5/6
kVA
FM
5/6
kVA
FMI
7.5/10
kVA
FM
7.5/10
kVA
FMI
7.5/10K FMI C
7.5/10
kVA
FM C
• Pay careful attention to the rated battery voltage marked on the rear panel. If you want to change the numbers
of the battery pack, please make sure you modify the setting simultaneously. The connection with wrong
battery voltage may cause permanent damage of the UPS. Make sure the voltage of the battery pack is correct.
• Pay careful attention to the polarity marking on external battery terminal block and make sure the correct
battery polarity is connected. Wrong connection may cause permanent damage to the UPS.
• Make sure the protective earth ground wiring is correct. The current spec, colour, position, connection and
conductance reliability of wire should be checked carefully.
• Make sure the utility input and output wiring is correct. The current spec, colour, position, connection and
conductance reliability of wire should be checked carefully. Make sure the L/N terminal is correct, not
reversed or short-circuited.
2-4 Software Installation
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown.
3. Operations
3-1. Button Operation
Button
Function
ON/Enter
Button
Turn on the UPS: Press and hold the button more than 0.5 sec to turn on
the UPS.
Enter Key: Press this button to confirm the selection in setting menu.
OFF/Esc
Button
Turn off the UPS: Press and hold the button more than 0.5 sec to turn off the UPS.
Esc key: Press this button to return to last menu in setting menu.
Test/Up Button
Battery test: Press and hold the button more than 0.5 sec to test the
battery while in AC mode or CVCF mode.
UP key: Press this button to display next selection in Setting menu.
Mute/Down
Button
Mute the alarm: Press and hold the button more than 0.5 sec to mute the
buzzer. Please refer to section 3-4.9 for details.
Down key: Press this button to display previous selection in Setting menu.
Test/Up +
Mute/Down
Button
Press and hold the two buttons simultaneously more than 1 sec. to enter
Escape the Setting menu.
* CVCF mode means converter mode.
9