45
4
CMS Components
Signal inputs
Namur
Pulse input for connecting inductive
sensors with Namur interface accord-
ing to
EN 60947-5-6
Sensor supply: 8.2 V, max. 8.2 mA
Conversion of the sensor recording into digital information:
– Inactive: >2.1 mA
Digital signal ON
– Active/pulse: <1.2 mA
Digital signal OFF
– Hysteresis:
≥
0.5 mA
Frequency range: 5 ... 9400 pulses/min (0.25 ... 157 Hz)
Pulse length: min. 200
s,
Use shielded connection cable for cable lengths >10 m.
Pulse input 3-wire
Pulse input for connecting inductive
sensors with
3-wire interface
Sensor supply: 24 V
Conversion of the input voltage into digital information:
– Inactive: 0 V/High-Z
Digital signal OFF
– Active/pulse: 24 V
Digital signal ON
– Hysteresis:
≥
¼ U
max
Frequency range: 5 ... 9400 pulses/min. (0.25 ... 157 Hz)
Pulse length: min. 200
s,
Use shielded connection cable for cable lengths >10 m.
Analogue input 0/4 ... 20 mA
for connecting speed transmitter 4 ...
20 mA or position detectors from ser-
vomotors with power interface 4 ... 20
mA.
Range: 0/4 ... 20 mA, load 150
Ω
, accuracy ±1 %
Overcurrent limitation: approx. 25 ... 28 mA
Use shielded connecting pipework
Digital inputs
*
Nominal cur-
rent:
2.3 mA (230 VAC), impedance 100 k
Ω
2.1 mA (120 VAC), impedance 75 k
Ω
2.1 mA (24 VDC), impedance 11 k
Ω
Due to low currents on the contacts, use gold-plated silver con-
tacts.
Signal ON:
0.78 mA (230 VAC) 77 VAC
0.97 mA (120 VAC) 56 VAC
0.55 mA (24 VDC) 6.9 VDC
Signal OFF:
0.35 mA (230 VAC) 36 VAC
0.35 mA (120 VAC) 21 VAC
0.27 mA (24 VDC) 4 VDC
Electrically safe separation between the input and electronics,
floating
*
Do not use for safety-relevant signals
Outputs
Analogue output
0/4 ... 20 mA or 0/2 ... 10 V
Current output 0/4 ... 20 mA
Voltage output 0/2 ... 10 V
Same setpoint for both outputs
Can be set via parameters
Accuracy ±1.5 %
Use shielded connecting pipework
Voltage ripple
≤
50 mV
pp
max. current 10 mA
Short circuit proof
Accuracy ±2 % of the maximum value
Use shielded connecting pipework
Содержание AEC-TPS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...