INSTALLATION

Determine an appropriate mounting location inside the light fixture 

minimizing the electric light contribution to the sensor’s photocell. 

Allow a minimum distance of 0.2” (5.1mm) from the wiring end of the 

sensor to the wall of the fixture. 
There are two mounting methods for the FSP-212—using the threaded collar or using the snap-in tabs.

Threaded Collar Mounting

1.  Drill a hole 1.30” (33.0mm) in diameter through the sheet metal in 

the bottom of the fixture.

2.  Add the rubber gasket to the threaded collar, and install the sensor 

face down, parallel to the mounting surface. Ensure the rubber 

gasket touches the inside surface of the fixture. Install the plastic 

nut securely against the fixture to a torque of 25-30 in-lbs to 

ensure IP rating is maintained. 

3.  Align the locking features between the sensor and lens module 

and push the lens module forward until the o-ring seals firmly. Turn 

the lens module clockwise to ensure it locks in place.

4.  Connect wires as shown in wiring diagram.
5.  Restore power from the circuit breaker.

NOTE: 

An optional skirt can be installed in place of the tightening nut. 

See the 

Ordering Information

 table on page 4 for details.

Snap-In Mounting

1.  Cut a rectangular hole 32.6mm (± 0.2mm) by 89.9mm (± 0.2mm) 

through the sheet metal in the bottom of the fixture. The surface of 

the bottom of the fixture must be between .75mm and 3.2mm.

2.  Push the FSP-212 up from the below the fixture until the tabs 

“snap” and the fixture locks in place.

3.  Align the locking features between the sensor and lens module and 

push the lens module forward until the o-ring seals firmly. Turn the 

lens module clockwise to ensure it locks in place.

4.  Connect wires as shown in wiring diagram.
5.  Restore power from the circuit breaker.

NOTE: 

Snap-in mounting is not rated for IP66.

OUTDOORS—USE AT THE EXPOSED SENSOR COLLAR PART ONLY WHEN INSTALLED AT THE SPECIFIC 

LOCATION PER INSTALLATION INSTRUCTIONS WITH A LISTED OUTDOOR ENCLOSURE.

Threaded Collar Mounting

Fixture 

Wall

Lens Assembly

FSP-212

Outside 

Fixture Wall

Inside Fixture

Wall

89.9mm (± 0.2mm)

32.6mm (± 0.2mm)

Fixture Bottom

Cutout for snap-in mounting

Snap-in Mounting

WARNING

TURN THE POWER OFF AT THE CIRCUIT BREAKER 

BEFORE INSTALLING THE SENSOR.

Tightening

Nut

Tightening

Nut

Fixture 

Wall

Lens Assembly

FSP-212

Outside 

Fixture Wall

Inside Fixture

Wall

Rubber

Gasket

Rubber

Gasket

Dimming

Driver

LINE

NEUTRAL

NEUTRAL

GRAY (-)

VIOLET (+)

LOAD

Non-Dimming

Driver

LINE

NEUTRAL

NEUTRAL

LOAD

Note: Dim Level functionality does not 

apply when wired  as shown above.

Содержание Wattstopper FSP-212

Страница 1: ...vides easy to use selectable modes with several adjustable parameters The FSP 212 offers four different control modes of operation plus service and test modes that can be selected using a rotary pot O...

Страница 2: ...4 for details Snap In Mounting 1 Cut a rectangular hole 32 6mm 0 2mm by 89 9mm 0 2mm through the sheet metal in the bottom of the fixture The surface of the bottom of the fixture must be between 75mm...

Страница 3: ...de E and Test Mode fade up and fade down time is 0 seconds Mode A Outdoor Parking Area Keeping Minimum Light Level at Night Features Always ON during the night ON at dusk Low Dim maintains minimum lev...

Страница 4: ...min 1 2 of set value during Low Trim Occupancy detected One half time delay expired Mode D Yes High Dim 30sec 30 min Ambient light level below daylight control level and occupancy detected Time delay...

Страница 5: ...ambient temperature conditions so ensure the installed location has good ambient temperature If lights still do not turn OFF call 800 879 8585 for technical support ORDERING INFORMATION Catalog Descr...

Страница 6: ...rents en plus des modes service et test qui peuvent tre s lectionn s avec un potentiom tre rotatif Une fois d marr chaque mode poss de un ensemble de param tres r gl s par d faut De plus les r glages...

Страница 7: ...nts de verrouillage entre le capteur et le module de lentille et poussez le module de lentille vers l avant jusqu ce que les joints toriques soient fermement scell s Tournez la lentille dans le sens d...

Страница 8: ...anent fois 0 secondes Mode A Zones de stationnement ext rieur maintenant un niveau de lumi re minimum durant la nuit Caract ristiques Toujours en marche durant la nuit en marche au cr puscule la grada...

Страница 9: ...rche en mode automatique Arr t automatique Mode A Oui Gradation faible Niveau par d faut Min 1V 30 sec 30 min D faut 15 min Niveau de lumi re ambiante sous le niveau de r gulation de la lumi re du jou...

Страница 10: ...condes Si les lumi res ne s teignent toujours pas consultez Niveau de gradation ou appelez au 1 800 879 8585 pour obtenir du soutien technique Les lumi res ne s teignent pas Veillez ce que le FSP 212...

Страница 11: ...uatro modos de control de funcionamiento diferentes m s modos de prueba y de servicio que se pueden seleccionar mediante el uso de un potenci metro giratorio Una vez activado cada modo tiene un conjun...

Страница 12: ...ADO Balasto Regulador Controlador L NEA NEUTRO NEUTRO GRIS VIOLETA CARGA Balasto No Regulador L NEA NEUTRO NEUTRO CARGA Nota Funcionamiento de nivel de atenuaci n queda desabilitado cuando se cablea d...

Страница 13: ...tinuaci n se apaga despu s del retardo apagado en la madrugada Cuando la luz ambiental se encuentra por debajo del nivel de control de luz diurna y se detecta la ocupaci n el sensor enciende las carga...

Страница 14: ...or establecido durante el ajuste bajo Ocupaci n detectada Medio retardo de tiempo caducado Modo D S Regulaci n baja 30 s 30 min Nivel de luz ambiental por debajo del nivel de control de luz diurna y s...

Страница 15: ...dos y luego se apagar n despu s de 2 5 segundos Si las luces todav a no bajan al nivel de regulaci n llame al 800 879 8585 para obtener soporte t cnico Las luces no se apagan Aseg rese de que la unida...

Отзывы: