Troubleshooting and Maintenance
102
M3000 Installation Guide
b.
Disconnect connector J6 from the Power/Communications board. Use an ohmmeter to check
the resistance between pins 3 and 4. If the resistance is less than 200 ohms, there is a short
from power to ground. Isolate the fault by doing the following:
–
Remove all boards from the backplane except the Power/Communications and CPU
boards. Add each board while measuring the resistance on J6 pins 3 and 4. When the
resistance falls below 200 ohms while a board is plugged in, isolate the board. Continue
checking the remaining boards for other ground faults.
–
Remove connectors one by one on the faulty boards until the fault condition disappears
(resistance goes above 200 ohms). Trace out wiring on these connectors to find and
correct the problem.
Reader Problems
Consult your reader installation manual for potential problems which are not related to the M3000
controller. Also refer to the following sections of this manual:
•
•
•
Using the 2RP Board
Problem:
The reader does not power up.
Resolution
:
1.
Be sure that JP1 on the 2RP board is set in the proper voltage selection location. Refer to
.
• WARNING! •
Do not set W1 to 12 V for a 5 V reader. Permanent damage may result to the
reader.
2.
Be sure that the proper resistor packs are installed in the 2RP board. Refer to
3.
Check the wiring between the 2RP board and the reader. Refer to
reader installation manual.
4.
Be sure the connector is firmly seated in the 2RP board.
Problem:
The reader has power, but the Badge Read OK LED on the CPU board does not light up
when a badge is presented.
Resolution
:
1.
Be sure the resistor packs are installed and are the correct value for the reader type being used.
2.
Be sure that the switch settings on the 2RP board for address and reader technology/format are
correct. Refer to
3.
Check the wiring between the reader and the 2RP board. Refer to
and the
reader installation manual.
Using the 2SRP Board
Problem:
The reader does not power up.
Resolution
:
1.
Be sure that JP1 on the 2SRP board is set in the proper voltage selection location. Refer to
Содержание m3000
Страница 1: ...7 3 M3000 Installation Guide...
Страница 4: ......
Страница 14: ...Introduction 14 M3000 Installation Guide...
Страница 24: ...Power Communications Board 24 M3000 Installation Guide Power Communications Board Layout Power Setup...
Страница 30: ...Power Communications Board 30 M3000 Installation Guide...
Страница 32: ...PXNplus CPU Board 32 M3000 Installation Guide PXNplus CPU Board Layout...
Страница 38: ...Reader Processing Boards 38 M3000 Installation Guide 2RP Board Layout 2RP Board Layout...
Страница 50: ...Reader Processing Boards 50 M3000 Installation Guide 2SRP Board Layout 2SRP Board Layout...
Страница 55: ...M3000 Installation Guide 55 2SRP Board 2SRP Supervised Reader Connector Points...
Страница 57: ...M3000 Installation Guide 57 2SRP Board Wiring 2SRP to Wiegand F 2F Strobed and Supervised F 2F Reader...
Страница 61: ...M3000 Installation Guide 61 2SRP Board Wiring 2SRP Door Strike Internal Relay...
Страница 65: ...M3000 Installation Guide 65 8RP Board Board Layout 8RP Board Layout...
Страница 70: ...Reader Processing Boards 70 M3000 Installation Guide...
Страница 72: ...Optional DI and DO Boards 72 M3000 Installation Guide 20DI Board Layout 20DI Board Layout...
Страница 75: ...M3000 Installation Guide 75 16DO and 16DOR Boards 16DO Board Layout...
Страница 76: ...Optional DI and DO Boards 76 M3000 Installation Guide 16DOR Board Layout...
Страница 80: ...Pre Power Up Testing 80 M3000 Installation Guide...
Страница 99: ...M3000 Installation Guide 99 CE Regulatory Notice CE Regulatory Notice...
Страница 100: ...Regulatory Information 100 M3000 Installation Guide...
Страница 110: ...110 M3000 Installation Guide...
Страница 114: ...114 M3000 Installation Guide Resistances Detected by PXNplus...
Страница 117: ...M3000 Installation Guide 117 Index...