CARE AND OPERATION
Page 17
Note: The control board is equipped with an internal
memory which will recall the last setting and mode
the stove was in prior to loss of power. Because we
individually check each stove prior to packaging, one
of the two scenarios will appear when you first plug in
your stove.
1). The Green LED at the top of the control board will illu-
minate and the blowers will be running. This is a stan-
dard cool down mode and will last no longer than five
minutes. This happens during testing when the stove is
turned off (which initiates cool down mode) and then is
unplugged.
2). The Green LED at the top will illuminate and the red
and yellow LED’s will illuminate on the control board,
indicating that the stove is in the run mode. This hap-
pens during testing if the stove is unplugged without
first turning the control board off (the control board re-
members its last setting, which was the run mode).
If your stove follows that described in number 2 above,
simply press the ON / OFF button once to turn the stove
off, this will initiate the cool down mode. The stove can be
restarted at any time during the cool down mode by press-
ing the ON / OFF button once.
Start-up Sequence of Events
1. Fault time delay is initiated (14 minutes 15 seconds).
2. Fuel feed rate of 100% for 1 minute 50 seconds (when
trim left at factory setting of 0) auger trim setting ranges
from 1:26 to 2:14 depending on -4 to +4 respectively.
3. Exhaust blower operation starts (medium range volt-
age).
4. Room air blower operation starts (medium range volt-
age).Power LED is activated (steady green).
6. Igniter operation activated (line voltage).
7. Photoeye looks for flame (flame dominance scheme).
8. * If needed second & third fuel dumps are available at
predetermined time deliveries (4 minutes & 6 minutes
after initial).
Flame Detection Sequence of Events -
This is what
happens after flame has been detected.
Happens within the
Start-up Time Delay
sequence.
0 to 1 minute no fuel feed.
Flame settles.
Bed of embers built.
1 minute mark: Fuel Feed rate 20% for 4 minutes
15 seconds (1 second on / 4 seconds off).
2 minute mark: igniter turns OFF / room air blower =
panel setting.
5 minute 15 seconds mark: exhaust blower = panel
setting / LED indicator still active.
Start-up Time delay ends 14 minutes 15 seconds
after pushing the start button!
PHOTOEYE
PN LABEL
LOCATION
POWER
SELECT
MAIN
HARNESS
FUSE
Содержание Traditions T300P Series
Страница 28: ...WIRING DIAGRAM Page 28 ...
Страница 33: ...REPLACEMENT PARTS DIAGRAMS Page 33 1 2 3 4 6 7 8 10 11 12 5 9 ...
Страница 34: ...REPLACEMENT PARTS DIAGRAMS Page 34 14 15 16 17 20 21 22 24 25 23 27 13 18 ...
Страница 36: ...INSTALLATION TIPS Page 36 ...
Страница 37: ...SIMPLE OPERATING INSTRUCTIONS LABEL Page 37 ...
Страница 40: ...1110 West Taft Avenue Orange CA 92865 ...