E-strikes

 

L

Note: This can only be used with cylindrical locks. These cannot be used with mortise locks, deadbolts, or rim 

exit devices. Allegion suggests a storeroom function for a cylindrical lockset when paired with an e-strike (ex. the 

Schlage ND-Series ND80).

 

L

Note: this e-strike is not rated for preloading (pressure against the strike when the door is closed).

1a  Prepare the door jamb, per the drawing below.

1b  Confirm whether the strike is for fail safe or fail secure mode.

1c  Install the mounting brackets to the jamb using M5 x 12mm screws and pressed metal nuts. Do not tighten.

1d  Install electric strike jamb by attaching with #10-32 screws and lock washers.

1e  Secure M5 x 12 screws hold mounting brackets to jamb.

How to modify fail-safe to fail-secure, or vice versa.

1a  Loosen the screw, as per the product diagram below.

1b  Rotate the set plate 180° and slide the plate until it is properly seated.

1c  Tighten the screw.

Fail-Safe mode when 

Mode Selector is pointing to Fail Safe

Fail-Safe mode when 

Mode Selector is pointing to FS

Fail-Lock mode when

Mode Selector is pointing to Fail Lock

Set Screw

Mode Selector

Mode Selector

Set Screw

 

L

Note: The products are intended to be installed in accordance with the installation wiring diagram, mechanical 

assembly drawings provided with each product, the local authority having jurisdiction (AHJ) and the National 

Electric Code, NFPA 70. When installed in fail secure mode (power loss results in locked door), the local authority 

shall be consulted with regard to the use of possible panic hardware to allow emergency exit from the secure area. 

The electric door strike shall be installed in such a way and in such a location so as to not impair the operation of 

an emergency exit device or panic hardware mounted on the door.

Mounting Bracket

Spacer

(optional by others)

Spacer

(Optional by others)

Spacer

(Optional

by others)

M5x12mm Flat-Head Screw (2pcs)

Optional Trim Plate

Jamb

M5x12mm

Flat-Head

Screw

      

(86mm)

3-3/8”

(187mm)

7-3/8”

(36mm)

1-3/8”

(200mm)

7-7/8”

(86mm)

3-3/8”

(86mm)

3-3/8”

(168mm)

6-3/8”

(31mm)

1-7/32”

(31mm)

1-7/32”

(31mm)

1-7/32”

(105mm)

4-1/8”

(124mm)

4-7/8”

(89mm)

3-1/2”

(155mm)

6-1/8”

(173mm)

6-7/8”

(144mm)

5-11/16”

ANSI square/Hollow metal

Aluminum

Wood

Содержание 8310-2420

Страница 1: ...for Door to Close vinyl decal 1 9 Door locked when red unlocked when green black vinyl sign 1 10 Door occupied when red vacant when green black vinyl sign 1 11 E strike with 3 faceplates and hardware...

Страница 2: ...B2 Power 50 VA DPS Switch Descriptions 8310 2420 Series Power max 3 0 W Electrical configuration SPDT Suggested Wiring 22AWG Gap distance max 0 75 Operation at a glance When the exterior PUSH TO OPEN...

Страница 3: ...onic board in place 1e Place the diffuser insert inside the flush enclosure making sure the mounting screw holes on the diffuser insert and the flush enclosure align For Push to Open switches a Use th...

Страница 4: ...Safe mode when Mode Selector is pointing to FS Fail Lock mode when Mode Selector is pointing to Fail Lock Set Screw Mode Selector Mode Selector Set Screw L Note The products are intended to be instal...

Страница 5: ...r The transformer should only be installed OUTSIDE of the Power Supply Cabinet per all National Electric Code NEC NFPA 70 requirements along with local code requirements and it should be kept in close...

Страница 6: ...ently off Do not wire the primary terminals of the transformer until the secondary terminals are connected first The supplied transformer will have its secondary terminals wired to the terminals red w...

Страница 7: ...ls in cabinet via wire access hole RED GREEN BLUE Connected to 24V DC from the VDC terminals in the cabinet via wire access hole REM LOC RELAY SPEAKER Wired to the Inside Push to Open terminals in the...

Страница 8: ...0 50 seconds The second option d 1 flashing will be how long to wait before activating relay 2 0 15 seconds The third option H 2 flashing will be how long relay 2 will be activated for 0 50 seconds T...

Страница 9: ...2 3 ON DP RED GREEN BLUE REM LOC RELAY SPEAKER See the diagrams below for the dip switch functionalities Enable Dip Switch Bank Idle COL Dip Switch Bank Switch number Description Switch number Descrip...

Страница 10: ...K THIS DOOR WAIT FOR DOOR TO CLOSE Place sign on the door inside the restroom at eye level INSIDE THE RESTROOM POWER SUPPLY 6 12 24 VDC SMP3 24V OPEN CLSD CLSD OPEN SW1 SW2 6V OPEN OPEN 12V SW1 SW2 AC...

Страница 11: ...shown connecting the Push to Open switch to the Push to Open terminals Com Rem PBTN N O Pwr AC DC Com Rem PBTN N O Pwr AC DC IMPORTANT Ensure wiring polarity is consistent from Relay 3 to each remote...

Страница 12: ...osing the door or after pushing Push to Lock Logic Module not in Mode 7 Change Logic Module to Mode 7 and ensure all mode 7 settings are set as shown in the instructions No power to the strike Ensure...

Страница 13: ...he solenoid releases This can be caused by too much stack pressure on the door pressing on the strike Electric Strike itself is set to Fail Secure rather than Fail Safe Follow the electric strike inst...

Страница 14: ...is latching then the door may not fully latch If this occurs the source of the pressure force needs to be removed so that the door can fully close This can be caused by too much stack pressure preven...

Страница 15: ...inals Take a jumper wire and touch the screw heads of the PBTN and terminals the actuators wires are hooked up to If the unit acts as if the actuator was actually pushed then either the actuator was w...

Страница 16: ...ion DPS switch not closing contact Wiring issue Verify wiring is correct to Power Supply Relay Cabinet and DPS wires fully connected Incorrect mounting Mounting gap should be no more than 3 4 between...

Страница 17: ...7 Cabinet base template 9 8 6...