DX³ 4
-pole RCBO
6000 A/10 kA
Cat. N°(s) :
4 111 85, 86, 87, 88, 89 / 4 112 04, 05, 06, 07,
4 112 08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35,
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51,
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81
5. GENERAL CHARACTERISTICS
(continued)
Association and coordination with upstream MCBs:
. Three-phase network (+N) 400/415 V, in accordance with standard IEC 60947-2
. TT neutral earthing or TNS system
Upstream MCB
DX
³
10 kA B and C curves
DX
³
6000/10 kA B, C and D curves
Downstream RCBO
≤32 A
40 A
50 A
63 A
DX
³
6000 A
B and C curves
≤25 A
10 kA
10 kA
10 kA
10 kA
32 A
-
10 kA
10 kA
10 kA
Upstream MCB
DX
³
10000 16 kA
B/C/D curves
DX
³
25 kA
B/C/D curves
DX
³
36 kA
C curve
DX
³
50 kA
B/C/D curves
Downstream
RCBO
≤15 A
32 A
40 to
125 A
≤25 A
32 A
40 to
125 A
≤25 A
32 A
40 to
80 A
≤25 A
32 A
40 to
63
DX³ 6000 A
B and C curves
≤20 A
16 kA
16 kA 16 kA
25 kA
25 kA 25 kA
36 kA 36 kA
36 kA
50 kA 50 kA
50 kA
25 A
-
16 kA 16 kA
-
25 kA 25 kA
-
36 kA
36 kA
-
50 kA
50 kA
32 A
-
-
16 kA
-
-
25 kA
-
-
36 kA
-
-
50 kA
Association and coordination with upstream Moulded Case Circuit Breakers (MCCBs):
. Three-phase network (+N) 400/415 V, in accordance with standard IEC 60947-2
.TT neutral earthing or TNS system
Upstream MCCBs
DPX
³
160
16 kA
DPX
³
160
25 kA
DPX
³
160
36 kA
DPX
³
160
50 kA
Downstream
RCBO
16 A
25 A
40 to
160 A
16 A
25 A
40 to
160 A
16 A
25 A
40 to
160 A
16 A
25 A
40 to
160 A
DX³ 6000 A
B and C curves
≤13 A
16 kA
16 kA
16 kA 25 kA
25 kA 25 kA
25 kA
25 kA 25 kA
25 kA 25 kA
25 kA
16 A
-
16 kA
16 kA -
25 kA 25 kA
-
25 kA 25 kA
-
25 kA
25 kA
20 A
-
16 kA
16 kA -
25 kA 25 kA
-
25 kA 25 kA
-
25 kA
25 kA
25 A
-
-
16 kA -
-
25 kA
-
-
25 kA
-
-
25 kA
32 A
-
-
16 KA -
-
25 kA
-
-
25 kA
-
-
25 kA
Technical data sheet: F01315EN/03
Updated on: 30/05/2018
Created on: 27/05/11