16 

Appendix 1: The table of the fault code 

Fault reason 

Fault code 

BUS voltage fault 

00-14 

Power soft start fault 

15-24 

Inverter voltage fault 

25-39 

Overheat 

40-44 

Output short circuit 

45-49 

Overload 

50-54 

Input NTC fault 

55-59 

Power fault 

60-64 

Input FUSE fault 

65-69 

Other 

88 

 

Appendix 2: Table for working status 

S/N  Working status 

LED on Front panel 

Alarm beep 

Note 

Normal 

Battery 

Bypass 

Fault 

Inverter mode (mains power) 

 

 

Mains power voltage 

● 

 

 

 

 

 

 

     

Mains power 

high/low voltage 

protection, switch to 

battery mode 

● 

● 

 

 

 

One beep / 4 sec   

 

 

Battery mode 

 

 

Battery voltage -   

normal 

● 

● 

 

 

 

One beep / 4 sec 

 

 

Warning for 

abnormal voltage of 

battery 

● 

 

 

 

 

One beep / sec 

 

 

Bypass mode 

 

 

Mains power 

– 

normal

under 

Bypass

 

 

 

 

 

● 

 

One beep / 2 mins   

Mains power 

– high 

voltage warning 

(under Bypass) 

 

 

 

 

● 

 

One beep / 4 sec 

 

 

Mains power 

– low 

 

 

 

 

● 

 

One beep / 4 sec 

 

 

Содержание 1-1 Series

Страница 1: ...using our products Please strictly obey all the instructions in this manual and pay attention to all the warning and operation information It is not advisable to install or operate the machine before...

Страница 2: ...S if any damage in transport If find damaged or parts missing do not power on please turn to the carrier and dealer To determine whether this UPS is the model you want to buy Check the model name show...

Страница 3: ...ry over 8 hours before used Once the AC mains power energizes the UPS it will automatically charge the battery Without prior charging UPS output remains as usual but with shorter back up time than nor...

Страница 4: ...E 1 2 5 V A C 3 5 A I N P U T O U T P U T S O C K E T T E L M O D E M F A X O U T I N R S 2 3 2 U S B E P O I N T E L L I G E N T S L O T O U T P U T L N G N D R E S E T R E S E T T O 7 2 V D C 4 0 A...

Страница 5: ...10mm2 10KVAH 10mm2 10mm2 10mm2 10mm2 10mm2 Note The cable for 6KVAS 6KVAS should withstand over 40A current It is recommended to use 10AWG or thicker wire for safety and efficiency The cable for 10KV...

Страница 6: ...er in OFF position and then install the battery pack Pay highly attention to the rated battery voltage marked on the rear panel if you want to change the numbers of the battery pack please make sure y...

Страница 7: ...nnecting N1 L2 it becomes three outputs one high voltage 208v 220v 230v 240V at L1 N2 two low voltage outputs 100v 110v 115v 120V at L1 N1 and L2 N2 However there is a limit for current rating at L1 N...

Страница 8: ...ls Correct installation procedure is highly vital or else probable electric shock will arise Users are strictly required to follow the below procedure Connect battery in correct way and make sure the...

Страница 9: ...function INQUIRING KEY Non function setting mode Press and hold or for more than half a second less than 2 seconds display the items orderly Press and hold for more than 2 seconds Circularly and order...

Страница 10: ...ted B The fan icon is for fan working indication when fan normally runs the icon will display rotation if the fan is not connected or faulty the icon blinks C Press the mute button under the battery m...

Страница 11: ...S are working in battery mode 3 4 2 Turn Off operation i Turn off the UPS in line mode Press and hold the OFF key for more than half a second to turn off the UPS and inverter After UPS shutting down L...

Страница 12: ...erface Press and hold the function setting key for more than 2 seconds then come to setting interface press and hold the function setting key for more than half a second less than 2 seconds select the...

Страница 13: ...is 220V Confirm the output voltage setting interface After selecting numerical value press and hold the function setting for more than half a second less than 2 seconds Now the OPU setting function is...

Страница 14: ...ce Press and hold function setting key for more than half a second less than 2 seconds exit from the setting interface and return to main interface 3 7 Parameters inquiring operation Press and hold th...

Страница 15: ...pproximately reckoned according to the battery voltage Press and hold the inquiring key for more than 2 seconds LCD begins to display the items circularly and orderly which transfer to another every 2...

Страница 16: ...w LED are on When the input mains meets the input range of the ECO mode and the ECO function is on the UPS will works in ECO mode If input AC mains exceed the range of ECO several times within one min...

Страница 17: ...le for working status S N Working status LED on Front panel Alarm beep Note Normal Battery Bypass Fault 1 Inverter mode mains power Mains power voltage N Mains power high low voltage protection switch...

Страница 18: ...arning for bypass mode overload One beep 2 sec 7 Fans fault fan icon One beep 2 sec 8 Faults mode Long beep LED indicator lights long time LED indicator flicker LED indicator status depends on other c...

Страница 19: ...Turn of the UPS and disconnect all the load make sure there no any fault or internal short circuit of the load And then restart the UPS if failure still please contact the supplier Fault LED on audibl...

Страница 20: ...ries If you want to replace the battery cable please purchase it from our local service center or distributors to avoid fever and lighter which can cause fire from inadequate power capacity Don t disp...

Страница 21: ...cancel Turn on Overload Turn off Battery inspection Standby or Shutdown Repeat AC Display screen repeat key DC Battery Appendix 3 Specification Sheet 1 3KVA Rated Capacity 1KVA 1 5KVA 2KVA 3KVA Input...

Страница 22: ...d rate 1Hz s Total voltage harmonic distortion Full linear load 3 Full nonlinear load 5 Battery Battery type Sealed lead acid maintenance free battery Quantity 2 3 4 4 6 6 8 DC voltage 24V 36V 48V 48V...

Страница 23: ...3 mins 125 150 30 secs 150 100ms Voltage accuracy 0 2 Load crest 3 1 From AC mode to BAT mode 0ms transfer time From BAT mode to AC mode 0ms transfer time Efficiency Mains mode 92 full load BAT mode 9...

Страница 24: ...Isolated 10KVA 10KVA Isolated Containing isolation transformers No Yes No Yes Dimension W D H Long 262 514 455 262 650 735 262 514 455 262 650 735 Standard 262 514 735 262 650 735 262 514 735 262 650...

Страница 25: ...ftware and hardware on the network such as running HP open view IBM net view SUN net manager and other operation system UPS is with function login on internet which can supply information of UPS statu...