along the back of the unit it is usually unnecessary to fully re move the inner mesh screen Drape the mes...

Страница 11: ...cklist Job Name Job no Date Job Location City State Installer City State Unit Model No Serial No Service Technician Nameplate Voltage Rated Load Ampacity Compressor Outdoor Fan Maximum Fuse or Circuit...

Страница 12: ......

Отзывы: