background image

10 / 26 

 

DX³ 4

-pole RCBO  

6000 A/10 kA 

 

Cat. N°(s) : 

4 111 85, 86, 87, 88, 89  / 4 112 04, 05, 06, 07, 

4 112  08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35, 
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51, 
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81 

 

 

5. GENERAL CHARACTERISTICS 

(continued) 

Association  and  coordination  with  upstream  Moulded  Case  Circuit  Breakers  (MCCBs),  only  for  sensitivities  300mA  and 
1000mA: 

. Three-phase network (+N) 230/240 V, in accordance with standard IEC 60947-2 
. TT neutral earthing or TNS system 

 

Upstream MCCB 

 

DPX³ 250 25 kA

 

DPX³ 250 36 kA

 

DPX³ 250 50 kA

 

DPX³ 250 70 kA

 

Downstream RCBO 

≤ 250

≤ 250

≤ 250

≤ 250

DX³ 6000

A  

B and C curves 

≤32A

 

40 kA 

50 kA 

50 kA 

50 kA 

 
 

 

Upstream MCCB 

 

DPX / DPX-H  
250 

DPX / DPX-H 
630 

DPX / DPX-H 
1250 

DPX / DPX-H 
1600 

Downstream RCBO 

25 A 

40 to 250A 

≤ 630

 1250A 

≤ 1,600

DX³ 6000

A  

B and C curves 

20 A 

50 kA 

50 kA 

50 kA 

50 kA 

50 kA 

25A 

50 kA

 

50 kA

 

50 kA

 

50 kA

 

32A 

50 kA

 

50 kA

 

50 kA

 

50 kA

 

 
 

 

Upstream MCCB 

Downstream RCBO 

DPX 250 ER AB 

DPX  400 AB 

DX

³

 6000A  

B and C curves 

≤32 A

 

50 kA 

50 kA 

 

Selectivity between two levels of protection 

. The downstream MCB must always have a magnetic threshold and a rated current lower than those of the upstream protection. 
. Selectivity or Discrimination is said to be total (T) if there is discrimination up to the value of breaking capacity (in accordance with standard 
EN/IEC 60947-2) of the downstream MCB. 

Discrimination with upstream fuses, only for sensitivities 300mA and 1000mA: 

. Discrimination limit with a voltage of 230 V ~ (Values in A) 

 
 

Upstream fuse gG type 

Downstream RCBO 

32A 

40A 

50A 

63A 

80A 

100A 

125A 

160A 

DX³ 6000

A  

B and C curves 

10 A 

1600 

2200 

3200 

3000 

T

 

T

 

T

 

13A 

1400 

1800 

2600 

3000 

5600 

T

 

T

 

16A 

1400 

1800 

2600 

3000 

5600 

T

 

T

 

20A 

1200 

1500 

2200 

2500 

4600 

T

 

T

 

25A 

1300 

2000 

2200 

4100 

5500 

T

 

32A 

1200 

1700 

1900 

3500 

4500 

T

 

T = Total discrimination 

The downstream RCBO must always have a magnetic threshold and rated current lower than those of the upstream circuit breaker. 

 

 

 

Technical data sheet: F01315EN/03 

Updated on: 30/05/2018 

Created on: 27/05/11 

 

 

Содержание 4 111 85

Страница 1: ...es for closing and opening trip free mechanism 2 RANGE Polarity 4 protected poles Width 4 modules 4 x 17 8 mm 71 2 mm Rated currents In 10 13 16 20 25 32 A Magnetic tripping curve C between 5 and 10 I...

Страница 2: ...ed Cage terminals with release and captive screws Terminals fitted with shutters preventing a cable being placed under the terminal with the terminal partly open or closed Alignment and spacing of the...

Страница 3: ...nd contacts closed Trip indication on residual current fault Yellow indicator on the front Locking Padlocks possible in the open or closed positions with padlock support Cat No 4 063 03 and 5 mm padlo...

Страница 4: ...C 61009 1 Tested with 20 000 operations with no load Electrical endurance Compliant with standard EN IEC 61009 1 Tested with 10 000 operations with load at In x Cos 0 9 Tested with 2 000 residual curr...

Страница 5: ...ristics of a RCBO are modified depending on the ambient temperature which prevails in the cabinet or enclosure where the RCBO is located Reference temperature 30 C in accordance with standard IEC EN 6...

Страница 6: ...ristics of a RCBO are modified depending on the ambient temperature which prevails in the cabinet or enclosure where the RCBO is located Reference temperature 30 C in accordance with standard IEC EN 6...

Страница 7: ...40 to 125 A 25 A 32 A 40 to 80 A 25 A 32 A 40 to 63 DX 6000 A B and C curves 20 A 16 kA 16 kA 16 kA 25 kA 25 kA 25 kA 36 kA 36 kA 36 kA 50 kA 50 kA 50 kA 25 A 16 kA 16 kA 25 kA 25 kA 36 kA 36 kA 50 k...

Страница 8: ...50 to 630 A 500 to 1 250 A 630 to 1600 A DX 6000 A B and C curves 20 A 25 kA 25 kA 25 kA 25 kA 25 KA 25 A 25 kA 25 kA 20 kA 20 kA 32 A 25 kA 25 kA 15 kA 15 kA Upstream MCCB Downstream RCBO DPX 250 ER...

Страница 9: ...5 A 32A 40 to 80 A 25 A 32 A 40 to 63 A DX 6000 A B and C curves 20 A 32 kA 32 kA 25 kA 50 kA 50 kA 25 kA 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA 25 A 32 kA 25 kA 50 kA 25 kA 50 kA 50 kA 50 KA 50 kA 32 A...

Страница 10: ...am MCCB Downstream RCBO DPX 250 ER AB DPX 400 AB DX 6000A B and C curves 32 A 50 kA 50 kA Selectivity between two levels of protection The downstream MCB must always have a magnetic threshold and a ra...

Страница 11: ...eam RCBO 10A 13A 16A 20A 25A 32A 40A 50A 63A 80A 100A 125A DX 6000A B and C curves 10A 80 100 128 160 200 252 3000 5000 T 13A 100 128 160 200 252 2500 4000 6000 16A 128 160 200 252 2000 3600 5500 20A...

Страница 12: ...300 384 480 600 756 1600 3000 4000 25A 384 480 600 756 1300 2400 3300 32A 480 600 756 1100 1450 2700 Upstream MCB DX 25 kA B curve Downstream RCBO 10A 16A 20A 25A 32A 40A 50A 63A 80 A 100A 12 A DX 600...

Страница 13: ...25A 32A 40A 50A 63A 80A DX 6000A B and C curves 10A 120 150 210 500 700 1000 1800 3000 13A 120 150 200 400 600 1200 1500 2500 16A 150 187 300 500 700 1300 2000 20A 187 300 400 500 1000 1600 25A 240 40...

Страница 14: ...0 16 kA to 50 kA Downstream RCBO 16A 25A 40A 63A 80A 100A 125A 160A DX 6000A B and C curves 10A 5 T T T T T T T 13A T T T T T T T 16A T T T T T T T 20A 5 5 5 5 6 T T 25A 4 5 4 5 4 5 4 5 T T 32A 3 4 4...

Страница 15: ...Discrimination limit with a voltage of 230 V Values in A Upstream MCCB DPX 250 DPX H 250 Electronic DPX DPX H 630 1250 1600 DMX 2500 4000 Downstream RCBO 40A 100A 160A 250A 160 to 4000A DX 6000A B an...

Страница 16: ...mpliance with European Union Directives Compliance with Directive 2002 95 EC of 27 01 03 known as RoHS which provides for a restriction on the use of dangerous substances such as lead mercury cadmium...

Страница 17: ...12 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES Thermal magnetic tripping curve range typical of B and C curve RCBOs 1 h 0 01 s x In t 1 13 1 45 Thermal...

Страница 18: ...24 25 26 27 28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Average thermal magnetic tripping curves range typical...

Страница 19: ...25 26 27 28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Average thermal magnetic tripping curves range typical of...

Страница 20: ...1 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Current limiting curves Icc Prospective short circuit symmetrical current rms value in kA Ip Maximum peak value kA 1 Short circuit rms cu...

Страница 21: ...12 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Thermal stress limiting curves B curve 4 pole RCBO Icc Prospective short circuit symmetrical c...

Страница 22: ...12 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Thermal stress limiting curves C curve 4 pole RCBO Icc Prospective short circuit symmetrical c...

Страница 23: ...28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Tripping current curves Tripping time curve depending on the value...

Страница 24: ...28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Tripping current curves Tripping time curve depending on the value...

Страница 25: ...28 29 30 31 32 33 34 35 4 112 36 37 38 39 40 41 42 44 45 46 47 49 50 51 4 112 52 4 113 50 56 57 59 60 61 62 80 81 7 CURVES continued Tripping current curves Tripping time curve depending on the value...

Страница 26: ...mbinations of auxiliaries and RCBOs The auxiliaries are installed to the left of the RCBOs Maximum number of auxiliaries 3 Maximum number of 1 module signalling auxiliaries 2 Maximum number of control...

Отзывы: