background image

ICS-7-OEM Instruction Manual 

 

02058-53-000 

Page 22 of 29

 

Issue 3          19 January 2021 

 

Mismatch Detector 

 
The ICS-7-OEM trips out and disables the laser when either of its two safety circuits opens. If all the 
door  interlock  and  emergency  stop switches  have two  contacts, one  in each safety loop, then it  is 
normal for both safety circuits to open more or less simultaneously. 
 
When the ICS-7-OEM Safety Circuit Mismatch Detection is enabled, if the second safety circuit does 
not open within a short time of the first (typically around 1 second), a mismatch is triggered and the 
Fault light illuminates on the front panel. It is then not possible to arm the system. 
 
The ICS-7-OEM can also detect a mismatch between its two ‘Output Monitor’ circuits. If for example 
these terminals are being used to monitor a pair of power contactors, should one of the contactors 
become  welded  ‘on’  a  mismatch  will  be  indicated  and  the  system  will  be  locked  out  until  the 
contactor is repaired and the ICS-7-OEM is reset. 
 
Safety Circuit Mismatch Detection can only be used if all inputs to the ICS-7-OEM are dual channel. 
This  includes  all  the  door  contacts  and  emergency  stop  buttons.  If  any  input  only  operates  one 
channel, then a mismatch will inevitably occur and the mismatch detector will be triggered. In the 
event that it is not possible for all of the inputs to be dual channel, the mismatch detector must be 
disabled as described later in this section. Note that the use of a single channel safety contact and 
the disabling of the mismatch detector will reduce the achievable safety performance level of the 
system. 
 

8.1  Configurable Options for Safety Circuit Mismatch Events 

 

Mismatch Event Behaviour 

 
In  the  event  of  a  mismatch  being  detected  either  of  the  following  two  actions  are  available 
depending on the option switch settings: 
 
a) Lock out, preventing further use, unless the system is reset by switching it off and on again; 
 
b) Lock out, preventing further use, unless the system is attended to by a qualified technician. 
 
Option  a)  is  suitable  for  mission-critical  applications  where  the  inability  to  use  the  laser  would  be 
costly or inconvenient. Having detected and indicated that there is a fault it allows the system to be 
reset to operate on the one good safety circuit provided the faulty circuit has been closed. The need 
to  manually  reset  the  system  before  it  can  be  used  provides  a  clear  indication  to  operators  that 
there  is  a  problem  that  needs  to  be  addressed  at  the  earliest  opportunity  and  that  other  risk 
limitation steps may be required in the interim. An example might be to secure the affected door out 
of use until it can be repaired. 
 
Option b) is the lowest risk option, as once a safety circuit fault has been detected the system cannot 
be  used.  The  ICS-7-OEM  can  only  be  reset  by  opening  the  cabinet  in  which  it  is  mounted  and 
operating the Fault Reset button. Procedures should indicate that this is only carried out by suitably 
trained technicians once the fault has been repaired. 
 
By default, the mismatch detector is factory set to be enabled in option ‘a’ above. 

Содержание ICS-7-OEM

Страница 1: ...ICS 7 OEM Instruction Manual 02058 53 000 Issue 3 19 January 2021 LASERMET ICS 7 OEM INSTRUCTION MANUAL FAIL SAFE LASER INTERLOCK CONTROLLER...

Страница 2: ...7 OEM Illuminated Sign Control Output 14 6 3 Interlock Operator Output Contacts 15 7 Expansion Boards 20 7 1 Installing Expansion Boards 21 7 2 Use with Active Guarding 21 7 3 Expansion Board Fault Ou...

Страница 3: ...ies with the basic requirements for health and safety as provided by the following directives and standards Directives Machinery Directive 2006 42 EC June 2010 Low Voltage Directive 2014 35 EU EMC Dir...

Страница 4: ...fixing holes They must not come into contact with each other or any other moving part when in use The parts should never be subject to impact or mechanical strain Safety switches should never be defe...

Страница 5: ...mance level e Eight safety interlock outputs each rated at 4A resistive 50VDC are provided to enable the laser operate door locks or provide signals to a PLC The interlock outputs are volt free contac...

Страница 6: ...ny queries Contact details are given at the end of this manual 3 1 Differences between ICS 7 OEM and ICS 6 OEM Power supply to expansion modules is now switched on in the disarmed state allowing visua...

Страница 7: ...be wired as described in this manual using suitably rated door sensors and measures taken to minimise the effects of common cause failures in the sensors and wiring which may be connected to the unit...

Страница 8: ...sition for wiring It should be inaccessible by operators It has indicator lights on its top surface which would normally only need to be observed by installation and maintenance personnel Provision sh...

Страница 9: ...controller All dual channel inputs and outputs are wired ABBA with one channel connected A A and the other channel B B Input signals are connected on the right bottom of the controller and are indica...

Страница 10: ...satile interlock system and there are a variety of ways in which it can be used Be sure you know which configuration you require before you attempt to wire the unit If you require further assistance p...

Страница 11: ...lock switch should have two safety contacts which are closed when the door is closed Some door contacts such as Lasermet s IS MECH switches have an additional monitor contact which closes when the doo...

Страница 12: ...ls Fit a wire link across the B terminals The Mismatch Detector cannot be used and must be disabled see the Mismatch Detector section below It is usual to use low voltage 4 core flexible cable for the...

Страница 13: ...cts which open when the button is pressed 2NC Connect one safety contact which opens when the button is pressed to the A terminals of the E STOP terminal block Connect the other safety contact to the...

Страница 14: ...er is armed One of the seven normally open outputs of the ICS 7 OEM is used to illuminate the sign This output must not then be used to operate a laser interlock as well Option 2 Two way Illuminated W...

Страница 15: ...directly wired to the ICS 7 OEM Where there is any possibility of the equipment being changed or moved it is often most convenient to be able to unplug the equipment Lasermet provide a range of small...

Страница 16: ...l only work off 12VDC LS 20 and LS 200 Shutter The LS 20 and LS 200 Shutters can use the above circuit however it is recommended that the monitoring circuit shown below is included to allow the ICS 7...

Страница 17: ...t the shutter closes when the Interlock Operator contact opens Any ICS 7 OEM output used for shutters must not also be used for laser interlock control The contact is limited to 4A resistive load If y...

Страница 18: ...13849 1 and feature two interlock input channels This will require a distribution plug and socket with more connections Furthermore some lasers also include one or two laser safe contacts which can be...

Страница 19: ...ile always allowing people to enter or leave the room in the event of a power loss In order to ensure that people can always enter or leave the room in the event of an emergency it will be necessary t...

Страница 20: ...used with lasers which are potentially capable of damaging or burning through their enclosures The enclosure is lined with replaceable active detection panels If the laser burns through the panel it...

Страница 21: ...s to be seen On closing the Arm inputs the switched 24V supply is switched off momentarily to test the operation of the Active Guarding circuits then switched back on if the test succeeds NOTE This be...

Страница 22: ...ote that the use of a single channel safety contact and the disabling of the mismatch detector will reduce the achievable safety performance level of the system 8 1 Configurable Options for Safety Cir...

Страница 23: ...lus interface card generates a mismatch event during its start up sequence so if this expansion card is being used the pre check mismatch detection must be disabled by setting Option 3 to On Mismatch...

Страница 24: ...the system has been wired up For each Interlock a pair of yellow LEDs indicate that the interlock is open If the contact is not used and a wire link has been fitted the corresponding LED will not ill...

Страница 25: ...is triggered which disables the system and illuminates a red Fault light on the front panel The Mismatch Detector also monitors the internal relays of the controller and the safety proving contacts o...

Страница 26: ...illuminated in yellow This may occur if an expansion board has detected a fault or if the expansion socket is open and no termination plug has been fitted 10 Operation Once correctly wired the ICS 7 O...

Страница 27: ...s power to the shutters or the laser and may result in accessible laser beams depending on your system set up This action should only be taken when everyone is ready and the necessary safety precautio...

Страница 28: ...Weight 0 8kg Dimensions are approximate Values given as typical are average values measured across a number of samples and are not guaranteed Lasermet reserve the right to alter any specification wit...

Страница 29: ...ovide a complete system We also supply equipment and consultancy covering all aspects of laser safety Full support design and installation is available from Lasermet please contact us for any queries...

Отзывы: