background image

PAGE 7

1.  The above picture shows the installation of a typical disinfection system and the related components that may be 

used for the installation. The use of a by-pass assembly is recommended in case the system requires “off-line” 

maintenance. If this is the case, it must be noted that the system will require supplementary disinfection of the 

distribution system if any water is used during this by-pass condition. In addition, during by-pass, the water will NOT 

be disinfected. Please refer to the complete disinfection procedure as outlined on page 8 of this document. If the 

water is to be consumed while the system is off-line, the water must be boiled for twenty minutes prior to consumption.

2.  Select a suitable location for the disinfection system and its related components. As it is recommended to install a 

ground fault protected circuit (GFCI), make sure that this is taken into consideration prior to any installation. The 

system can either be installed vertically( inlet port at the bottom), or horizontally, however the vertical installation is 

the most preferred method. When selecting a mounting location, you must also leave enough space to allow for the 

removal of the UV lamp and/or quartz sleeve (minimum clearance equal to disinfection system overall length; refer to 

dimensions page).

3.  Install the quartz sleeve as outlined on page 9.
4.  Mount the system to the wall using the supplied clamps. Various connection methods can be used to connect the 

water source to the system, however union type connectors are recommended. The use of a flow restrictor device is 

strongly recommended when installing your system in order to maintain the manufacturer’s rated flow rate. The flow 

restrictor should be installed on the outlet port and is designed to be installed in one direction only. Ensure that the 

flow of the water matches the flow direction as indicated on the flow restrictor. 

DO NOT SOLDER CONNECTIONS 

WHILE ATTACHED TO THE SYSTEM AS THIS COULD DAMAGE THE O-RING SEALS.

5.  Mount the electronic ballast controller horizontally to the wall, near the UV reactor chamber. Ideally place the controller 

above the reactor and away from any water connection point, to prevent any water from potentially leaking onto the 

controller by means of a leak at a connection point or a “sweating” system. Make sure you allow for a “drip-loop” on 

the lamp power cord, again to prevent any water from potentially entering the controller. A ground stud and nut are 

provided on the UV reactor chamber. Attach the supplied 3 foot long, #14 AWG green ground wire to this ground stud 

using the ring terminal end. Attach the fork teminal end of the ground wire to the electronic ballast controller ground 

screw.

6.  Install the UV lamp as outlined on page 9.
7. 

When all plumbing connections are made, slowly turn on the water supply and check for leaks. The most likely cause 

for leaks is from the o-ring seal. In case of leak, shut water off, drain chamber, remove the gland nut assembly, wipe 

the o-ring and threads clean and re-install. Refer to exploded view diagram page.

8. 

Once it is determined that there are no leaks, plug the system into the GFCI, and check electronic ballast controller 

to ensure the system is operating properly. The controller is designed to detect both power to the system and lamp 

illumination. It is important to NEVER LOOK DIRECTLY AT THE GLOWING UV LAMP.

9.  Allow the water to run for a few minutes to clear any air   or dust that may be in the UV chamber.

PLEASE NOTE:

 When there is no flow, the water in the chamber will become warm, as the UV lamp 

is always on. To remedy this, run a cold water tap anywhere in the house for a minute to flush out the 

warm water.

Click to buy NOW!

PD

F-XCHANGE

w

ww

.docu-track.c

om

Click to buy NOW!

PD

F-XCHANGE

w

ww

.docu-track.c

om

Содержание 7-LWT-UV009

Страница 1: ...RTIFIED PLUMBER IS RECOMMENDED In the event that you need assistance for servicing your UV system please first contact the professional contractor who installed the system Congratulations on purchasing your new Lancaster Water UV Disinfection System This unit is designed to give you many years of trouble free service For servicing and future inspection purposes please file this booklet with your i...

Страница 2: ...rforming any cleaning or maintenance activities Never yank the cord to remove from an outlet grasp the wall plug and pull to disconnect 8 Do not use this disinfection system for other than intended use potable water application The use of attachments not recommended or sold by the manufacturer distributor may cause an unsafe condition 9 Intended for indoor use only Do not install this disinfection...

Страница 3: ...t a lower performance than intended Qty 2 21S UV Electronic Ballast Mounting Screw Qty 2 21A UV Electronic Ballast Mounting Anchor Ground Screw attached Model SS UV Chamber Domed Quartz Sleeve length 7 LWT UV009 7 LWT UV016 7 LWT UV030 100 UV 200 UV 300 UV 7 Q6 13 1 8 7 Q10 21 3 8 7 Q20 34 3 4 UV Lamp A Four pins 7 L6 11 13 16 7 L10 20 1 16 7 L20 33 3 16 18 UV Lamp Compression Spring 14 UV Aluminu...

