11
Measurement of interference voltage DC + AC (UST)
Measuring method:
fullwave rectification
Measuring
range
Display
range
Resolution
Frequency range
Limits of error
1…50 V
0.0…50 V
0.1 V
DC/AC 45…400 Hz sine
± (5% of mv +5 digit)
Measuring sequence:
approx. 4 measurements /s
Internal resistance:
approx. 1.5 M
Ω
Max. overload:
Urms = 250 V
Measurement of interference frequency (FST)
Measuring method:
Measurement of oscillation period of the
interference
voltage
Measuring range
Display range
Resolution
Range
Limits of error
16.0 … 400 Hz
16.0…299.9…999 Hz 0.1 … 1Hz 1 V … 50 V
± (1% v. mv +2 digit)