3 / 26
DX³ 4
-pole RCBO
6000 A/10 kA
Cat. N°(s) :
4 111 85, 86, 87, 88, 89 / 4 112 04, 05, 06, 07,
4 112 08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35,
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51,
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81
4. PREPARATION - CONNECTION
(continued)
Conductor type:
. Copper cable
. Cable cross-section:
Without ferrule
With ferrule
Rigid
cable
1 x 0.75 mm² to 35 mm²
2 x 0.75 mm² to 16 mm²
-
Flexible
cable
1 x 0.75 mm² to 25 mm²
2 x 0.75 mm² to 16 mm²
1 x 0.75 mm² to 25 mm²
. Prong supply busbar at the top or the bottom of the product, alone
or with a 16 mm² flexible wire (without
ferrule) or a connection
terminal in the same terminal.
. Fork supply busbar at the bottom of the product
Recommended tools:
. For the screw terminals, screwdriver with 5.5 mm to 6.5 mm blade
or Pozidriv no. 2 screwdriver
. For attaching or removing the DIN rail, screwdriver with 5.5 mm to
6.5 mm blade or Pozidriv no. 2 screwdriver
Manual actuation of the RCBO
. Ergonomic 2-position handle:
-"O-OFF": Device open
-"I-ON": Device closed
Contact status display:
. By marking of the handle:
-"O-OFF" in white on a green background = contacts open
-"I-ON" in white on a red background = contacts closed
Trip indication on residual current fault:
. Yellow indicator on the front
Locking:
. Padlocks possible in the open or closed positions with padlock
support (Cat. No. 4
063 03) and Ø 5 mm padlock (Cat. No. 4
063
13) or Ø6 mm padlock (Cat. No.
227 97)
Sealing:
.
Possible in the open or closed positions
Labelling:
. Circuit identification by way of a label inserted in the label holder
situated on the front of the product
5. GENERAL CHARACTERISTICS
Neutral earthing system:
. IT , TT, TN
Marking on the front side:
. By permanent ink pad printing
Marking on the upper panel:
. By permanent ink pad printing
Test operating voltages:
I
n
30 mA
300 mA
1000 mA
min. U
320 V~
220 V~
230 V~
max. U
440 V~
440 V~
440 V~
Breaking capacity:
. With a three-phase n neutral (with alternating current 50 Hz)
Standard
Voltage
between
poles
Breaking capacity
EN 61009-1
230 V
Icn
6 kA
400 V
6 kA
EN 60947-2
230 V
Icu
10 kA
400 V
10 kA
230 V
Ics
50 % Icu
400 V
50 % Icu
Residual breaking capacity:
. I
m = 4.5 kA in accordance with EN 61009-1 section 9.12.11.4d
(I
m: short-circuit to earth)
Breaking capacity on one single pole (phase pole):
. In accordance with I
IT
EN60947-2
–
Appendix H (double fault in
IT system): 3 kA at 400 V ~ and 6 kA at 230 V~
. In accordance with Icn1 EN60898-1: 10 kA at 230 V~
Technical data sheet: F01315EN/03
Updated on: 30/05/2018
Created on: 27/05/11