• 08: Bypass mode setting
Interface
Setting
Parameter 2:
OPN: Bypass allowed. When selected, UPS will run at Bypass
mode depending on Bypass enabled/disabled setting.
FBD: Bypass not allowed. When selected, it’s not allowed for
running in Bypass mode under any situations.
Parameter 3:
ENA: Bypass enabled. When selected, Bypass mode is activated.
DIS: Bypass disabled. When selected, automatic Bypass
is acceptable, but manual Bypass is not allowed. Manual
Bypass means users manually operate UPS for Bypass mode.
For example, pressing OFF button in AC mode to turn into Bypass
mode.
• 09: Battery maximum discharge time setting
Interface
Setting
Parameter 3:
000~999: Set the maximum discharge time from 0 min-999
min. UPS will shut down to protect battery after discharge time
arrives. The default value is 990 min.
DIS: Disable battery discharge protection and backup time will
depend on battery capacity.
• 10: Reserved
Interface
Setting
Reserved
• 11: Reserved
Interface
Setting
Reserved
• 12: Reserved
Interface
Setting
Reserved
• 13: Battery voltage calibration
Interface
Setting
Parameter 2: Select ‘Add’ or ‘Sub’ function to calibrate battery
voltage to real figure.
Parameter 3: The voltage range is from 0 V to 5.7 V, the default
value is 0 V.
• 14: Charger voltage adjustment
Interface
Setting
Parameter 2: You may choose ‘Add’ or ‘Sub’ to adjust charger
voltage
Parameter 3: The voltage range is from 0 V to 6.4 V, the default
value is 0 V.