8 / 26
DX³ 4
-pole RCBO
6000 A/10 kA
Cat. N°(s) :
4 111 85, 86, 87, 88, 89 / 4 112 04, 05, 06, 07,
4 112 08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35,
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51,
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81
5. GENERAL CHARACTERISTICS
(continued)
Association and coordination with upstream Moulded Case Circuit Breakers (MCCBs):
. Three-phase network (+N) 400/415 V, in accordance with standard IEC 60947-2
.TT neutral earthing or TNS system
Upstream MCCB
DPX³ 250
25 kA
DPX³ 250
36 kA
DPX³ 250
50 kA
DPX³ 250
70 kA
Downstream RCBO
25 to 250 A
25 to 250 A
25 to 250 A
25 to 250 A
DX³ 6000 A
B and C curves
≤32 A
25 kA
25 kA
25 kA
25 kA
Upstream MCCB
DPX 250 36 kA
DPX-H 250 70KA
DPX / DPX-H
630
DPX / DPX-H
1250
DPX / DPX-H
1600
Downstream RCBO
25 A
40 to 250 A
250 to 630 A
500 to 1,250 A
630 to 1600 A
DX³ 6000 A
B and C curves
≤20 A
25 kA
25 kA
25 kA
25 kA
25 KA
25 A
-
25 kA
25 kA
20 kA
20 kA
32 A
-
25 kA
25 kA
15 kA
15 kA
Upstream MCCB
Downstream RCBO
DPX 250 ER AB
DPX 400 AB
DX³ 6000 A
B and C curves
≤32 A
25 kA
25 kA
Association and coordination with upstream fuses only for sensitivities 300mA and 1000mA :
. Three-phase network (+N) 230/240, in accordance with standard IEC 60947-2
. TT neutral earthing or TNS system
Upstream fuse
gG and aM types
Downstream RCBO
≤20 A
25 A
32 A
40 A
50 A
63 A
80 A
100 A
125 A
160 A
DX³ 6000 A
B and C curves
≤13 A
100 kA
100 kA
100 kA
100 kA
100 KA 100 kA
100 kA
100 kA
100 kA
40 KA
16 A
-
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
40 kA
20 A
-
-
100 kA
100 kA
100 KA 100 kA
100 kA
100 kA
100 kA
40 kA
25 A
-
-
-
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
40 kA
32 A
-
-
-
-
100 kA
100 kA
100 kA
100 kA
100 kA
40 kA
Technical data sheet: F01315EN/03
Updated on: 30/05/2018
Created on: 27/05/11