10
SURFACE MOUNTING
CABINETS
4
FACEPLATES MOUTING
(CONTINUED)
■
Fitting
For the installation of control and
signalling units or devices with a voltage
U>50 V on the faceplate, it is necessary
to add an equipotential link conductor
between the faceplate and the cabinet.
To achieve this, you must bend the
connecting lug of the faceplate with
pliers.
Connect the conductor (Cat. No 3 397 53)
to the faceplate with a screw, a nut and 2
washers (not supplied) in order to ensure
the continuity.
The connection on the cabinet is made by
screwing a M6 nut (not supplied) on the
specified attachment points.
5
SIGNALLING
As well as the label-holders on all
DIN rail mounting equipment and the
plastic marking strip Cat. No 0 203 99,
a clip-on holder accessory is available
for 24 modules (Cat. No 3 397 55) and
36 modules (Cat. No 3 397 56).
6
FITTING THE DOORS
The solid or glass doors can be fitted to
open to the left or the right (see selection
table page 5).
The slots for the hinges and the door
release are provided on both sides of the
cabinet.
Door kit components: 2 axis, 2 hinges,
1 handle up to 5 rows, 2 handles from
6 rows, 1 key and 1 cross bolt and 2 lip seals
■
Finishes
To ensure the IP (Protection Index) of the
cabinet you must:
1- Clip the blanking keyhole (supplied
with the cabinet) on the side of the
hinges.
2-
Seal the holes at the opposite of
the hinges (1 at the top and 1 at the
bottom) by using the caps supplied
with the cabinet.