Страница 4: ...ONIC BALLAST CONTROLLER MODEL 7 LWT UV009 7 LWT UV016 7 LWT UV030 INLET OUTLET A B C D E F DIA 1 0 MNPT 1 0 MNPT 1 5 MNPT 3 1 2 3 1 2 3 1 2 5 17 3 8 13 3 8 1 3 8 13 9 16 5 25 5 8 21 11 16 21 13 16 1 3 8 5 1 4 2 1 8 39 3 4 35 1 16 35 9 16 C l i c k t o b u y N O W PDF XCHANGE w w w docu track c o m C l i c k t o b u y N O W PDF XCHANGE w w w docu track c o m ...

Страница 5: ...ctor POWER CONSUMPTION 34 W 29 W 45 W 50 W 90 W 80 W LAMP WATTS LAMP TYPE LOW PRESSURE HIGH OUTPUT LPHO ELECTRICAL MAXIMUM OPERATING PRESSURE 125 PSI AMBIENT AIR WATER TEMPERATURE 36 to 104 F PRESSURE DROP at 30mJ cm RATED FLOW 2 LESS THAN 1 PSI CHAMBER MATERIAL 304 SS INLET OUTLET PORT SIZE 1 0 MNPT 1 0 MNPT 1 5 MNPT STEADY WORK GREEN LED LAMP ON INDICATOR LAMP LIFE REMAINING DAYS CONTINUES TO BE...

Страница 6: ...llation is vertical with the lamp connector on top This is to prevent water damage from occurring on the lamp connector and lamp pins Leave space at least equal to the overall length of the disinfection system to allow clearance for the removal and replacement of the lamp and or quartz sleeve The electronic ballast should be mounted either above or beside the stainless steel UV reactor chamber Nev...

Страница 7: ...y Ensure that the flow of the water matches the flow direction as indicated on the flow restrictor DO NOT SOLDER CONNECTIONS WHILE ATTACHED TO THE SYSTEM AS THIS COULD DAMAGE THE O RING SEALS 5 Mount the electronic ballast controller horizontally to the wall near the UV reactor chamber Ideally place the controller above the reactor and away from any water connection point to prevent any water from...

Страница 8: ...rom the system until no chlorine smell is detectable Make sure that each fixture that was disinfected in step two is completely flushed of the chlorine solution as the consumption of the water is not advised due to the extremely high concentrations of chlorine It is important to remember that in the event that a UV is briefly shut down for a routine cleaning or during power interruptions where wat...

Страница 9: ...TER LAMP REPLACEMENT PG 9 refer to www lamprecycle org for lamp disposal QUARTZ SLEEVE REPLACEMENT CLEANING Mineral deposits and sediment may accumulate on the quartz sleeve decreasing the UV light transmittance and system performance Good maintenance of filtration equipment will reduce the accumulation of residues If necessary remove the quartz sleeve and clean with a commercially available scale...

Страница 10: ...und again if the lamp has not been replaced The alarm can be silenced up to 4 times 28 days After 4 times the alarm can no longer be silenced until a replacement lamp is installed and the lamp life timer is reset RESET LAMP LIFE TIMER AFTER LAMP REPLACEMENT After replacing the lamp by following instructions on the previous page reset the lamp life timer to 365 days by pressing and holding the butt...

Страница 11: ...OUND SCREW UNDER BALLAST U CLIP BUSHING LAMP CONNECTOR ALUMINUM GLAND NUT LAMP COMPRESSION SPRING O RING QUARTZ SLEEVE GROUND NUT UV LAMP GROUND WIRE RING TERMINAL STAINLESS STEEL UV CHAMBER QUARTZ SLEEVE DOMED END Refer to PRODUCT OVERVIEW page for replacement part numbers GROUND WIRE FORK TERMINAL ...

Страница 12: ...emperature Excessive Heat Generated Water temperature is too high Ensure treatment is on cold water side only prior to heating of water Water Appears Milky Caused by air in the water lines run water until air is purged Unit Leaking Water Problem with o ring seal on gland nut ensure o ring is in place check for cuts or abrasions clean o ring moisten with water and re install replace if necessary Co...

Страница 13: ...PAGE 13 A DIVISION OF C B TOOL CO 1340 MANHEIM PIKE LANCASTER PA 17601 3196 TEL 717 397 3521 FAX 717 392 0266 www lancasterwatergroup com E mail info lancasterwatergroup com 3 18 ...

Отзывы: