background image

3-3. Audible Alarm

 

Description

Buzzer status

Muted

UPS status
Bypass mode

Beeps once every 2 minutes

Yes

Battery mode

Beeps once every 4 seconds

Fault mode

Beeps continuously

Warning
Overload 

Beeps twice every second

No

Low battery

Beeps once every second

Battery unconnected
Over charge
EPO enable
Fan failure/Over temperature
Charger failure
IP fuse broken
Overload 3 times in 30 min
EPO status
Cover of maintain switch is open
Fault
BUS start failure

Beeps continuously

Yes

BUS over
BUS under
BUS unbalance
Inverter soft start failure
High Inverter voltage 
Low Inverter voltage
Inverter output short circuited
Negative power fault
Battery SCR short circuited
Inverter relay short circuited
Over temperature
CPU communication failure
Overload

3-4. Single UPS Operation

1.  Turn on the UPS with utility power supply (in AC mode) 
  1)  After power supply is connected correctly, set the breaker of the battery pack at ‘ON’ position (the step 

only available for long-run model). Then set the input breaker at ‘ON’ position. At this time the fan is 
running and the UPS supplies power to the loads via the Bypass. The UPS is operating in Bypass mode. 

  Note: When UPS is in Bypass mode, the output voltage will directly power from utility after you switch 

on the input breaker. In Bypass mode, the load is not protected by UPS. To protect your precious devices, 
you should turn on the UPS. Refer to next step. 

  2)  Press and hold the ‘ON’ button for 0.5 sec to turn on the UPS and the buzzer will beep once.  
  3)  A few seconds later, the UPS will enter to AC mode. If the utility power is abnormal, the UPS will operate 

in Battery mode without interruption.

  Note: When the UPS is running out of battery, it will shut down automatically at Battery mode. When the 

utility power is restored, the UPS will auto restart in AC mode. 

2. Turn on the UPS without utility power supply (in Battery mode)

  1)  Make sure that the breaker of the battery pack is at ‘ON’ position (only for long-run model). 
  2)  Press and hold the ‘ON’ button for 0.5 sec to turn on the UPS and the buzzer will beep once.
  3)  A few seconds later, the UPS will be turned on and enter Battery mode.

3. Connect devices to UPS

  After the UPS is turned on, you can connect devices to the UPS.
  1)  Turn on the UPS first and then switch on the devices one by one, the LCD panel will display total load level. 
  2)  If it is necessary to connect the inductive loads such as printer, the in-rush current should be calculated 

carefully to see if it meets the capacity of the UPS, because the power consumption of these kinds of 
loads is on the heavier side.

  3)  If the UPS is overloaded, the buzzer will beep twice every second.
  4)  When the UPS is overload, please remove some loads immediately. It is recommended to have the total 

loads connected to the UPS less than 80% of its nominal power capacity to prevent overload for system 
safety. 

  5)  If the overload time is over acceptable time listed in spec at AC mode, the UPS will automatically transfer 

to Bypass mode. After the overload is removed, it will return to AC mode. If the overload time is over 
acceptable time listed in spec at Battery mode, the UPS will become fault status. At this time, if Bypass 
is enabled, the UPS will power to the load via Bypass. If Bypass function is disabled or the input power 
is not within Bypass acceptable range, it will cut off output directly.

4. Charge the batteries

  1)  After the UPS is connected to the utility power, the charger will charge the batteries automatically except 

in Battery mode or during battery self-test. 

  2)  Suggest to charge batteries at least 10 hours before use. Otherwise, the backup time may be shorter 

than expected time.

  3)  Make sure the battery numbers setting on the control board (Please refer to the section 3-4.12 for 

detailed setting) is consistent to real connection.

5. Battery mode operation
  1)  When the UPS is in Battery mode, the buzzer will beep according to different battery capacities. If the 

13

14

Содержание NUMERIC Onfiniti

Страница 1: ...www numericups com NEW ENERGY TO POWER USER AND INSTALLATION MANUAL NEW ENERGY TO POWER Onfiniti 5 10 kVA www numericups com A ...

Страница 2: ...4 2 3 Single UPS installation 7 2 4 Software installation 10 3 Operations 10 3 1 Button operation 10 3 2 Led indicators and LCD panel 11 3 3 Audible alarm 13 3 4 Single UPS operation 14 3 5 Abbreviation meaning in LCD display 17 3 6 LCD setting 18 3 7 Operating mode Status description 25 3 8 Fault code 26 3 9 Warning indicator 26 4 Trouble Shooting 27 5 Storage and Maintenance 28 5 1 Storage 28 5 ...

Страница 3: ...2 2 Warning This is a product designed for commercial and industrial applications additional measures may be needed to prevent electrical disturbances 1 Safety and EMC Instructions Please read the following user manual and the safety instructions carefully before installing the unit or using the unit 1 1 Transportation and Storage Please transport the UPS system only in the original package to pro...

Страница 4: ...I Standard 3 charger 7 5 10 kVA FMI Standard 3 charger 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable optional One USB cable One battery cable optional Note Before installation please inspect the unit Be sure that nothing inside the package is damaged during transportat...

Страница 5: ...t Terminal Diagram 7 7 5 10 kVA FMI Rear Panel Diagram 8 7 5 10 kVA FMI Input Output Terminal Diagram 9 7 5 10 kVA FM C Rear Panel Diagram 10 7 5 10 kVA FM C Input Output Terminal Diagram 11 7 5 10 kVA FMI C Rear Panel Diagram 12 7 5 10 kVA FMI C Input Output Terminal 5 6 ...

Страница 6: ...VA FMI Standard 3 charger 4 16 10 6 10 6 6 10 7 5 10 kVA FM Standard 4 16 8 10 8 10 4 16 7 5 10 kVA FM Standard 1 charger 4 16 8 10 8 10 4 16 7 5 10 kVA FM Standard 2 charger 2 25 8 10 8 10 4 16 7 5 10 kVA FM Standard 3 charger 2 25 8 10 8 10 4 16 7 5 10 kVA FMI Standard 4 16 8 10 8 10 4 16 7 5 10 kVA FMI Standard 1 charger 4 16 8 10 8 10 4 16 7 5 10 kVA FMI Standard 2 charger 2 25 8 10 8 10 4 16 ...

Страница 7: ...e sure the L N terminal is correct not reversed or short circuited 2 4 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown 3 Operations 3 1 Button Operation Button Function ON Enter Button Turn on the UPS Press and hold the button more than 0 5 sec to turn on the UPS Enter Key Press this button to confirm the selection in set...

Страница 8: ...Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the output is short Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the Bypass ...

Страница 9: ...mode 1 Make sure that the breaker of the battery pack is at ON position only for long run model 2 Press and hold the ON button for 0 5 sec to turn on the UPS and the buzzer will beep once 3 A few seconds later the UPS will be turned on and enter Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices...

Страница 10: ... sec and then the buzzer will beep once 2 UPS will cut off power to output and there is no display shown on the display panel 9 Mute the buzzer 1 To mute the buzzer please press the Mute button for at least 0 5 sec If you press it again after the buzzer is muted the buzzer will beep again 2 Some warning alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 10 ...

Страница 11: ...s AC CVCF Battery Battery Test 01 Output voltage Y 02 Output frequency Y 03 Voltage range for Bypass Y 04 Frequency range for Bypass Y 05 Reserved 06 Reserved 07 Reserved 08 Bypass mode setting Y 09 Battery maximum discharge time setting Y Y Y Y Y 10 Reserved 11 Reserved 12 Reserved 13 Battery voltage calibration Y Y Y Y Y 14 Charger voltage adjustment Y Y Y Y Y 15 Inverter voltage calibration Y Y...

Страница 12: ...0 Hz or within 56 64 Hz at 60 Hz according to setting in Parameter 2 If 50 Hz selected in Parameter 2 UPS will transfer to battery mode when input frequency is not within 46 54 Hz If 60 Hz selected in Parameter 2 UPS will transfer to Battery mode when input frequency is not within 56 64 Hz If Parameter 2 is ATO the Parameter 3 will show the current frequency 03 Voltage range for bypass Interface S...

Страница 13: ...etting Interface Setting Parameter 3 000 999 Set the maximum discharge time from 0 min 999 min UPS will shut down to protect battery after discharge time arrives The default value is 990 min DIS Disable battery discharge protection and backup time will depend on battery capacity 10 Reserved Interface Setting Reserved 11 Reserved Interface Setting Reserved 12 Reserved Interface Setting Reserved 13 ...

Страница 14: ...rate inverter voltage Parameter 3 The voltage range is from 0 V to 6 4 V the default value is 0 V 16 Reserved Interface Setting Reserved 17 Reserved Interface Setting Reserved 18 Reserved Interface Setting Reserved 19 Reserved Interface Setting Reserved 20 Reserved Interface Setting Reserved 23 24 ...

Страница 15: ...press Test key for more than 0 5 sec Then the UPS will beep once and start Battery Test The line between I P and Inverter icons will blink to remind users on the battery status This operation is used to check the battery status LCD display Fault status Description When UPS becomes faulty it will display fault messages in the LCD panel LCD display 3 8 Fault Code Fault event Fault code Icon Fault ev...

Страница 16: ...ries Do not attempt to dispose of batteries by burning them This could cause battery explosion The batteries must be rightly disposed according to local regulations Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not disassemble the UPS system F...

Страница 17: ...20 230 240 VAC AC Voltage Regulation 1 Frequency Range Synchronized Range 46Hz 54 Hz 50Hz system 56Hz 64 Hz 60Hz system Frequency Range Batt Mode 50 Hz 0 1 Hz or 60Hz 0 1 Hz Overload AC mode 105 110 3 min 110 130 30 sec 130 1 5 sec Current Crest Ratio 3 1 max Harmonic Distortion 3 100 Linear Load 6 100 Non linear Load Transfer Time Line Battery 0 ms Inverter Bypass 0 ms BATTERY Battery Numbers 16 ...

Отзывы: