Refrigeration Trouble Shooting Table
Problem
Area to Check
Area to Check
Potential Faults
Ice Melting
Condensing unit fan
motor running?
Yes
Evaporator fan
motor(s) running
with snowflake
icon illuminated?
Yes
No
Broken fan blade
Possible dirty condenser
Defective evaporator fan motor
Defective wiring to evaporator fan
motor(s)
Compressor
functioning?
No
Defective relay, overload, capacitor,
compressor, or component wiring
Compressor
functioning: ice
build-up on
compressor coil?
Yes
Evaporator hose obstructed or kinked
Defective wiring in defrost circuit
Possible defective defrost heat, circuit,
or controller
Compressor
functioning: no ice
build-up on
compressor coil?
Yes
Incorrect refrigerant
Wrong or low voltage
Impurities in refrigerant charge
Interior light
functioning?
Yes
No
Defrost icon (left
hand of control
display)
No
Defective controller wiring
Defective evaporator fan wiring
Defective bulb
Defective controller wiring
Defective evaporator fan wiring
Condensing unit fan
and compressor
running when
plugged into
substitute power
source
No
Defective motor
Defective wiring
Defective controller
Defective wiring in circuit