Hardware Components

20 — 

revision 1.007

3

NGP Controller

Note:

Any expansion modules used with the NGP system, like the 8 Point and 16 Point Expanders, 
can also be used on the NGP Main Control Unit, Module Bus (SNAPP).

3.1

Mounting a Control Box

On Dry Wall: 

1. Use 1/8 in. hollow wall, expansion anchors. 

2. Unscrew the screws from the anchors. 

3. Hold the control box on the mounting surface. 

4. Mark the mounting holes. 

5. Force a starter hole in each mark with a sharp tool, e.g., a screw driver with a small, flat edge. 

6. Hammer the anchors into each hole. 

7. Align the box mounting holes over the anchor holes and screw in the anchor screws until tight.

On Concrete Surface: 

1. Hold the control box on the mounting surface. 

2. Mark the mounting holes. 

3. Use a hammer drill with a 3/16 in. carballoy drill bit and make 1 in. deep holes in each marking.

4. Insert a # 6-8 plastic anchor in each hole and hammer them in. 

5. Use # 8 x 1 in., Phillips, wood screws to screw into the plastic anchors and mount the box.

3.2

Control Box Dimensions

The dimensions of the control box enclosure, with the cover closed, are H 537 mm x W 343 mm x D 106 
mm (H 21.14 x W 13.50 x D 4.17 inches).

Please refer to the 

NGP Hardware Installation Guide 55-60000E, 

section 

Enclosure

, for more detailed 

information.

Содержание OnGuard 2013

Страница 1: ...PERPETUAL INNOVATION 2013 NGP Keypad Installation Guide...

Страница 2: ...s that the product is free from defects in material and workmanship under normal use and service with proper maintenance for one year from the date of factory shipment Lenel assumes no responsibility...

Страница 3: ...tralia 9 3 CE Conformity 9 Hardware Components 11 1 LCD Keypad Overview 13 2 LCD Keypad Notes 18 2 1 When a Keypad Is First Powered 18 2 2 Main Test Menu Selections 18 2 3 User s Access Card Quick Enr...

Страница 4: ...9 1 Installation Notes 43 9 2 Programming Notes 43 10 UL Systems Requirements 44 10 1 Entry and Exit Delays 44 10 2 Testing 44 10 3 Partitioned Systems 44 11 Alarms 44 11 1 Burglar Alarm Local 44 11...

Страница 5: ...COMPLIANCE STATEMENTS...

Страница 6: ......

Страница 7: ...ices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed five 5 The REN for the NGP using the North American Modem is 0 1 The REN for the...

Страница 8: ...The REN for the NGP using the Worldwide Modem is 0 0 2 2 Cautions If this equipment NGP is deemed potentially harmful to the telephone network the telephone company will attempt to notify you in adva...

Страница 9: ...transformer wired into a protected branch circuit Only certified transformers should be used whose output is designated as SELV The current draw from these units should not exceed 1 8 Amps refer to th...

Страница 10: ...Compliance Statements 10 revision 1 007...

Страница 11: ...HARDWARE COMPONENTS...

Страница 12: ......

Страница 13: ...m Depth 1 0 in 2 54 cm Ratings LCD Keypad with Reader Input 12 VDC 110 mA Output 12 VDC 1x10 mA LCD Keypad Input 12 VDC 95 mA Output 12 VDC 1x10 mA Temperature for both 10 C to 55 C 14 F to 131 F 93 T...

Страница 14: ...Button Apply the Alert Button labels as required 5 Point 2 Alert Button 6 Point 1 Alert Button 7 Apply dealer s logo label supplied in the indented space at the top of the keypad Module Point Assignm...

Страница 15: ...he keypad on its back section make sure the keypad s securing screws supplied are always in 4 Tamper Spring 5 Sonalert 6 Circuit Board Pin Connectors Insert circuit board pin connectors into fixed ter...

Страница 16: ...d 13 Module Bus 14 Module Bus 15 Wiegand 16 Point 4 7 17 Point 4 5 18 Input 1 19 Common 20 Input 2 21 Wiegand Reader Data 1 and 0 No reader LED connection 22 Future 23 Output Keypad Output goes negati...

Страница 17: ...e same hole as it was attached so the back cover fits over it The plastic cylinder prevents the tamper spring from being affected by flat objects wedged in behind the keypad The additional keypad base...

Страница 18: ...ng press any number key five 5 times to display the Main Test Menu This screen will also display the current module bus power Keypad tone volume adjustment Use the left and right arrow keys to indicat...

Страница 19: ...ample A Standard LCD keypad assigned as the first module on the module bus For all inputs to be used on this keypad eight 8 inputs must be assigned The first three 3 inputs are assigned to the keypad...

Страница 20: ...nto each hole 7 Align the box mounting holes over the anchor holes and screw in the anchor screws until tight On Concrete Surface 1 Hold the control box on the mounting surface 2 Mark the mounting hol...

