17

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Pressure
Regulator

Remove
These
Components

Pilot
Orifice

Spring

Adjusting
Screw

Slotted
Cap

P

S

I

OFF

I

ON

CONTROL

IG

N

IT

E

Manifold
Pressure
Test Port

Inlet Pressure Test Port

Retaining

Clip

Ignitor
Assembly

Pilot
Assembly

Pilot
Orifice

Flare Nut

BACK OF FIREPLACE

PAN BURNER

FIREBOX BOTTOM

BURNER POSITIONING

PAN

BURNER

PILOT ASSEMBLY

Figure 33

Figure 32

Figure 31

Figure 30

Figure 29

When reinstalling the ignitor assembly, use
extreme care to prevent damage and break-
age.  Do not apply any leverage to the ignitor
assembly while restoring the retainer clip to
its original position.

Note: If the ignitor is damaged, a replace-
ment kit is available, order Catalog Number
87L54.

Electronic Appliances

Step 7.

 

Honeywell Electronic Valves

 - See

Figure 32 

and the instructions provided with

the kit.  Remove the slotted cap screw, o-ring,
pressure-regulating adjusting screw and
spring.  Retain all parts for possible later use.
Install new components from the kit.  Black
cap and red spring for propane gas units.
Silver cap and stainless steel spring fro natural
gas units.

Before installing the cap, attach manometer
to the manifold side pressure test fitting and
adjust screw until pressure reads 3.5 inches
water column (0.87 kPa) for natural gas, and
10.0 inches water column (2.49 kPa) for
propane gas.

See 

Figure 33

  and replace the pilot orifice as

follows:  Remove the ignitor assembly retainer
clip, and carefully remove the ignitor assembly.

Exercise extreme care to prevent damage to
or breakage of the ignitor assembly

.  Remove

the screw securing the pilot assembly to its
mounting bracket.  Back off the flare nut at the
end of the pilot gas line to free the pilot assem-
bly from the gas line.  Remove the pilot orifice
and replace it with the one provided with the
conversion kit.  Reinstall the pilot assembly by
reversing the 

steps

 detailed here.

Step 6.

  Refer to 

Figure 31 

and remove the

pilot hood assembly to access the hexed pilot
orifice.  Remove and replace the orifice with
the one provided with the kit.

Millivolt Appliances

Step 4.

 

SIT Systems

 - Refer to 

Figure 30 

and

the instructions provided with the kit.  Using a
Torx T20, remove and discard the three pres-
sure regulator mounting screws.  Remove the
pressure regulator, spring, poppet, diaphragm
and bushing.  

Discard all removed compo-

nents

.  Ensure the rubber gasket installed on

the back of the replacement pressure regulator
is properly positioned and install the new pres-
sure regulator using the new screws supplied
with the kit.  Tighten screws to 25 In. lb. torque.

Step 5.

 Attach manometer to the manifold side

pressure test fitting and verify manifold pres-
sure reads 3.5 inches water column (0.87 kPa)
for natural gas, and 10.0 inches water column
(2.49 kPa) for propane gas.

Содержание EBVCLNE

Страница 1: ...rvice dos incendies L installationetservicedoit treex cut parunqualifi installeur agencedeserviceoulefournisseurdegaz B VENT MULTI OPEN ELITE SERIES B VENTED GAS FIREPLACES P N 850 025M REV B 01 2007...

Страница 2: ...c stone and one bag of vermiculate is located in the bottom compartment INTRODUCTION These vented gas fireplaces are designed for residential applications They must be installed with approved type B 6...

Страница 3: ...re not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This ap pliance is not convertible for use with other gases unless a certified kit is...

Страница 4: ...Height from Roof to Lowest Discharge Opening In addition when the unit is installed in the middle of a room the side walls surrounding the unit must not extend beyond the front or rear edge of the un...

Страница 5: ...tronic Appliances Connect 120 Vac electrical power to the appliance receptacle Step 5 page 11 Make connection to gas supply Step 6 page 12 OutsideAirKitInstallation Step 7 page 13 Install the log set...

Страница 6: ...nits is contemplated it should be dis cussed with an architect and the local Build ing Department Do not place insulation materials within 1 in of the gas vent system FIREPLACE FRAMING SPECIFICATIONS...

Страница 7: ...hes millimeters 6 159 9 248 Optional Gas Line Location Center of gas line is 3 in 76 mm up from floor Gas Line Center of gas line is 3 in 76 mm up from floor Minimum Framing Stud size is 2 x 4 41 1054...

Страница 8: ...top 1 2 13 DETAIL OF FINISH WALL BRACKET 13 2 ELECTRICAL INLETS B A B 8 203 DIA FLUE COLLAR 6 175 4 116 4 116 OUTSIDE AIR SHUTTER EBVPF Peninsula 12 305 20 510 TOP VIEW 40 1019 FRAMING SPACERS Top an...

Страница 9: ...2 20 510 OUTSIDE AIR SHUTTER 4 116 B A A 6 152 DIA FLUE OUTLET B 8 203 DIA FLUE COLLAR 13 24 610 6 175 12 305 2 70 3 76 13 41 1041 37 940 24 610 12 305 FRONT VIEW LEFT SIDE VIEW TOP VIEW 4 102 40 101...

Страница 10: ...out Remove the modesty panel care fully so that none of the wires become loose or disconnected 5 Remove the outlet receptacle by remov ing the two securing screws See Figure 17 The left and right desi...

Страница 11: ...in a potential safety hazard The appliance must be electrically grounded in accordance with local codes or in the absence of local codes the National Electrical Code ANSI NFPA 70 latest edition In Ca...

Страница 12: ...duct vertically DO NOT terminate the duct closer than 3 below the chimney top Outside combustion air ducting may be run upwards or vertically through framing and ceiling joists with the hood installe...

Страница 13: ...he pilot The pilot flame should engulf the flame rod as shown in Figure 23 Replace logs after pilot inspection To light the burner turn ON the modesty panel mounted ON OFF switch and rotate the gas va...

Страница 14: ...the operation of this safety limit switch First allow the appliance to cool then reset the safety switch by pushing the red reset button on the back of the switch To access the blocked flue safety li...

Страница 15: ...th of the mantel See Figure 27 Mantels constructed of non combustible materials may be installed at any height above the appliance opening however do not allow anything to hang below the hood Figure 2...

Страница 16: ...L TE JUSQU L OP RATION DE L APPAREIL CONVERTI EST CH QUE SUIVANT LES CRIT RES TABLIS DANS LES INSTRUCTIONS DE PROPRI TAIRE PROVISIONN ES AVEC L QUIPEMENT WARNING THIS CONVERSION KIT SHALL BE INSTALLED...

Страница 17: ...and 10 0 inches water column 2 49 kPa for propane gas See Figure 33 and replace the pilot orifice as follows Remove the ignitor assembly retainer clip andcarefullyremovetheignitorassembly Exercise ex...

Страница 18: ...placeitwiththeoneprovidedinthe kit See the following table for orifice sizes for natural and propane models Figure 34 illustrates the orifice B InstalltheburnersasshowninFigure29 The primary air openi...

Страница 19: ...19 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE NOTES...

Страница 20: ...0 025M REV B 01 2007 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products C...

Отзывы: