Page 7

10ACE SERIES

CAUTION

Danger of Equipment Damage.

Avoid deep vacuum operation. Do not use compres-
sors to evacuate a system. Extremely low vacuums
can cause internal arcing and compressor failure.

Damage caused by deep vacuum operation will void
warranty.

7. Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.

8. Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

9. When the absolute pressure requirement above has

been met, disconnect the manifold hose from the vac-
uum pump and connect it to an upright cylinder of
HCFC-22 refrigerant. Open the manifold gauge valves
to break the vacuum from 1 to 2 psig positive pressure
in the line set and indoor unit. Close manifold gauge
valves and shut off the HCFC-22 cylinder and remove
the manifold gauge set.

Start Up

IMPORTANT

If unit is equipped with crankcase heater, it should
be energized 24 hours before unit start−up to pre-
vent compressor damage as a result of slugging.

1. Rotate the fan to check for frozen bearings or binding.
2. Inspect all factory− and field-installed wiring for loose

connections.

3. After evacuation is complete, open the liquid line and

vapor line service valves to release refrigerant charge
(contained in outdoor unit) into the system.

4. Replace the stem caps and secure finger tight, then

tighten an additional one-sixth (1/6) of a turn.

5. Check voltage supply at the disconnect switch. The

voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted the power company and the voltage
condition has been corrected.

6. Set the thermostat for a cooling demand. Turn on pow-

er to the indoor blower and close the outdoor unit dis-
connect switch to start the unit.

7. Recheck voltage while the unit is running. Power must

be within range shown on the nameplate.

Содержание 10ACE Series

Страница 1: ...ox Industries Inc P O Box 799900 Dallas TX 75379 9900 INSTALLATION INSTRUCTIONS 10ACE Series Units CONDENSER UNITS 505 128M 03 06 Supersedes 01 06 Table of Contents 10ACE Outdoor Units 1 Shipping Pack...

Страница 2: ...16 24 1 4 565 048 33 838 32 1 4 819 24 1 4 616 060 33 940 32 1 4 921 24 1 4 718 General Information These instructions are intended as a general guide and do not supersede national or local codes in a...

Страница 3: ...l installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltage power sup...

Страница 4: ...es square free from nicks or dents Debur the ends The pipe must remain round do not pinch end of the line 2 Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage d...

Страница 5: ...he stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Страница 6: ...valve on the high side of the manifold gauge set which will pressurize line set and indoor unit 7 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be det...

Страница 7: ...ig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the HCFC 22 cylinder and remove the manifold gauge set Start Up IMPORTANT If unit is equipped with crankca...

Страница 8: ...iate charging procedure Charge Using Weigh in Method Fixed Orifice TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient temperature is cool use the weigh i...

Страница 9: ...eratures 4 Check the liquid line temperature The difference be tween the ambient and liquid temperatures should match values given in table 6 Loss of charge results in low capacity and efficiency 5 If...

Страница 10: ...ight out to extract the push pins along one side of the coil If necessary remove the push pins along the back of the unit it is usually unnecessary to fully re move the inner mesh screen Drape the mes...

Страница 11: ...cklist Job Name Job no Date Job Location City State Installer City State Unit Model No Serial No Service Technician Nameplate Voltage Rated Load Ampacity Compressor Outdoor Fan Maximum Fuse or Circuit...

Страница 12: ......

Отзывы: