104
5
Functional Description with Process Diagrams
5.4.3.2 I Term
The firing rate controller can use an actual current value (mA), the boiler temperature (°C, °F)
or the steam pressure (bar, psi) as the actual value for control. P 61 defines the unit of the
actual value.
For steam pressure, P 62 and P 63 are also required.
5.4.3.3 Constant Controller
If the firing rate controller is used as a constant control, its setpoint is obtained from the pa-
rameters
•
P 49 for setpoint 1
•
P 51 for setpoint 2
P no.
Description
Attributes
61
Selection of the actual value input and the unit for indication (0-Digit; 1-°C; 2-bar; 3-mA; 4-
°F; 5-psi)
V1.0.0.0
Selection of the unit in which the input for actual value is to be indicated
0 = Digit
1 = °C
2 = bar
3 = mA
4 = °F
5 = psi
Write: 0/GUI/UI
Read: 0
Default: 2
Min: 0
Max:5
62
Pressure input: Scaling minimum
V1.0.0.0
Pressure at 4 mA input current in 0,1 units (bar, psi).
Input of the lower limit of the display range, which corresponds to 4 mA at the input, if the
input is configured as pressure input.
This parameter can only be active if P 61 = 2
Example: Value = 100, is equal to a minimum pressure of 10,0 bar/psi
Write: 1/GUI/UI
Read: 0
Default: 0
Min: 0
Max:999
63
Scaling maximum
V1.0.0.0
Pressure at 20 mA input current in 0,1 units (bar, psi).
Input of the upper limit of the display range, which corresponds to 20 mA at the input, if the
input is configured as pressure input. This parameter can only be active if P 61 = 2
Example: Value= 500, is equal to a maximum pressure of 50,0 bar/psi
Write: 1/GUI/UI
Read: 0
Default: 160
Min: 0
Max: 999
P no.
Description
Attributes
49
Controller 1 maximum value (only for control by atmospheric conditions)
V1.0.0.0
Controller setpoint 1 max. for control by atmospheric conditions
Enter the setpoint maximum for the controller in °C or bar. The setting is active if the input
"Setpoint changeover" = 0.
Write 0/GUI/UI
Read: 0
Default: 84
Min: -32768
Max: 32767
51
Controller 2 maximum value (only for control by atmospheric conditions)
V1.0.0.0
Controller setpoint 2 maximum for control by atmospheric conditions
Enter the setpoint maximum for the controller in °C or bar. The setting is active if the input
"Setpoint changeover" = 1.
Write: 0/GUI/UI
Read: 0
Default: 84
Min: -32768
Max: 32767
Содержание AEC-TPS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...