18
Functional description: Elevator
alarm
Routine call overdue accordi ng to EN81-28:2018
Alternati ng flashi ng of the EN81-70 symbols yellow/green (from version
8.51), if no routine call has been received during the l ast time period P.25
Elevator emergency call
If the emergency call is triggered by pressing the emergency button for at
least one second
☞
P.24 the yellow indicator is acti vated. EXICALL® EN70
dials the programmed number(s) and established a hands-f ree connection.
When the call ed party sends DTMF command
1
. the LED „Speak “ is
acti vated.
AN NO U NCEM E NT
„Emergency call activated. You are about to be connected“
Call button backlight
To acti vate the push-button backlight short the two BE L terminals.
Misuse-Protection (S1)
The misuse protection signal is used to separate real emergency calls.
Duri ng the maximum duration of cabin travel
☞
P.24 you will hear the
announcement:
AN NO U NCEM E NT
„Emergency call activated. You are about to be connected.“
If the door state changes during this timeout you will hear:
AN NO U NCEM E NT
„Door is open. Emergency call deacti vated. Alarm
acknowledged“
If the door state does not alter during this timeout EXICALL® EN70 starts
to di al the calling number(s) playing
AN NO U NCEM E NT
„Emergency call activated“
Factory setti ng for misuse timeout: 30 seconds.
☞
P.24
Misuse-protection is onl y availabl e w hen suppl y voltage is applied.
Connection to building control system.
☞
P.19
There are two ways to connect misuse-protection si gnal:
1. Connect voltage following the
2. Use supply voltage SP and connect
door state between S1 and SCOM.
door contact.
S1
SCOM
active: 10 V - 40 V AC/DC
Door contact
S1
SP
SP
SCOM