background image

Page 3

10ACE SERIES

Slab Mounting

When installing unit at grade level, install on a level slab
high enough above grade to allow adequate drainage of
water. Top of slab should be located so run−off water from
higher ground will not collect around unit.

*A service clearance of 30" (762 mm) must be maintained on one of
the sides adjacent to the control box. Clearance to one of the other
three sides must be 36" (914 mm). Clearance to one of the remaining
two sides may be 12" (304 mm) and the final side may be 6" (152
mm).

A clearance of 24" (610 mm) must be maintained between two units.
48" (1219 mm) clearance required on top of unit. Maximum soffit over-
hang is 36" (914 mm).

Installation Clearances

Figure 1

(as noted)

(as noted)

(as noted)

(as noted)

.

Roof Mounting

Install the unit at a minimum of 4 inches (102 mm) above
the surface of the roof. Ensure the weight of the unit is
properly distributed over roof joists and rafters. Redwood
or steel supports are recommended.

Electrical

In Canada, wiring must conform with current local codes and
the current Canadian Electrical Code (CEC).

WARNING

Electric Shock Hazard.  Can cause in-
jury or death.

Line voltage is present at all compo-
nents on units with single-pole con-
tactors, even when unit is not in op-
eration!

Unit may have multiple power sup-
plies. Disconnect all remote electric
power supplies before opening ac-
cess panel.

Unit must be grounded in accordance
with national and local codes.

Refer to the furnace or blower coil installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.

1. Install line voltage power supply to unit from a properly

sized disconnect switch.

2. Install line voltage power supply to unit from a properly

sized disconnect switch. Any excess high voltage field
wiring should be trimmed or secured away from the
low voltage field wiring (see figures 2 and 3).

Figure 2

Separating High/Low Voltage Field Wiring

WIRE
TIES

High Voltage
Field Wiring
Low Voltage
Field Wiring
Factory
Wiring

Typical Field Wiring Diagram

Figure 3

(SEE

NOTE)

WARNING! − ELECTRIC SHOCK HAZARD. Can  cause INJURY
or DEATH. Unit must be grounded in accordance with national and
local codes.

NOTE − For use with copper conductors only. Refer to unit rating
plate for minimum circuit ampacity and maximum over-current
protection size.

*

*

*

*−048 &
−060
models

208−230/60/1

GROUND

3. Ground unit at unit disconnect switch or to an earth

ground.

NOTE − To facilitate conduit, a hole is located in the
bottom of the control box. Connect conduit to the con-
trol box using a proper conduit fitting. Units are ap-
proved for use only with copper conductors.
24V, Class II circuit connections are made to the low 
voltage pigtails. Refer to figure 3 for field wiring dia-
gram. A complete unit wiring diagram is located inside
the unit control box cover.

4. Install room thermostat (ordered separately) on an in-

side wall approximately in the center of the conditioned
area and 5 feet (1.5 m) from the floor. It should not be
installed on an outside wall or where it can be effected
by sunlight, drafts or vibrations.

Содержание 10ACE Series

Страница 1: ...ox Industries Inc P O Box 799900 Dallas TX 75379 9900 INSTALLATION INSTRUCTIONS 10ACE Series Units CONDENSER UNITS 505 128M 03 06 Supersedes 01 06 Table of Contents 10ACE Outdoor Units 1 Shipping Pack...

Страница 2: ...16 24 1 4 565 048 33 838 32 1 4 819 24 1 4 616 060 33 940 32 1 4 921 24 1 4 718 General Information These instructions are intended as a general guide and do not supersede national or local codes in a...

Страница 3: ...l installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltage power sup...

Страница 4: ...es square free from nicks or dents Debur the ends The pipe must remain round do not pinch end of the line 2 Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage d...

Страница 5: ...he stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Страница 6: ...valve on the high side of the manifold gauge set which will pressurize line set and indoor unit 7 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be det...

Страница 7: ...ig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the HCFC 22 cylinder and remove the manifold gauge set Start Up IMPORTANT If unit is equipped with crankca...

Страница 8: ...iate charging procedure Charge Using Weigh in Method Fixed Orifice TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient temperature is cool use the weigh i...

Страница 9: ...eratures 4 Check the liquid line temperature The difference be tween the ambient and liquid temperatures should match values given in table 6 Loss of charge results in low capacity and efficiency 5 If...

Страница 10: ...ight out to extract the push pins along one side of the coil If necessary remove the push pins along the back of the unit it is usually unnecessary to fully re move the inner mesh screen Drape the mes...

Страница 11: ...cklist Job Name Job no Date Job Location City State Installer City State Unit Model No Serial No Service Technician Nameplate Voltage Rated Load Ampacity Compressor Outdoor Fan Maximum Fuse or Circuit...

Страница 12: ......

Отзывы: