Connect the earth before connecting to the building wiring terminal. 

 

Installation and wiring must be performed in accordance with the local electrical laws and regulations. 

 

UPS designed for linear load, worst case inductive resistive load.

1-4  Operation

 

Do not disconnect the earth conductor cable on the UPS or the building wiring terminals at any time 
since this would cancel the protective earth of the UPS system and of all connected loads. 

 

The UPS system features its own, internal current source (batteries). The UPS output sockets or 
output terminal blocks may be electrically live even if the UPS system is not connected to the building 
wiring outlet. 

 

In order to fully disconnect the UPS system, first press the ‘OFF’ button and then disconnect the mains. 
Ensure that no liquid or other foreign objects can enter the UPS system. 

 

The UPS can be operated by any individual with no previous experience. 

Suggested Breaker rating for reference 

UPS Rating

Battery Breaker

Output Breaker

5 kVA FM C & 5 kVA FMI C

50A DC (C curve)

25A AC (C curve)

6 kVA FM C & 6 kVA FMI C

50A DC (C curve)

32A AC (C curve)

7.5 kVA FM & 7.5 kVA FMI 

63A DC (C curve)

40A AC (C curve)

7.5 kVA FM C & 7.5 kVA FMI C

63A DC (C curve)

40A AC (C curve)

10 kVA FM & 10 kVA FMI 

63A DC (C curve)

50A AC (C curve)

10 kVA FM C & 10 kVA FMI C

63A DC (C curve)

50A AC (C curve)

1-5  Standards

Safety
IEC/EN 62040-1
EMI
Conducted Emission

IEC/EN 62040-2

Category C3

Radiated Emission

IEC/EN 62040-2

Category C3

EMS
ESD

IEC/EN 61000-4-2

Level 4

RS

IEC/EN 61000-4-3

Level 3

EFT

IEC/EN 61000-4-4

Level 4

Surge

IEC/EN 61000-4-5

Level 4

CS

IEC/EN 61000-4-6

Level 3

Power-frequency magnetic field

IEC/EN 61000-4-8

Level 4

Low-frequency signals

IEC/EN 61000-2-2

Warning: This is a product designed for commercial and industrial applications, additional measures may be 
needed to prevent electrical disturbances.

1. 

Safety and EMC Instructions

Please read the following user manual and the safety instructions carefully before installing the unit or using

the unit.

1-1 

 Transportation and Storage

 

Please transport the UPS system only in the original package to protect against shock and impact.

 

The UPS must be stored in the room where it is ventilated and dry.

1-2 Preparation

 

Condensation may occur if the UPS system is moved directly from cold to warm environment.  
The UPS system must be absolutely dry before being installed. Please allow at least 2 hours for the 
UPS system to acclimatize to the environment. 

 

Do not install the UPS system near water or moist environments.

 

Do not install the UPS system where it would be exposed to direct sunlight or near a heater.

 

Do not block ventilation holes in the UPS housing.

1-3 Installation

 

Do not connect appliances or devices which would overload the UPS (e.g. large motor-type equipment) 
to the UPS output sockets or terminal. 

 

Do not place cables in such a way that it might cause someone to trip over or need to step over them. 

 

Do not block air vents in the UPS housing. The UPS must be installed in a location with good ventilation. 
Ensure enough space on each side for ventilation. 

 

UPS has provided earthed terminal, in the final installed system configuration, equipotential earth 
bonding to the external UPS battery cabinets.

 

The UPS can be installed by qualified maintenance personnel only.

 

An appropriate disconnect device as short-circuit backup protection should be provided in the building 
wiring installation.

 

An integral single emergency switching device which prevents further supply to the load by the UPS in 
any mode of operation should be provided in the building wiring installation. 

1

2

Содержание NUMERIC Onfiniti

Страница 1: ...www numericups com NEW ENERGY TO POWER USER AND INSTALLATION MANUAL NEW ENERGY TO POWER Onfiniti 5 10 kVA www numericups com A ...

Страница 2: ...4 2 3 Single UPS installation 7 2 4 Software installation 10 3 Operations 10 3 1 Button operation 10 3 2 Led indicators and LCD panel 11 3 3 Audible alarm 13 3 4 Single UPS operation 14 3 5 Abbreviation meaning in LCD display 17 3 6 LCD setting 18 3 7 Operating mode Status description 25 3 8 Fault code 26 3 9 Warning indicator 26 4 Trouble Shooting 27 5 Storage and Maintenance 28 5 1 Storage 28 5 ...

Страница 3: ...2 2 Warning This is a product designed for commercial and industrial applications additional measures may be needed to prevent electrical disturbances 1 Safety and EMC Instructions Please read the following user manual and the safety instructions carefully before installing the unit or using the unit 1 1 Transportation and Storage Please transport the UPS system only in the original package to pro...

Страница 4: ...I Standard 3 charger 7 5 10 kVA FMI Standard 3 charger 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable optional One USB cable One battery cable optional Note Before installation please inspect the unit Be sure that nothing inside the package is damaged during transportat...

Страница 5: ...t Terminal Diagram 7 7 5 10 kVA FMI Rear Panel Diagram 8 7 5 10 kVA FMI Input Output Terminal Diagram 9 7 5 10 kVA FM C Rear Panel Diagram 10 7 5 10 kVA FM C Input Output Terminal Diagram 11 7 5 10 kVA FMI C Rear Panel Diagram 12 7 5 10 kVA FMI C Input Output Terminal 5 6 ...

Страница 6: ...VA FMI Standard 3 charger 4 16 10 6 10 6 6 10 7 5 10 kVA FM Standard 4 16 8 10 8 10 4 16 7 5 10 kVA FM Standard 1 charger 4 16 8 10 8 10 4 16 7 5 10 kVA FM Standard 2 charger 2 25 8 10 8 10 4 16 7 5 10 kVA FM Standard 3 charger 2 25 8 10 8 10 4 16 7 5 10 kVA FMI Standard 4 16 8 10 8 10 4 16 7 5 10 kVA FMI Standard 1 charger 4 16 8 10 8 10 4 16 7 5 10 kVA FMI Standard 2 charger 2 25 8 10 8 10 4 16 ...

Страница 7: ...e sure the L N terminal is correct not reversed or short circuited 2 4 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown 3 Operations 3 1 Button Operation Button Function ON Enter Button Turn on the UPS Press and hold the button more than 0 5 sec to turn on the UPS Enter Key Press this button to confirm the selection in set...

Страница 8: ...Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the output is short Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the Bypass ...

Страница 9: ...mode 1 Make sure that the breaker of the battery pack is at ON position only for long run model 2 Press and hold the ON button for 0 5 sec to turn on the UPS and the buzzer will beep once 3 A few seconds later the UPS will be turned on and enter Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices...

Страница 10: ... sec and then the buzzer will beep once 2 UPS will cut off power to output and there is no display shown on the display panel 9 Mute the buzzer 1 To mute the buzzer please press the Mute button for at least 0 5 sec If you press it again after the buzzer is muted the buzzer will beep again 2 Some warning alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 10 ...

Страница 11: ...s AC CVCF Battery Battery Test 01 Output voltage Y 02 Output frequency Y 03 Voltage range for Bypass Y 04 Frequency range for Bypass Y 05 Reserved 06 Reserved 07 Reserved 08 Bypass mode setting Y 09 Battery maximum discharge time setting Y Y Y Y Y 10 Reserved 11 Reserved 12 Reserved 13 Battery voltage calibration Y Y Y Y Y 14 Charger voltage adjustment Y Y Y Y Y 15 Inverter voltage calibration Y Y...

Страница 12: ...0 Hz or within 56 64 Hz at 60 Hz according to setting in Parameter 2 If 50 Hz selected in Parameter 2 UPS will transfer to battery mode when input frequency is not within 46 54 Hz If 60 Hz selected in Parameter 2 UPS will transfer to Battery mode when input frequency is not within 56 64 Hz If Parameter 2 is ATO the Parameter 3 will show the current frequency 03 Voltage range for bypass Interface S...

Страница 13: ...etting Interface Setting Parameter 3 000 999 Set the maximum discharge time from 0 min 999 min UPS will shut down to protect battery after discharge time arrives The default value is 990 min DIS Disable battery discharge protection and backup time will depend on battery capacity 10 Reserved Interface Setting Reserved 11 Reserved Interface Setting Reserved 12 Reserved Interface Setting Reserved 13 ...

Страница 14: ...rate inverter voltage Parameter 3 The voltage range is from 0 V to 6 4 V the default value is 0 V 16 Reserved Interface Setting Reserved 17 Reserved Interface Setting Reserved 18 Reserved Interface Setting Reserved 19 Reserved Interface Setting Reserved 20 Reserved Interface Setting Reserved 23 24 ...

Страница 15: ...press Test key for more than 0 5 sec Then the UPS will beep once and start Battery Test The line between I P and Inverter icons will blink to remind users on the battery status This operation is used to check the battery status LCD display Fault status Description When UPS becomes faulty it will display fault messages in the LCD panel LCD display 3 8 Fault Code Fault event Fault code Icon Fault ev...

Страница 16: ...ries Do not attempt to dispose of batteries by burning them This could cause battery explosion The batteries must be rightly disposed according to local regulations Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not disassemble the UPS system F...

Страница 17: ...20 230 240 VAC AC Voltage Regulation 1 Frequency Range Synchronized Range 46Hz 54 Hz 50Hz system 56Hz 64 Hz 60Hz system Frequency Range Batt Mode 50 Hz 0 1 Hz or 60Hz 0 1 Hz Overload AC mode 105 110 3 min 110 130 30 sec 130 1 5 sec Current Crest Ratio 3 1 max Harmonic Distortion 3 100 Linear Load 6 100 Non linear Load Transfer Time Line Battery 0 ms Inverter Bypass 0 ms BATTERY Battery Numbers 16 ...

Отзывы: