Start-Up 

 
 

3.3 Chiller start-up 

 

 

When the ultracool unit is started for the first time, it is necessary to turn 
ON the Main power switch (element 1 in the control panel, see point 4) 
and wait 

six

 hour

s

 before continuing with the start-up sequence. This 

time is necessary for the crankcase of the compressor to heat it up. 
 
The oil in the crankcase of the compressor remains warm whenever the 
main power switch is in the ON position and the unit is connected to the 
line voltage. For this reason stop the ultracool unit by using the off-
switch, leaving the Main power switch in the ON position. 
 
Fill the tank 

with water of the required quality (see annex 9)

 

or with 

refrifluid

 through the provided connection until the maximum level of the 

tank is reached. 
 
Start the ultracool unit with the On/Off switch (element 2 in the control 
panel, see point 4). Stop the ultracool unit and refill the tank to the 
correct water level.  
 
Repeat this procedure until the water level in the tank remains constant. 
 

It’s necessary to verify the direction of rotation of the pump at the 
initial start up. 

To do so, start and stop the ultracool unit, using the 

On/Off switch (it is easier to see the turn direction when the pump is 
stopping). In the case of the pump rotating in the opposite direction from 
the indicated, it will be necessary to exchange two phases in the main 
power supply. It will not be necessary to check the turn direction of the 
fans, because they are delivered in phase with the pump. Since it may 
be difficult to see the pump’s rotation direction, verify that you did this 
operation correctly when the motor fan starts working: The air should 
enter the condenser and go out through the top of the chiller. If the air is 
moving in the opposite direction then exchange two phases in the main 
power supply. 
 
Connect the On/Off switch so that the ultracool unit starts. At the same 
time the digital thermometer and all the indicators that should light up will 
turn on too, according to their function.  
 
On the control thermostat select the desired temperature of the cold 
water outlet (see point 4.2.1). The ultracool units are delivered with a 
pre-set temperature of 10ºC (50ºF). 
 
Adjust the water pressure, using an external valve at the ultracool outlet, 
to the value indicated on the data plate (Nominal pressure). 

 

UC-140 

IND

IGO 

 50

/60Hz 

30

.0

4

.0

3 re

v.

 

1

 

Содержание Ultracool Superplus series

Страница 1: ...OPERATION MANUAL ultracool mini 0140 Indigo Ref MI 080 Rev 1 Date 30 04 03 50 60 Hz...

Страница 2: ...The basic maintenance as indicated in point 5 1 should be carried out by properly trained personnel and if necessary under the supervision of a person qualified for this job ultrafilter personnel or p...

Страница 3: ...t up of the ultracool unit 7 3 3 Chiller strat up 8 4 Control Panel 4 1 Components of the control panel 9 4 2 Control thermostat 10 4 2 1 Operation 10 5 Maintenance 5 1 Basic maintenance 11 6 Troubles...

Страница 4: ...ded application in order to undertake additional safety measures if necessary 1 2 Safety regulations The operator has to observe the national working operating and safety regulations Also existing int...

Страница 5: ...compressor The ultracool unit must be transported by palet jack or forklift truck 2 3 Site The ultracool unit must be installed in an atmosphere where the range of temperatures is within the indicated...

Страница 6: ...nstallation the concentration of ethylene glycol should be checked Do not use automotive antifreeze Use lab grade ethylene glycol or refrifluid only Do not use an ethylene glycol concentration above t...

Страница 7: ...r outlet of the ultracool unit and a solenoid valve in the water inlet The supply of this solenoid valve will be carried out by terminals designed for that purpose see electrical diagrams 2 7 Electric...

Страница 8: ...of the ambient air Nominal 25 C 77 F Minimum 15 C 5 F 2 Maximum 50 C 122 F 1 For ambient temperatures below 5 C 40 F it is necessary to add ethylene glycol to the water of the circuit see point 2 4 3...

Страница 9: ...ial start up To do so start and stop the ultracool unit using the On Off switch it is easier to see the turn direction when the pump is stopping In the case of the pump rotating in the opposite direct...

Страница 10: ...when the compressor is working 7 Water level alarm indicator this is lit when the water level in the tank is too low It causes the ultracool unit to stop 8 Low flow temperature control indicator This...

Страница 11: ...probe In the 50Hz version the display shows the temperature in C and in the 60Hz version it shows it in F as depicted above Setting the temperature Follow these steps to introduce the required workin...

Страница 12: ...r filter if the pressure drop exceeds 0 5 bar 8 psi change the filter element Monthly With the Unit disconnected Main power switch Off clean the condenser with a blast of compressed air from the insid...

Страница 13: ...ation stopped Check the motor fan fuses If the problem persists contact authorised technical service Disconnect the chiller On Off and Main power switch both Off see point 4 Open the front panel of th...

Страница 14: ...following codes LO HI E0 Er2 EE The temperature has been below the setpoint for some minutes The temperature has been above the setpoint for some minutes Thermostat or temperature sensor is faulty If...

Страница 15: ...5 kW 1 1 1 0 max flow 4000 17 6 4000 17 6 min flow l h US gal min 400 1 8 400 1 8 max pres 6 3 91 6 3 91 Water pump min pres bar psi 3 3 48 3 3 48 Water tank volume litre US gal 100 26 100 26 Water co...

Страница 16: ...15 8 Log Book 8 Log Book 8 1 Log Book Date Remarks Signature UC 140 INDIGO 50 60Hz 29 01 03 rev 0...

Страница 17: ...below 50 S cm The product refrifluid supplied by ultrafilter includes in its composition an anticorrosive bactericide and antifreeze until 7 C 19 4 F It has the following characteristics Parameter Lim...

Страница 18: ...6003 E5326003 Sight glass 1 0107397000 0107397000 Refrigerant gas kg lb 14 31 R 134a R 134a Level control 1 E4202004 E4202004 Water by pass 1 E2301002 E2301002 Pump pressure gauge 1 E5544014 E5544022...

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Отзывы: