25
Control loop:
After turning the function rotary switch, the voltage display mode is reached. Pushing
"DISPLAY" now calls up the control loop. According to the selected measuring
function, different setting values can be displayed and changed in the control loop.
The "DISPLAY" button switches between the different set values inside a contiuous
loop. The "SELECT
" button selects the decimal point to be changed. Pushing the
"CHANGE
" button the instrument either switches between certain set values or
increases the decimal point selected with "SELECT
" by 1.
After parmeter setting has been finished the next display can be called with
"DISPLAY" or the measurement can be started with "START" .
Depending on the selected function, the following parameters can be displayed or
changed:
Function Parameter
Setting
range
Remarks
U
ST
display
only
F
ST
display
only
RE 3pole
FM (AFC/94/105/111/128)Hz
UM
48 V/20 V
lockable to 20 V with CODE
and RK
0.000
Ω
... 29.99
Ω
in position RE 3pole only *
RE LIMIT
0.000
Ω
... 999 k
Ω
only if activated with CODE
RE 4pole
(warning- On/Off
only if RE LIMIT
sound)
is activated with CODE
R*
On/Off
only if activated with CODE
U
ST
display
only
F
ST
display
only
RE 3pole
FM (AFC/94/105/111/128)Hz
UM
48 V/20 V
lockable to 20 V with CODE
and RK
0.000
Ω
... 29.99
Ω
in position RE 3pole only *
RE 4pole
I ( ratio )
80 ... 1200
display only
RE LIMIT
0.000
Ω
... 999 k
Ω
only if activated with CODE
(warning- On / Off
only if RE LIMIT
sound)
is activated with CODE
R*
On / Off
only if activated with CODE
* ( see chapter 8.4.4 )
Содержание A188506510
Страница 1: ...Operating Instructions EARTH GROUND TESTER SATURN GEO X ...
Страница 18: ...16 300 Ω 2999 Ω 1 Ω ...
Страница 20: ...18 16 15 14 10 4 5 9 8 6 3 7 2 1 11 12 13 back Rückseite derrière ...
Страница 65: ...63 Notes ...