7. Operating Procedures For Single Systems
7.1.
Preparations
UPS is shipped with 3pcs of battery fast fuses in a plastic package attached to the front side of UPS.
After all connections are completed as described in Keor T Installation Manual, the battery fuses must be placed
as shown below. The fuses’ indicators should be placed at top. Use only the fuses delivered with the UPS.
Figure.7.1-1
Figure.7.1-2
KEOR T 5-30KVA
KEOR T 40-50KVA
INDICATORS