6
• The equipment may only be installed and commissioned by authorized Legrand UPS Technical Service Personnel.
• This manual contains important instructions that you should follow during installation and maintenance of the
UPS and batteries. Please read all instructions before operating the equipment and save this manual for future
reference.
• Not obeying the instructions written on this manual which may result with possible injury of the operator or
damage of the equipment.
• Even when connections removed, residual voltages of capacitors and/or high temperature may exist on
connection terminals and inside the UPS. Before working on terminals, check between all the terminals included
PE that no hazardous voltages exist.
• According to IEC 62040-2; this is a product for commercial and industrial application. In the second environment
installation restrictions or additional measures may be needed to prevent disturbances.
• The equipment shall be packed and fixed properly during transportation to avoid fall down and proper
equipment should be used for transportation. Never transport in horizontal position.
• The UPS must always stands in a vertical position. Make sure that the floor can support the weight of the system.
• UPS is designed for indoor use. To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled indoor environment, free of conductive contaminants. Ambient temperature must not
exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum without condensation).
• Contact your local recycling or hazardous waste centre for information on proper disposal of the used battery or
UPS.
• In case of an extraordinary situation (damaged body, cabinet or connections, penetration of foreign materials
into the body or cabinet etc.) deenergize the UPS immediately and consult to the LEGRAND Technical Assistance
Centre.
3.2.
Important Notice for Battery
•
The batteries may only be installed and commissioned by authorized Legrand UPS Technical Service
Personnel.
• Do not dispose of batteries in a fire. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
• In case of electrolyte in contact with skin, immediately wash the contaminated skin with water.
•
A battery can present risk of electric shock and high short circuit currents.
3.3.
Description of the Symbols Used on the Labels Applied to the UPS
3.1.
Important Notice for UPS
3. Safety
Information related to safety of the UPS, battery, load and the user is summarized below.
But the equipment should not be installed before reading the manual completely.
PE: PROTECTIVE EARTH
PB: PROTECTIVE BONDING
DANGER! HIGH VOLTAGE (BLACK/YELLOW)
This symbol points out the instructions, which may result with injury of
the operator or damage of the equipment if not obeyed.
Содержание Keor T 10KVA
Страница 1: ...LE10795AB KEOR T 208V 5 60 KVA Operating Manual ...
Страница 4: ...KEOR T ...
Страница 53: ...49 KEOR T Operating Manual SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 5 30kVA ...
Страница 54: ...50 SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 40 60kVA ...
Страница 55: ...51 KEOR T Operating Manual COMMON RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 5 30kVA ...
Страница 56: ...52 COMMON RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT 40 60kVA ...