Instructions on Commissioning and Maintenance
7.2.3
Preparations
7.2.3.1 Checking the Compact Flame Scanner
The flame detector can be checked for proper functionality without a flame being present.
1
Carry out the complete electrical installation of the flame detector and connect it to the
supply voltage.
A LAMTEC test emitter of the FFP30 type (IR + UV) can be used as an auxiliary means
for flame simulation.
2
Simulation of flame radiation in front of the flame detector's viewing port. This can be
achieved using a lighter or any other type of a modulated-light source (do not use the
mains frequency) having a sufficiently high intensity. For example the light from a lamp can
be modulated by moving splayed fingers to and fro in front of the bulb. However, start-up
suppression requires a stable signal to do this. If necessary and if the signal is not suffi-
cient, the
9.1 Layout of the Operational Controls
) should be
set to
OFF
in order to make the reaction to the simulated flame signal visible.
The flame detector will switch on its output contacts if the flame signal is simulated for a suf-
ficient period of time. This is indicated by the extinction of the red LED and the pulsating light
of the green LED. The 6-level intensity indicator illuminates.
If no flame signal is indicated despite apparent correct functionality then check the output con-
tact (refer to chapter
7.2.3.2 Alignment
The following information applies analogous to the process optics of Fiber optic.
IR- flame detectors
should be installed / aligned in such a way that possible reflections from
the combustion chamber are already largely suppressed by constructive measures. A ball-
and-socket joint for the alignment of the sensor to the flame is normally not required, since the
optics of the flame detector is characterised by a wide viewing angle.
UV- flame detectors
should generally be used with a ball-and-socket joint only, since the op-
tics of the flame detector has a narrow viewing angle. For this reason an optimum alignment
towards the flame is of utmost importance.
7.2.3.3 Optics
There are no special requirements for locking discs or similar components when using
IR-
flame scanners
. Small accumulations of dirt due to dust and similar materials are generally
not critical for flame detection.
In
UV- flame scanners
, the requirements for locking discs are more critical. Ensure that ma-
terials, such as quartz, that allow UV light to pass through freely are used. These materials
are used in the LAMTEC UV adjustable holding devices (FH30, FV30, FH40 and FV40) Small
accumulations of dust, water and other contaminants are much more likely to affect the per-
formance of flame detection than when using an IR scanner.
WARNING!
When using an F200K without mains frequency suppression, it must be ensured that it is pro-
tected against the detection of mains frequency light. The mounting of the sight opening on
the burner must meet the requirements of a tool mounting. Unintentional loosening of the
F200K must be prevented.
Advice on this is available from LAMTEC support.
Содержание F200K Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual F200K Compact Flame Scanner ...
Страница 2: ......
Страница 39: ...38 7 Instructions on Commissioning and Maintenance ...
Страница 71: ...70 11 Commissioning Protocol 11 Commissioning Protocol ...
Страница 72: ...71 12 EU Declaration of Conformity 12 EU Declaration of Conformity ...
Страница 73: ...72 12 EU Declaration of Conformity ...