Lennox Hearth Products EBVCLNE Скачать руководство пользователя страница 12

12

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Figure 20

Figure 19 - 

GAS CONNECTION

These appliances are equipped with a gas flex
line for use (where permitted) in connecting the
unit to the gas line. A gas flex line is provided to
aid in attaching the B-vent appliance to the gas
supply. The gas flex line can only be used where
local codes permit. See 

Figure 19

  for flex line

description. The flex line is rated for both natu-
ral and propane gas. A manual shut off valve is
also provided with the flex line.

The gas control valve is located in the lower
control compartment. To access the valve
proceed as follows:

1

- Open the control compartment access panel,

(Figure 20 )

 by actuating the spring-loaded

magnetic catches securing the panel, gently
depressing the outer top corners of the panel
until the catches "pop" the panel free and
allowing it to swing out and down to open.

2

- Remove the bottom control compartment

access panel by compressing the spring-
loaded hinge pin on the left side until it
disengages from the left cabinet panel  hole.
Pull the panel away from the fireplace. 

See

Figure 20.

3

- Remove the modesty panel by pulling the

bottom edge of the modesty panel out of
the locking slots of the cabinet bottom.
Then tilt the top edge at a 45

°

 angel and

lift out. Remove the modesty panel care-
fully, so that none of the wires become
loose or disconnected.

The millivolt control valve has a 

³⁄₈

"

(10 mm) NPT thread inlet port. The electronic
control valve has a 

¹⁄₂

" (13 mm) NPT thread inlet

port and is fitted with a 

¹⁄₂

" x 

³⁄₈

" (13 mm x

10 mm) NPT fitting.

Secure all joints tightly using appropriate
tools and sealing compounds (ensure pro-
pane resistant compounds are used in pro-
pane applications).

Step 6. Outside Air Kits – 

Optional  outside make-

up air kits, Model FOAK-4 or FAOK-4LD, may be
used with these appliances.  Refer to the installa-
tion instructions packaged with the air kits for
specific installation information. If used, the out-
side air kit must be installed before the fireplace is
framed and enclosed in the finished wall.

Outside air drawn into the fireplace supplies
air to the fire for combustion. Only one outside
air duct is necessary, if installed. See the

Figures on pages 8, 9 and 10  

for the location

of the units outside air inlet.

If additional length of duct is necessary, pur-
chase locally available U.L. Class 0 or Class 1
metallic ducting. The duct may extend up to 50'
(15.24 m) in any direction.

Note: 

When installing the air duct vertically,

DO NOT 

terminate the duct closer than 3'

below the chimney top.

Outside combustion air ducting may be run
upwards or vertically through framing and
ceiling joists, with the hood installed through
an outside wall and 3' (1 m) below the termi-
nation. Ducting may also be run downward
through floor 

J

oists and under the home to a

ventilated crawlspace not considered part of
the living area of the home.

Note: Do not terminate outside air kit in attic
space under any circumstances.

Turn on gas supply and test for gas leaks using
a soapy water solution. 

Never use an open

flame to check for leaks

.

A.

 Mix a 50% dish soap, 50% water solution.

B.

 Light the appliance (refer to the lighting

instructions provided in the Homeowner's Care
and Operation Instructions).

C.

 Brush all joints and connections with the

soapy water solution to check for leaks. If
bubbles are formed, or gas odor is detected,
turn the gas control knob to the “OFF” posi-
tion. Either tighten or refasten the leaking
connection and retest as described above.

D. 

When the gas lines are tested and leak free,

observe the individual tongues of flame on the
burner. Make sure all ports are open and
producing flame evenly across the burner. If
any ports are blocked, or partially blocked,
clean out the ports.

CAUTION: NEVER LOCATE INLET WHERE IT
CAN BE BLOCKED BY SHRUBS, SNOW
DRIFTS, ETC. NEVER LOCATE INLET IN GA-
RAGE OR ANY AREA WHERE THERE IS AN-
OTHER FUEL BURNING APPLIANCE OR PROD-
UCTS EMITTING COMBUSTIBLE GASES SUCH
AS PAINT, GASOLINE, ETC. IN COLD CLI-
MATES, IT IS RECOMMENDED THE COMBUS-
TION AIR DUCT BE INSULATED.

The hand operated outside air control lever is
located on the right side (EBVST, EBVPF, and
EBVCL)  or left side (EBVCR) of the fireplace
opening. 

See Figure 21 on page 13.

To open the outside air shutter, open the bottom
control access panel, reach into the gap between
the firebox bottom and the modesty panel,  and
pull the outside air control lever all the way out.

After completing the installation of the op-
tional outside air vent system, the outside air
control lever must be put in service and tested
to ensure proper operation before completing
any enclosure around the firebox.  Failure to
do so may result in extensive and costly re-
work. Before the operation of the vent system
can be tested, the lever securing screw must
be removed. 

