Installation
28
Part No. 70476501ENR7
Level the tumble dryer to within 0.125 inch (3 mm) from front-
to-rear (level on cylinder rib), and side-to-side (level on top
panel). Shim under corners to level and stabilize unit. Tumble
dryer must not rock.
Fire Suppression System (Optional
Equipment)
WARNING
Electrical shock can result in death or serious
injury. If the water dispensing system is activated,
do not attempt to operate the tumble dryer. If the
water dispensing system is activated, have the
tumble dryer inspected by a qualified agency before
operating the tumble dryer.
W879
Check Local Codes and Permits
Call your local water company or the proper municipal authority
for information regarding local codes.
IMPORTANT: It is your responsibility to have
ALL plumbing connections made by a qualified
professional to assure that the plumbing is adequate
and conforms to local, state, and federal regulations
or codes.
IMPORTANT: It is the installation or owner’s
responsibility to see that the necessary or required
water, water pressure, pipe size, or connections are
provided. Manufacturer assumes no responsibility
if the fire suppression system is not connected,
installed, or maintained properly.
Water Requirements
IMPORTANT: Water must be supplied to the fire
suppression system, or the fire suppression system
will not operate as intended.
Connection point to the electric water solenoid valve is a
3/4 inch (19 mm) hose. The fire suppression system equipped
tumble dryer must be supplied with a minimum water pipe
size of 1/2 inch (12.7 mm) and be provided with a minimum
of 20 psi (138 kPa) and a maximum of 120 psi (827 kPa)
of pressure at all times. Flowrate must be no less than, but
approximately 15 gallons (57 liters) per minute.
NOTE: Water pressure under 20 psi (138 kPa) will
cause low flow and water leakage at water solenoid
valve.
If the rear of the tumble dryer or the water supply is located in
an area where it will be exposed to cold/freezing temperatures,
provisions must be made to protect these water lines from
freezing.
IMPORTANT: Temperature of the water supply must
be kept between 40°F and 120°F (4.4°C and 48.9°C)
. If water in the supply line or water solenoid valve
freezes, the fire suppression system will not operate.
IMPORTANT: If temperature sensors inside the tumble
dryer register a temperature below 40F° (4.4°C) , the
fire suppression system control will lock out. This
feature protects against operation of the tumble dryer
with a possible frozen water supply. Only when the
temperature sensors register a temperature above
40F° (4.4°C) will the machine reset for operation.
IMPORTANT: Flexible supply line/coupling must be
used. Solenoid valve failure due to hard plumbing
connections will void the warranty. It is recommended
that a filter or strainer be installed in the water supply
line.
Water Connections
Two hoses and a Y-valve are provided with the tumble dryer to
allow for connection of water supply to tumble dryer. The water
connections are made to the bushings of the water solenoid
valve, located on the rear of the tumble dryer. The Y-valve
provides a single female hose connection (Standard US 3/4-11
1/2 NH thread). Refer to Figure 3 and Figure 4 .