Страница 21: ...ll field wiring connections for readers door controllers relays and other inputs Please refer to the NGP Hardware Installation Guide 55 60000E section Next Generation Panel for more details The LCD ke...

Страница 22: ...e 23 This configuration is only supported using a keypad that specifically supports external readers Note that there is no connection for reader buzzer and LED Only the first two card formats assigned...

Страница 23: ...revision 1 007 23 Keypad and External Reader Wiring 1 RS 485 bus on NGP CN23 CN26 2 Ground 3 Data B 4 Data A 5 Power 6 Reader 7 Ground 8 Data B 9 LED no connection 10 LED no connection 11 Data 0 12 Da...

Страница 24: ...with an NGP LCD keypad refer to the NGP LCD Keypad Programming Reference Guide The CPU Failure feature is available with main control module firmware version 4 3 or greater For more information pleas...

Страница 25: ...Seized Ring 7 Tip 8 Ring 9 Jumpers Two 2 vertical Jumpers in 1 2 Output 8 will be 12 VDC high from 0 V if main control board CPU fails Two 2 vertical Jumpers in 2 3 Output 8 will be 0 V low from 12 VD...

Страница 26: ...oing to Negative 0V or Negative 0V going to Positive 12 VDC Default Positive Advanced Configurations S005 03 Field 2 Parallel STU 8OP Supports Line Fail yes no Default no UK ACPO yes Field 3 Parallel...

Страница 27: ...500 mA Module Bus 14 VDC 400 mA Total current draw with the auxiliary and module bus must not exceed 650 mA Europe For units that include the mains transformer within the control cabinet INPUT 230 VA...

Страница 28: ...Hardware Components 28 revision 1 007...

Страница 29: ...PROGRAMMING THE SYSTEM...

Страница 30: ......

Страница 31: ...d s serial number are left and right arrows These represent the left and right arrow keys lower down on the keypad These arrow keys are used to browse through menus If the arrow keys are pressed in th...

Страница 32: ...lia New Zealand and China H K Hong Kong 6 1 2 Selecting North America If North America is selected the screen will ask the number of users that will be operating the system Use the left and right arro...

Страница 33: ...000 the next screen will request a Pin of the Day to log on After that is entered a secondary user code will be requested The Master user codes can be used again 6 1 4 UK ACPO Pin of the Day The serv...

Страница 34: ...d dial tone For Tone dialing ensure the phone line supports this As the phone number is entered the cursor will automatically move to the next character entry position Use the left and right arrow key...

Страница 35: ...igurations using the keypad To enable this feature Config Dial Out is set to 1 in Advanced program section S005 10 2 Log on to the keypad as a system or service user 3 Push the right arrow key for Men...

Страница 36: ...Programming the System 36 revision 1 007...

Страница 37: ...DIAGNOSTICS...

Страница 38: ......

Страница 39: ...right arrow keys on the keypad the Status options can be scrolled to display several system conditions When the desired one to view is displayed press Ok Status Options System Ok Keypad Status Diagnos...

Страница 40: ...Diagnostics 40 revision 1 007...

Страница 41: ...UL LISTED SYSTEMS...

Страница 42: ......

Страница 43: ...gnates an alert signal Do not program as a fire or burglary signal Audible alarm designations Fire 3 pulse temporal Burglary Steady Alert Beeping 9 2 Programming Notes For central station and police c...

Страница 44: ...y even have different addresses but are under the responsibility of someone having mutual interest other than the alarm installing company This does not apply to strip mall applications where each ind...

Страница 45: ...o the alarm housing so that an alarm is produced if the cable is severed or disconnected 6 When the system is placed on duty a timer in the system shall prevent the turning off prior to a time set by...

Страница 46: ...ocal burglar alarm above System supplies standard line security DACT when used with IP Module 650 9060 as defined in UL 365 11 5 Burglar Alarm Central Station Grade C Dact Grade AA Packet Switched Dat...

Страница 47: ...ne relay The circuit shall also be terminated with a Model 166 6841 end of line resistor 11 8 Household Burglar Alarm 1 Refer to Grade A local burglar alarm above for maximum standby and loading condi...

Страница 48: ...UL Listed Systems Notes and Requirements 48 revision 1 007...

Страница 49: ...ay UL 44 F Fire alert button 14 K Keypad 13 Keypad module point assignment 14 Keypad serial number 18 Keypad terminal block wiring 15 L LEDs 14 M Main test menu 18 Mains supply 9 Mounting a control bo...

Страница 50: ...Index 50 revision 1 007...

Страница 51: ...Lenel Systems International Inc 1212 Pittsford Victor Road Pittsford New York 14534 USA Tel 585 248 9720 Fax 585 248 9185 www lenel com docfeedback lenel com...

Отзывы: