ELIOT Kit STOP&GO Connected 

 

Cat. N°: 4

 149 54

 

 

 

4. PREPARATION - CONNECTION

 (continued)

 

On site information displayed by the Stop&Go 

(continued)

Details for “too recurrent” non

-permanent faults:

  

During its functioning, the Stop&Go memorises the numbers of 
faults and of remote/manual resetting operations. 
. When an event occurs, the Stop&Go analyses the event and in 
case of fault (short-circuit or ground fault) it starts the recurring fault 
procedure. 
. See table for details: 

# of faults 

Period 

Consequence 

≤ 5 minutes

 

- Remote resetting is disabled. 
- The application shows this state 
with the following message: 

 

≤ 1 hour

 

- The application shows this 
condition with a message indicating 
the number of faults within the time 
frame and the indication to check the 
electrical installation on site. 
- Remote resetting remains enabled. 

≤ 1 day 

 

≤ 7 days

 

15 

≤ 30 days 

 

Selector AUTO / MAN: 

. Enables and disables the remote command of the Stop&Go. 

. Possible states: 
- AUTO: allows to remotely control the 
Stop&Go via the Smartphone app (reclosing of 
the associated device following a fault). 
- MAN: on-site manual control only by the 
handle of the Stop&Go (isolating and power 
handles together) 
 
 
 
 

Note: in case of on-site maintenance, to put the selector on MAN is 
not enough. The use of a padlock is the only secured way 

 

 

 

4. PREPARATION - CONNECTION

 (continued)

 

Stop&Go signalling led: 

 

  Possible states: 

Led colour 

State 

Meaning 

 

red 

Fast blinking 

Waiting for manual or remote 
reset command following a 
temporary fault (non-permanent) 
If the Stop&Go detects a too 
recurrent fault, remote actuation is 
disabled 

Steady 

“Unwanted tripping”: Stop&Go has 

detected a permanent default in 
the system 
Remote actuation is disabled 

 

green 

Fast blinking 

Stop&Go in MAN mode 

Steady 

“Normal situation”: associated 

device is powered and Stop&Go in 
AUTO mode. 

  Switched-off 

Stop&Go not supplied or sliding 
front face downward 

Wi-Fi module signalling led: 

. Power led: indicates the status of operation of the interface: 

 

-

 

Steady green 

 interface supplied 

-

 

Steady off 

 interface not supplied 

 

 

 

Technical data sheet: F02465EN/01 

Updated: 28/03/2019 

Created: 06/10/2016 

 

 

 

Содержание 4 149 54

Страница 1: ...non permanent fault It reports the information through the Smartphone app Allows the user to remotely switch it ON In case of recurrent non permanent faults the Stop Go will not allow some remote comm...

Страница 2: ...e kit to connect at the downstream of the supplier indifferently in one of the two dedicated ports Supply of the Wi Fi Interface Mandatory in 12 VDC via the specific Power supply module and specific s...

Страница 3: ...install a specific protection upstream of the Stop Go because it is self protected 4 PREPARATION CONNECTION continued Wiring diagrams continued Power supply module protected by an MCB protected by a...

Страница 4: ...lip the Wi Fi module and the power supply on a different DIN row than the Stop Go module 4 PREPARATION CONNECTION continued Diagnostic procedure Once the kit assembly and the electrical connections ha...

Страница 5: ...the Stop Go the Stop Go power handle is down and the isolating handle is up and the Stop Go led flashes quickly in red 7 2 An alert message is displayed 7 3 Press on TURN ON 4 PREPARATION CONNECTION...

Страница 6: ...site information displayed by the Stop Go continued Device handle status continued Operation sequences continued In case of an Unwanted tripping of the associated device and during the verification o...

Страница 7: ...ows to remotely control the Stop Go via the Smartphone app reclosing of the associated device following a fault MAN on site manual control only by the handle of the Stop Go isolating and power handles...

Страница 8: ...rogramming mode or to restore factory settings Possible states Pressing time Action t 3 sec Wi Fi interface put in configuration mode via WPS button t 7 sec Wi Fi interface put in configuration mode v...

Страница 9: ...ne and laser marking Lateral side marking by laser left side Standard and programming information right side cabling and traceability information Technical data sheet F02465EN 01 Updated 28 03 2019 Cr...

Страница 10: ...ype Measurement type Value dBm 802 11b 1Mbps RMS 18 2 802 11g 54Mbps RMS 16 2 802 11n 72 2Mbps RMS 16 2 Characteristics of the fault detection Rd0 non operating rated resistance between the live parts...

Страница 11: ...ce against solid and liquid bodies IP 40 IEC EN 60529 Class II front panel with faceplate Resistance to sinusoidal vibrations According to IEC 60068 2 6 Axis x y z Frequency range 5 100 Hz duration 90...

Страница 12: ...ream of the associated device to the Stop Go and to protect the power supply module with a fuse holder or an MCB see Wiring diagrams Supply of the ADSL Wi Fi Box The Wi Fi module communicates with an...

Страница 13: ...1 2003 corr Feb 2004 A1 2004 A11 2005 A12 2008 Electrical accessories Circuit breakers for overcurrent protection for household and similar installations Part 1 Circuit breakers for a c operation IEC...

Страница 14: ...ing switch can be modified to 2 auxiliary contacts 1 module cat n 4 062 66 Electronic EMS CX3 Auxiliary contact Fault signalling module cat n 4 149 29 Control auxiliaries It is forbidden to associate...

Страница 15: ...ing command closing of the circuit not allowed Close manually the Stop Go 4 A too recurrent non permanent fault has been detected Remote reclosing command closing of the circuit not allowed Contact yo...

Страница 16: ...n MAN mode Remote reclosing command closing of the circuit not allowed Put selector in AUTO position 8 Stop Go in locked position Remote reclosing command closing of the circuit not allowed If it is p...

Отзывы: