background image

battery capacity is more than 25%, the buzzer will beep once every 4 seconds; If the battery voltage 
drops to the alarm level, the buzzer will beep quickly (once every sec) to remind users that the battery 
is at low level and the UPS will shut down automatically. Users could switch off some non-critical loads 
to disable the shutdown alarm and prolong the backup time. If there is no more load to be switched off 
at that time, you have to shut down all loads as soon as possible to protect the devices or save data. 
Otherwise, there is a risk of data loss or load failure. 

  2)  In Battery mode, users can press the Mute button to disable the buzzer.
  3)  The backup time of the long-run model depends on the external battery capacity.
  4)  The backup time may vary from different environment temperature and load type.
  5)  When setting backup time for 16.5 hours (default value from LCD panel), after discharging 16.5 hours, 

UPS will shut down automatically to protect the battery. This battery discharge protection can be enabled 
or disabled through LCD panel control. (Refer to 3-7 LCD setting section)

6. Test the batteries
  1)  If you need to check the battery status when the UPS is running in AC mode/CVCF mode, you could press 

the “Test” button to let the UPS do battery self-test.

  2)  Users also can set battery self-test through monitoring software.

7. Turn off the UPS with utility power supply in AC mode
  1)  Turn off the inverter of the UPS by pressing ‘OFF’ button for at least 0.5 sec, and then the buzzer will 

beep once. The UPS will turn into Bypass mode. 

  Note: If the UPS has been set to enable the Bypass output, it will Bypass voltage from utility power to 

output sockets and terminal even though you have turned off the UPS (inverter).

  Note: After turning off the UPS, please be aware that the UPS is working at Bypass mode and there is 

risk of power loss for connected devices. 

  2)  In Bypass mode, output voltage of the UPS is still present. In order to cut off the output, switch off the              

input breaker. A few seconds later, there is no display shown on the display panel and UPS is completely 
switched off.

8. Turn off the UPS without utility power supply in Battery mode
  1)  Turn off the  UPS by pressing ‘OFF’ button for at least 0.5 sec and then the buzzer will beep once.
  2)  UPS will cut off power to output and there is no display shown on the display panel.

 9. Mute the buzzer
  1)  To mute the buzzer, please press the ‘Mute’ button for at least 0.5 sec. If you press it again after the 

buzzer is muted, the buzzer will beep again.

  2)  Some warning alarms can’t be muted unless the error is fixed. Please refer to section 3-3 for the details. 

10. Operation in warning status
  1)   When Fault LED flashes and the buzzer beeps once every second, it means that there are some problems 

for UPS operation. Users can get the fault code from LCD panel. Please check the trouble shooting table 
in chapter 4 for details. 

11. Operation in Fault mode
  1)  When Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in the 

UPS.  Users can get the fault code from display panel. Please check the trouble shooting table in section 
4 for details.

  2)  Please check the loads, wiring, ventilation, utility, battery and so on after the fault occurs. Don’t try to 

turn on the UPS again before solving the problems. If the problems can’t be fixed, please contact the 
distributor or service people immediately.

  3)  In emergencies, cut off the connections from utility, external battery and output immediately to avoid 

more risk or danger.

12. Operation of changing battery numbers
  1)  This operation is only available for professional or qualified technicians.
  2)  Turn off the UPS. If the load couldn’t be cut off, you should remove the cover of maintenance bypass 

switch on the rear panel and turn the maintenance switch to ‘BPS’ position first.

  3)  Switch off the input breaker, and switch off the battery breaker (only available for long-run model), or 

disconnect battery wire for standard model.

  4)  Remove the cabinet cover, and then modify the jumpers (JP1, JS3) on the control board to set the battery 

numbers as following table: 

Battery Number

JP1

JS3

pin1 & pin2

pin3 & pin4

pin5 & pin6

pin7 & pin8

16

X

X

0

0

0

17

X

X

1

1

0

18

X

X

0

0

1

19

X

X

1

0

1

20

X

X

1

1

1

 

Note: 1 =  connect with jumper; 0 = no jumper; x = the pins are for other functions.

  5)  Modify the battery pack for the setting number carefully. After completing, put the cover back and switch 

on the battery breaker for long-run model.

  6)  Switch on the input breaker and the UPS will enter Bypass mode. If the UPS is in maintenance Bypass 

mode, turn the maintenance switch to ‘UPS’ position and then turn on the UPS.

15

16

Содержание NUMERIC Onfiniti

Страница 1: ...www numericups com NEW ENERGY TO POWER USER AND INSTALLATION MANUAL NEW ENERGY TO POWER Onfiniti 5 10 kVA www numericups com A ...

Страница 2: ...4 2 3 Single UPS installation 7 2 4 Software installation 10 3 Operations 10 3 1 Button operation 10 3 2 Led indicators and LCD panel 11 3 3 Audible alarm 13 3 4 Single UPS operation 14 3 5 Abbreviation meaning in LCD display 17 3 6 LCD setting 18 3 7 Operating mode Status description 25 3 8 Fault code 26 3 9 Warning indicator 26 4 Trouble Shooting 27 5 Storage and Maintenance 28 5 1 Storage 28 5 ...

Страница 3: ...2 2 Warning This is a product designed for commercial and industrial applications additional measures may be needed to prevent electrical disturbances 1 Safety and EMC Instructions Please read the following user manual and the safety instructions carefully before installing the unit or using the unit 1 1 Transportation and Storage Please transport the UPS system only in the original package to pro...

Страница 4: ...I Standard 3 charger 7 5 10 kVA FMI Standard 3 charger 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable optional One USB cable One battery cable optional Note Before installation please inspect the unit Be sure that nothing inside the package is damaged during transportat...

Страница 5: ...t Terminal Diagram 7 7 5 10 kVA FMI Rear Panel Diagram 8 7 5 10 kVA FMI Input Output Terminal Diagram 9 7 5 10 kVA FM C Rear Panel Diagram 10 7 5 10 kVA FM C Input Output Terminal Diagram 11 7 5 10 kVA FMI C Rear Panel Diagram 12 7 5 10 kVA FMI C Input Output Terminal 5 6 ...

Страница 6: ...VA FMI Standard 3 charger 4 16 10 6 10 6 6 10 7 5 10 kVA FM Standard 4 16 8 10 8 10 4 16 7 5 10 kVA FM Standard 1 charger 4 16 8 10 8 10 4 16 7 5 10 kVA FM Standard 2 charger 2 25 8 10 8 10 4 16 7 5 10 kVA FM Standard 3 charger 2 25 8 10 8 10 4 16 7 5 10 kVA FMI Standard 4 16 8 10 8 10 4 16 7 5 10 kVA FMI Standard 1 charger 4 16 8 10 8 10 4 16 7 5 10 kVA FMI Standard 2 charger 2 25 8 10 8 10 4 16 ...

Страница 7: ...e sure the L N terminal is correct not reversed or short circuited 2 4 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown 3 Operations 3 1 Button Operation Button Function ON Enter Button Turn on the UPS Press and hold the button more than 0 5 sec to turn on the UPS Enter Key Press this button to confirm the selection in set...

Страница 8: ...Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the output is short Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the Bypass ...

Страница 9: ...mode 1 Make sure that the breaker of the battery pack is at ON position only for long run model 2 Press and hold the ON button for 0 5 sec to turn on the UPS and the buzzer will beep once 3 A few seconds later the UPS will be turned on and enter Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices...

Страница 10: ... sec and then the buzzer will beep once 2 UPS will cut off power to output and there is no display shown on the display panel 9 Mute the buzzer 1 To mute the buzzer please press the Mute button for at least 0 5 sec If you press it again after the buzzer is muted the buzzer will beep again 2 Some warning alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 10 ...

Страница 11: ...s AC CVCF Battery Battery Test 01 Output voltage Y 02 Output frequency Y 03 Voltage range for Bypass Y 04 Frequency range for Bypass Y 05 Reserved 06 Reserved 07 Reserved 08 Bypass mode setting Y 09 Battery maximum discharge time setting Y Y Y Y Y 10 Reserved 11 Reserved 12 Reserved 13 Battery voltage calibration Y Y Y Y Y 14 Charger voltage adjustment Y Y Y Y Y 15 Inverter voltage calibration Y Y...

Страница 12: ...0 Hz or within 56 64 Hz at 60 Hz according to setting in Parameter 2 If 50 Hz selected in Parameter 2 UPS will transfer to battery mode when input frequency is not within 46 54 Hz If 60 Hz selected in Parameter 2 UPS will transfer to Battery mode when input frequency is not within 56 64 Hz If Parameter 2 is ATO the Parameter 3 will show the current frequency 03 Voltage range for bypass Interface S...

Страница 13: ...etting Interface Setting Parameter 3 000 999 Set the maximum discharge time from 0 min 999 min UPS will shut down to protect battery after discharge time arrives The default value is 990 min DIS Disable battery discharge protection and backup time will depend on battery capacity 10 Reserved Interface Setting Reserved 11 Reserved Interface Setting Reserved 12 Reserved Interface Setting Reserved 13 ...

Страница 14: ...rate inverter voltage Parameter 3 The voltage range is from 0 V to 6 4 V the default value is 0 V 16 Reserved Interface Setting Reserved 17 Reserved Interface Setting Reserved 18 Reserved Interface Setting Reserved 19 Reserved Interface Setting Reserved 20 Reserved Interface Setting Reserved 23 24 ...

Страница 15: ...press Test key for more than 0 5 sec Then the UPS will beep once and start Battery Test The line between I P and Inverter icons will blink to remind users on the battery status This operation is used to check the battery status LCD display Fault status Description When UPS becomes faulty it will display fault messages in the LCD panel LCD display 3 8 Fault Code Fault event Fault code Icon Fault ev...

Страница 16: ...ries Do not attempt to dispose of batteries by burning them This could cause battery explosion The batteries must be rightly disposed according to local regulations Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not disassemble the UPS system F...

Страница 17: ...20 230 240 VAC AC Voltage Regulation 1 Frequency Range Synchronized Range 46Hz 54 Hz 50Hz system 56Hz 64 Hz 60Hz system Frequency Range Batt Mode 50 Hz 0 1 Hz or 60Hz 0 1 Hz Overload AC mode 105 110 3 min 110 130 30 sec 130 1 5 sec Current Crest Ratio 3 1 max Harmonic Distortion 3 100 Linear Load 6 100 Non linear Load Transfer Time Line Battery 0 ms Inverter Bypass 0 ms BATTERY Battery Numbers 16 ...

Отзывы: