Functional Description with Process Diagrams
5.4.3.6 Burner Shut-OFF
P no.
Description
Attributes
44
Start-up sequence: firing-rate [Digit]
V1.0.0.0
Start-up output in digit depending on internal firing-rate.
Enter the burner firing-rate with which the burner shall start in the start-up sequence.
Write: 0/GUI/UI
Read: 0
Default: 0
Min: 0
Max:999
45
Start-up sequence: start-up time [s]
V1.0.0.0
Start-up time in s
Enter the maximum duration, during which the start-up sequence should effect.
Write: 0/GUI/UI
Read: 0
Default: 1
Min: 0
Max:32767
46
External firing-rate limit [Digit]
V1.0.0.0
External firing-rate limit in digit depending on the internal firing-rate.
Only for activated burner firing-rate controller.
Write: 0/GUI/UI
Read: 0
Default: 999
Min: 0
Max:999
P no.
Description
Attributes
47
Soft stop time
burner run-out time [s]
V1.0.0.0
Currently without function.
Write: 0/GUI/UI
Read: 0
Default: 0
Min: 0
Max:100
54
switch-on threshold
V1.0.0.0
Switch-off hysteresis for the lower control range
If the actual value falls below the setpoint minus the value set in this parameter, the burner is
switched on again.
Enter the switch-on point as the difference to the setpoint.
Switch on value = setpoint value - parameter content.
Example: The burner shall start at 110.
Setpoint value = 120, parameter value = 10, switch-on point = 120 - 10 = 110.
If the burner should switch on again above the setpoint, negative values can also be
entered. Thereby corresponds -1 = 65535 and -999 = 64537.
Parameter content = 65536 - difference.
Example: The burner shall start at 125.
Setpoint value = 120, parameter value = 65536 - 5 = 65531, switch-on point = 120 - (-5) =
125.
Write: 0/GUI/UI
Read: 0
Default: 1
Min: -32768
Max: 32767
55
Switch-off threshold for the upper control range
V1.0.0.0
Switch-off hysteresis of the upper control range in °C or bar (x.xx)
Input of the upper control range. If the actual value exceeds the setpoint by this value, the
burner runs at base fire.
The value entered corresponds to the difference between the current setpoint and the upper
limit of the control range. Depending on the setting in P 61, the content is interpreted as °C
(directly without decimal point) as bar (resolution 0.1 bar - range 0.1 to 99.9 bar) or in digits.
Write: 0/GUI/UI
Read: 0
Default: 5
Min: 0
Max:999
Содержание AEC-TPS
Страница 1: ...www lamtec de Sensors and Systems for Combustion Engineering Manual Combustion Management System CMS...
Страница 2: ......
Страница 42: ...41 4 CMS Components 4 2 5 Terminal Assignment Fig 4 9 AEC TPS 230 VAC or 120 VAC terminal assignment...
Страница 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Страница 142: ...141 7 Operating Control and Displays Accessing channel information AL1 Fig 7 12 GUI6xx channel information...
Страница 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Страница 154: ...153 7 Operating Control and Displays Accessing the CO O2 settings AL2 Fig 7 24 CO O2 settings menu...
Страница 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Страница 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Страница 163: ...162 7 Operating Control and Displays 7 2 8 User Settings Accessing the display settings Fig 7 33 Display settings menu...
Страница 164: ...163 7 Operating Control and Displays Accessing the language settings AL1 Fig 7 34 Language settings menu...
Страница 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Страница 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Страница 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Страница 198: ...197 7 Operating Control and Displays 1 Digital inputs 2 Digital outputs 3 PLC Signals 4 Analogue measurement values...
Страница 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Страница 271: ...270 10 Maintenance 6 Close the window Connection between PC and CMS is established Indication of the con nected CMS...
Страница 272: ...271 10 Maintenance How to update the firmware in the CMS AL2 1 Open the menu Firmware update 2 Prepare firmware update...
Страница 274: ...273 10 Maintenance Activating the Debug Data 1 Start CMS Remote Software 2 Set device online 3 Show debug data...
Страница 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Страница 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Страница 283: ...282 12 Appendix...