28
7
Instructions on Commissioning and Maintenance
7.2.2
Special Points to Note When Using the Device in Explosion-proof Areas
The following applies when using the F200K Ex-II, F200K Ex in explosion-proof areas:
•
For use only in approved explosion protection zones.
•
To protect its aperture, only mount the F200K Ex-II, F200K Ex on a burner or boiler using
one of its holders: the FV30, FH30 or FS50.
•
Use only the types of cable specified by the manufacturer when extending cables.
•
When extending cables in the potentially explosive area, use only terminal housings that
are approved for this area. LAMTEC recommends the connection housing FG24 Ex for
this purpose.
•
Check if cable connections fit tightly. Should there be a need to loosen the cable connec-
tion, it is to be ensured that the cables do not turn while loosening and tightening the cable
connection.
•
Note, in particular, the information on setup in EN 60079-14, section 12.2 (cables and
earthing).
•
Only remove the connector of the F200K Ex-II, F200K Ex or any other cable connections
when it is deenergised.
See the warning on the device:
WARNING – DO NOT DISCONNECT WHEN ENERGISED.
•
In particular, seperation has to be in accordance with EN 60079-14 'Appendix:
Instructions for procedures to work safely in an explosive gas atmosphere', only permitted
after the release by personnel in charge of the explosion protection of the operating
company.
•
Opening the device is required during commissioning!
Should there be any risk of danger to the surroundings in an opened device, a clearance
measurement as described above should be done before the opening.
•
A transformer for generating the supply voltage must be carried out according to
IEC 61558-2-6.
•
You must use a current limiter with a limit on the rated voltage.
•
When using the device in the ambient temperature range, you must keep the temperature
in accordance with the temperature class:
See Ex marking on the device
•
If devices are so damaged that they no longer meet the requirements of the protection
class, you must replace them.
Special instructions for use in Hazardous Area Class I Division 2 (valid for F200K Ex-II)
•
During installation, the rules of the NEC (National Electrical Code) must be considered.
UL Listed Version:
•
The plug of the connecting cable must be secured against self-loosening after mounting
on the flame detector. There are screws on the union nut of the connector.
Содержание F200K Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual F200K Compact Flame Scanner ...
Страница 2: ......
Страница 39: ...38 7 Instructions on Commissioning and Maintenance ...
Страница 71: ...70 11 Commissioning Protocol 11 Commissioning Protocol ...
Страница 72: ...71 12 EU Declaration of Conformity 12 EU Declaration of Conformity ...
Страница 73: ...72 12 EU Declaration of Conformity ...