See Figure 21 on page 13.

Gas Stub

¹₂

" x

 

³₈

" Flare

Shut-Off Valve

³₈

 Flex Tubing

³₈

" NPT 

₂ ³₈

Flare Fitting

³₈

" Nipple

³₈

"

 

Union

³₈

" Close Nipple

³₈

" Shut-Off Valve

¹₂

 x 

³₈

 

"

Reducer

Gas
Valve

Gas Flex Line Connector

Piezo
Ignitor

Gas Valve

Modesty
Panel

Control

Compartment

Access panel

ON/OFF
 Switch

Hinge
Pin

Modesty Panel
Lock Slot

Содержание EBVCLNE

Страница 1: ...rvice dos incendies L installationetservicedoit treex cut parunqualifi installeur agencedeserviceoulefournisseurdegaz B VENT MULTI OPEN ELITE SERIES B VENTED GAS FIREPLACES P N 850 025M REV B 01 2007...

Страница 2: ...c stone and one bag of vermiculate is located in the bottom compartment INTRODUCTION These vented gas fireplaces are designed for residential applications They must be installed with approved type B 6...

Страница 3: ...re not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This ap pliance is not convertible for use with other gases unless a certified kit is...

Страница 4: ...Height from Roof to Lowest Discharge Opening In addition when the unit is installed in the middle of a room the side walls surrounding the unit must not extend beyond the front or rear edge of the un...

Страница 5: ...tronic Appliances Connect 120 Vac electrical power to the appliance receptacle Step 5 page 11 Make connection to gas supply Step 6 page 12 OutsideAirKitInstallation Step 7 page 13 Install the log set...

Страница 6: ...nits is contemplated it should be dis cussed with an architect and the local Build ing Department Do not place insulation materials within 1 in of the gas vent system FIREPLACE FRAMING SPECIFICATIONS...

Страница 7: ...hes millimeters 6 159 9 248 Optional Gas Line Location Center of gas line is 3 in 76 mm up from floor Gas Line Center of gas line is 3 in 76 mm up from floor Minimum Framing Stud size is 2 x 4 41 1054...

Страница 8: ...top 1 2 13 DETAIL OF FINISH WALL BRACKET 13 2 ELECTRICAL INLETS B A B 8 203 DIA FLUE COLLAR 6 175 4 116 4 116 OUTSIDE AIR SHUTTER EBVPF Peninsula 12 305 20 510 TOP VIEW 40 1019 FRAMING SPACERS Top an...

Страница 9: ...2 20 510 OUTSIDE AIR SHUTTER 4 116 B A A 6 152 DIA FLUE OUTLET B 8 203 DIA FLUE COLLAR 13 24 610 6 175 12 305 2 70 3 76 13 41 1041 37 940 24 610 12 305 FRONT VIEW LEFT SIDE VIEW TOP VIEW 4 102 40 101...

Страница 10: ...out Remove the modesty panel care fully so that none of the wires become loose or disconnected 5 Remove the outlet receptacle by remov ing the two securing screws See Figure 17 The left and right desi...

Страница 11: ...in a potential safety hazard The appliance must be electrically grounded in accordance with local codes or in the absence of local codes the National Electrical Code ANSI NFPA 70 latest edition In Ca...

Страница 12: ...duct vertically DO NOT terminate the duct closer than 3 below the chimney top Outside combustion air ducting may be run upwards or vertically through framing and ceiling joists with the hood installe...

Страница 13: ...he pilot The pilot flame should engulf the flame rod as shown in Figure 23 Replace logs after pilot inspection To light the burner turn ON the modesty panel mounted ON OFF switch and rotate the gas va...

Страница 14: ...the operation of this safety limit switch First allow the appliance to cool then reset the safety switch by pushing the red reset button on the back of the switch To access the blocked flue safety li...

Страница 15: ...th of the mantel See Figure 27 Mantels constructed of non combustible materials may be installed at any height above the appliance opening however do not allow anything to hang below the hood Figure 2...

Страница 16: ...L TE JUSQU L OP RATION DE L APPAREIL CONVERTI EST CH QUE SUIVANT LES CRIT RES TABLIS DANS LES INSTRUCTIONS DE PROPRI TAIRE PROVISIONN ES AVEC L QUIPEMENT WARNING THIS CONVERSION KIT SHALL BE INSTALLED...

Страница 17: ...and 10 0 inches water column 2 49 kPa for propane gas See Figure 33 and replace the pilot orifice as follows Remove the ignitor assembly retainer clip andcarefullyremovetheignitorassembly Exercise ex...

Страница 18: ...placeitwiththeoneprovidedinthe kit See the following table for orifice sizes for natural and propane models Figure 34 illustrates the orifice B InstalltheburnersasshowninFigure29 The primary air openi...

Страница 19: ...19 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE NOTES...

Страница 20: ...0 025M REV B 01 2007 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products C...

Отзывы: