Lauda Ultracool Superplus series Скачать руководство пользователя страница 5

 

-      - 

4

 

 
 

Installation 

 

2 Installation

 

 

 

2.1 Reception and Inspection 

 

On receipt of the ultracool unit, it must be inspected for damage during 
transport. In the case of any damage, external or internal, this cannot be 
referred to the manufacturer because all units are checked before 
dispatch. 

If any damage is observed, this should be documented 

and reported to the forwarding company. The ultrafilter warranty 
does not include any damages incurred during transportation. 

 

 

The refrigerant circuit controls are set before shipment of the unit. They 
should not be re-adjusted under any circumstances (except by our 
ultrafilter service department). This would void the warranty of the unit.

 

 

2.2 Transportation 

 

 Keep the unit upright at all times. Do not tilt when shipping or moving. 

The tilting of the ultracool unit may affect the internal suspension 
of the refrigerant compressor. 

 

 

The ultracool unit must be transported by palet jack or forklift truck. 

 

2.3 Site 

 

The ultracool unit must be installed in an atmosphere where the range of 
temperatures is within the indicated margins mentioned in point 3.1. For 
ambient temperatures lower than 5ºC (41ºF) it is necessary to add 
ethylene glycol to the water of the circuit, as indicated in point 2.4.  
  
We recommend the installation of the ultracool unit in a well-ventilated 
site and in a corrosive-free, dust-free atmosphere. 
 
In the case of out-door installation the chiller must be protected from rain 
with a roof and it must be installed in such way that the control panel 
receives as few direct sunlight as possible.  
 
A space of 1 m (4 ft) should be left around the ultracool unit to facilitate 
maintenance work and cleaning, especially in front of the condensor 
grid. The inlet of fresh air onto the condensor should be in the most 
direct way possible, avoiding any chance of air recycling (the ceiling 
above should not be at less than 1 m (4 ft)). 
 

UC-140 I

NDI

GO 

 50/

60Hz 29.

01.

03

 rev

. 0 

Содержание Ultracool Superplus series

Страница 1: ...OPERATION MANUAL ultracool mini 0140 Indigo Ref MI 080 Rev 1 Date 30 04 03 50 60 Hz...

Страница 2: ...The basic maintenance as indicated in point 5 1 should be carried out by properly trained personnel and if necessary under the supervision of a person qualified for this job ultrafilter personnel or p...

Страница 3: ...t up of the ultracool unit 7 3 3 Chiller strat up 8 4 Control Panel 4 1 Components of the control panel 9 4 2 Control thermostat 10 4 2 1 Operation 10 5 Maintenance 5 1 Basic maintenance 11 6 Troubles...

Страница 4: ...ded application in order to undertake additional safety measures if necessary 1 2 Safety regulations The operator has to observe the national working operating and safety regulations Also existing int...

Страница 5: ...compressor The ultracool unit must be transported by palet jack or forklift truck 2 3 Site The ultracool unit must be installed in an atmosphere where the range of temperatures is within the indicated...

Страница 6: ...nstallation the concentration of ethylene glycol should be checked Do not use automotive antifreeze Use lab grade ethylene glycol or refrifluid only Do not use an ethylene glycol concentration above t...

Страница 7: ...r outlet of the ultracool unit and a solenoid valve in the water inlet The supply of this solenoid valve will be carried out by terminals designed for that purpose see electrical diagrams 2 7 Electric...

Страница 8: ...of the ambient air Nominal 25 C 77 F Minimum 15 C 5 F 2 Maximum 50 C 122 F 1 For ambient temperatures below 5 C 40 F it is necessary to add ethylene glycol to the water of the circuit see point 2 4 3...

Страница 9: ...ial start up To do so start and stop the ultracool unit using the On Off switch it is easier to see the turn direction when the pump is stopping In the case of the pump rotating in the opposite direct...

Страница 10: ...when the compressor is working 7 Water level alarm indicator this is lit when the water level in the tank is too low It causes the ultracool unit to stop 8 Low flow temperature control indicator This...

Страница 11: ...probe In the 50Hz version the display shows the temperature in C and in the 60Hz version it shows it in F as depicted above Setting the temperature Follow these steps to introduce the required workin...

Страница 12: ...r filter if the pressure drop exceeds 0 5 bar 8 psi change the filter element Monthly With the Unit disconnected Main power switch Off clean the condenser with a blast of compressed air from the insid...

Страница 13: ...ation stopped Check the motor fan fuses If the problem persists contact authorised technical service Disconnect the chiller On Off and Main power switch both Off see point 4 Open the front panel of th...

Страница 14: ...following codes LO HI E0 Er2 EE The temperature has been below the setpoint for some minutes The temperature has been above the setpoint for some minutes Thermostat or temperature sensor is faulty If...

Страница 15: ...5 kW 1 1 1 0 max flow 4000 17 6 4000 17 6 min flow l h US gal min 400 1 8 400 1 8 max pres 6 3 91 6 3 91 Water pump min pres bar psi 3 3 48 3 3 48 Water tank volume litre US gal 100 26 100 26 Water co...

Страница 16: ...15 8 Log Book 8 Log Book 8 1 Log Book Date Remarks Signature UC 140 INDIGO 50 60Hz 29 01 03 rev 0...

Страница 17: ...below 50 S cm The product refrifluid supplied by ultrafilter includes in its composition an anticorrosive bactericide and antifreeze until 7 C 19 4 F It has the following characteristics Parameter Lim...

Страница 18: ...6003 E5326003 Sight glass 1 0107397000 0107397000 Refrigerant gas kg lb 14 31 R 134a R 134a Level control 1 E4202004 E4202004 Water by pass 1 E2301002 E2301002 Pump pressure gauge 1 E5544014 E5544022...

Страница 19: ......

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Отзывы: