14
1
INSERTING OF THE CABLES/
CABLES ENTRY
The XL³ S 160 are fitted with knockout
cable entries in order to mount cable
glands ISO 25 and/or ISO 32:
-
24 modules: 14 entries Ø 25 and
7 entries Ø 32
-
36 modules: 20 entries Ø 25 and
10 entries Ø 32
Ø 32 mm
Ø 25 mm
Ø 32 mm
Ø 25 mm
It’s also possible to cut rectangular areas to
allow the circulation of several cables.
The angles are pre-marked on the top
and at the bottom of the cabinet. The
cutting is done using a jigsaw or a tube
cutter.
Number
of
modules
Rectangular knockout
entries
Number and dimension
24
7 (62x80) mm
36
10 (62x80) mm
2
PROTECTIVE CONDUCTORS AND IP
2X DISTRIBUTION TERMINAL BLOCKS
First, you need to fit the mounting lugs
which are supplied with the cabinet
(2 lugs) by using the nuts.
Mounting
lug
Mounting nut
(tightening with a
10 mm spanner)
The brass terminal block Cat. No 0 373 00
can be fixed on the lugs supplied with the
cabinet (with the 2 screws and 2 nuts
supplied with the Cat. No 0 373 00).
4 positions in the cabinets are possible.
→ 2 at the top and/or 2 at the bottom.
Here is example with 2 earth terminal
blocks at the top of the cabinet.
Wiring and connection
SURFACE MOUNTING
CABINETS