42
No
Alarms
Description
1
Bypass voltage failure
Bypass voltage is out of the limit
2
Bypass phase sequence wrong
Phase sequence of bypass mains voltage is not OK
3
Inverter not sync. with bypass
Frequency of bypass voltage is beyond the frequency range for online operation or bypass voltage is out of
limit.
4
Battery breaker open
Battery fuses blown or breaker opened by user
5
Battery test failure
Battery failure
6
Rectifier temperature high
Rectifier IGBT module temperature high
7
Rectifier overload
RMS current drawn from any of the input lines exceeds its nominal value.
8
Rectifier communication lost
Front panel cannot communicate with rectifier
9
Input voltage failure
Input voltage is out of the limit
10
Input phase sequence wrong
Phase sequence of input mains voltage is not OK
11
Rectifier not sync. with input
Frequency of input mains voltage is beyond the frequency range of rectifier or input mains voltage is out of
limit.
12
Rectifier not precharged
DC voltage not charged by inrush circuit
13
DC voltage failure
DC Bus voltage is out of the limit
14
Inverter temperature high
Inverter IGBT module temperature high
15
Output overload
RMS current drawn from any of the output lines exceeds its nominal value.
16
Inverter DC component high
Inverter voltage's DC component is out of the limit
17
Inverter communication lost
Front panel can not communicate with inverter
18
Output DC component high
Output voltage's DC component is out of the limit
19
Output voltage failure
Output voltage is out of the limit
20
Output short circuit
Short circuit at the output
21
Master communication lost
Slave cannot communicate with master
22
Slave not sync. with master
Slave lost the synchronization with the master
23
N number failure
Parallel UPS count is below the adjusted N number
24
Redundancy lost
Parallel system alarm. The total load is more than the redundancy load.
The formula is : Load % > N / (N+1) * 100
Appendix-1: Alarms List
Содержание Keor T 10KVA
Страница 1: ...LE10795AB KEOR T 208V 5 60 KVA Operating Manual ...
Страница 4: ...KEOR T ...
Страница 53: ...49 KEOR T Operating Manual SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 5 30kVA ...
Страница 54: ...50 SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 40 60kVA ...
Страница 55: ...51 KEOR T Operating Manual COMMON RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 5 30kVA ...
Страница 56: ...52 COMMON RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 40 60kVA ...