52
10
Accessories
DANGER!
Output contact, safe versus signalling contact
Electrical insulation is affected through base insulation, i.e. it is not allowed to simultaneously
apply SELV (safety extra low voltage) and mains voltage to the two contacts.
Output contact, safe
Changeover switch (floating)
- Maximum switching voltage
- Maximum switching current
- Switching capacity
- Internal fuse
max. 250 VAC, 48 VDC
Protection II
min. 6 VAC/DC
max. 0.5 A
min. 10 mA, at a limit load of 50 mA
min 0,1 W
on DC voltage max. 30 W
on AC voltage max. 120 W
500 mA slow IEC
Signalling contact
Normally open contact (floating)
–
Maximum switching voltage
–
Maximum switching current
–
Switching capacity
on DC voltage
on AC voltage
–
External fuse
max. 250 VAC, 30 VDC Protection class II
min. 6 VAC/DC
max. 0,5 A
min. 10 mA,
at a limit load of 50 mA
min. 0,1 W
max. 30 W
max 120 W
500 mA slow IEC,
750 mA slow UL
Connection core section
–
Flexible
–
Rapid
0,5 ... 2,5 mm
2
/20 AWG... 14 AWG
0,5 ... 4,0 mm
2
/20 AWG... 12 AWG
Technical Stressability
Operating mode
Creepage distances
Continuous operation
Intermittent operation 72h operation according to TRD 604
IEC 60730-1:2010, ÜK III, VG 2
Содержание F200K Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual F200K Compact Flame Scanner ...
Страница 2: ......
Страница 39: ...38 7 Instructions on Commissioning and Maintenance ...
Страница 71: ...70 11 Commissioning Protocol 11 Commissioning Protocol ...
Страница 72: ...71 12 EU Declaration of Conformity 12 EU Declaration of Conformity ...
Страница 73: ...72 12 EU Declaration of Conformity ...