33
KEOR T EVO
Installa
tion & Oper
ation M
anual
Make sure that all circuit breakers are at “OFF” position before starting with the
installation.
NEUTRAL SYSTEM :
KEOR T EVO does not modify the neutral system: output neutral system is the same as
input neutral system. Do not connect the output neutral to the protective ground or
protective bounding (PE or PB).
Installation of an external isolation transformer is required when necessary to modify
the neutral.
Connect the phase cable to X2 OUTPUT: X2/L1 – X2/L2 – X2/L3 terminal and the neutral cable to X2
OUTPUT: X2/N terminal.
Cables must be protected by fuses or MCCB, refer to Section 5.4
Electrical Characteristics - Inverter
Model (kVA)
10
15
20
Rated output voltage (selectable) (V)
400 3Ph+N+PB (380/415 configurable)
Output voltage tolerance
static load ±1%, dynamic load VF-SS-111 compliant
Rated output frequency (Hz)
50/60 Hz (selectable)
Autonomous frequency tolerance
±0.02% on mains power failure
Harmonic voltage distortion
< 2% with linear load, < 4% with non linear load
Table.6
Figure.6.3.1.5-1
Output Connection of UPS
Содержание KEOR T EVO
Страница 1: ...KEOR T EVO 10 15 20 KVA Installation Operation Manual LE10507AA ...
Страница 2: ...LE10507AA KEOR T EVO ...
Страница 24: ...22 Figure 6 3 1 3 Figure 6 3 1 4 Power Cables Path Communication Cables Path ...
Страница 30: ...28 Figure 6 3 1 4 1 KEOR T EVO 10 1x24pcs 9Ah BATTERY WIRING DIAGRAM ...
Страница 31: ...29 KEOR T EVO Installation Operation Manual Figure 6 3 1 4 2 KEOR T EVO 10 1x24pcs 9Ah BATTERY WIRING DIAGRAM ...
Страница 32: ...30 Figure 6 3 1 4 3 KEOR T EVO 10 1x24pcs 9Ah BATTERY WIRING DIAGRAM ...
Страница 76: ...74 SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT ...
Страница 77: ...75 KEOR T EVO Installation Operation Manual COMMON RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT ...
Страница 82: ...Notes ...
Страница 83: ......