BA_078_en_10.01 Level transmitter PASCAL Ci4 LEVEL 

Page 17/36 

 

6.4.2 

Setting a numeric value 

When setting numeric values, the screen shows the following elements (from top to bot- 
tom): 

  Designation of the parameter that can be set 

  Help text (if applicable) 

  Numeric value and unit 

  Function of buttons 

  Bar graph 

After  selecting  a  menue  item  for  numerical  entry  (e.g.  damping),  at  first  the  value  is  dis- 
played  only.  The  numeric  value  itself  is  shown  in  square  brackets  and  its  unit  behind  it. 
Unused leading digits are marked with bottom lines. You need to press OK again to enter 
the edit mode. 

Numeric values are entered digit by digit. First, always the leftmost digit is selected (visible 
with a triangle above and below the number). By pressing OK, you go to the next digit. 

 

Figure 16: Elements when setting a numeric value 

 

You  change  the  selected  digit  by  pressing  the          or          button.  The  higher  value  digit  is   
also increased or decreased when passing zero. For instance, you can easily go from 19 
to 20 without having to edit two digits. 

Lower value digits are not influenced, unless  the parameter limit is reached. The value is 
then set to the parameter limit. 

You can set negative numbers by decreasing the value below zero. 

When  you  press  the ESC  button,  you  can cancel  the  entry  at  any  time  and  return  to  the 
display of the set value. Any change of the value is not saved. 

With the OK button you confirm the set digit value and jump to the next digit. 

When you confirm the rightmost digit, the entire value is saved. You can save the new val- 
ue from any digit by pressing and holding the OK button. 

Содержание CI4350

Страница 1: ...devices 3 3 3 Mechanical Installation 3 3 4 Electrical Connection 3 3 5 Devices with Diaphragm Seal 4 3 6 Mounting the Remote Display 4 4 Operation 5 4 1 Test Terminals 5 4 2 Remove Display Activate W...

Страница 2: ...ocess and undamaged The device is intended to measure pressure of gases vapors and liquids as specified in the data sheet The CE marking on the device certifies its compliance with the applicable EU D...

Страница 3: ...wer process connection and the minus side to the upper process connection 3 3 Mechanical Installation Use gaskets if required that are suitable for the process connection and resistant to the media Be...

Страница 4: ...ipe mounting for pipe diameters from 30 64 mm For pipe mounting you can order the corresponding U bolts from LABOM For best EMC protection only use the included cable If you ordered the remote display...

Страница 5: ...y and control unit after installation During operation take care that the device remains within its intended pressure and tem perature ranges No other monitoring is necessary Permissible ambient tempe...

Страница 6: ...efully Figure 5 Removing the display After removing the display module you can reach the DIP switch on the CPU module The write protection is active when the DIP switch is in the ON position Figure 6...

Страница 7: ...g pressurized lines might cause severe injuries Danger of severe injuries or damage Relieve the process pressure before attempting to remove the device Shut off the pressure supply for all feed lines...

Страница 8: ...e and shape of the tank must be defined for calculating the volume and weight NOTE It would be physically correct to refer to the fill amount as a mass However the not quite correct term weight is rec...

Страница 9: ...ot affect the tank shape definition The table is managed internally in metre litre pairs and converted for the display depend ing on the units selected The display therefore adapts accordingly to the...

Страница 10: ...ht from the fill vol ume 6 1 5 Summary of the parameterisation concept 1 The fill height is calculated from the measured pressure using the density and height offset 2 The fill volume is calculated fr...

Страница 11: ...and hold the ESC button you always return to the measured value display Button Function Select function increase decrease value OK Confirm selected function or selected value ESC Cancel action ESC lo...

Страница 12: ...an inappropriate unit the largest displayable number is shown flashing In this case please select a different setting of the decimal point or a different unit In display mode you can review the device...

Страница 13: ...icon Use the same key combination to unlock the menue again The menue cannot be un locked with the key combination if the hardware DIP switch is activated 6 3 3 Icons indicating device status In the t...

Страница 14: ...use the entire display width Horizontal bargraph Three val ues Under the main value two additional values are shown Both of them can use the entire display width Horizontal bargraph Two values Two va...

Страница 15: ...avigate in the menues by using the arrow buttons The selected menue item is indicated by triangles on the left and right The OK button selects the menue item or switches to the corresponding submenue...

Страница 16: ...ss OK to switch to edit mode to change the parameter After this is done the display will then switch back to view mode so that you can check the new setting 6 4 1 1 Selection of a value from a selecti...

Страница 17: ...angle above and below the number By pressing OK you go to the next digit Figure 16 Elements when setting a numeric value You change the selected digit by pressing the or button The higher value digit...

Страница 18: ...ick setup Selection of the most important settings Level Parameterisation of level measurement Adjustment Adjustment functions for pressure measurement and current out put Display Functions for config...

Страница 19: ...mping Setting the damping of the output signal see 6 5 6 1 Device ID Setting the device ID see 6 5 10 1 Config memory Configuration memory reading writing and status see 6 5 10 3 Table 7 Quick Setup m...

Страница 20: ...r PASCAL Ci4 LEVEL Page 20 36 6 5 3 1 Level wizard The fill level wizard allows the easy parameterisation of the device You are guided through all the necessary setting dialogue boxes Figure 18 Guided...

Страница 21: ...s that the height offset is correctly set and the fill height relative to the level ze ro can be determined with sufficient accuracy The device calculates the density from the measured pressure and th...

Страница 22: ...11 Density submenue Enter or teach in the tank shape A basic requirement for the correct recording of the tank shape is the correct parameteri sation of the density and height offset Entering and teac...

Страница 23: ...in process two control points will be very close together which can lead to problems with the volume calculation The odd control point is deleted after checking for closely located control points Che...

Страница 24: ...e static pressure measurement For these devices there is an additional menue entry called Zero point pst 6 5 4 1 Zero point correction The zero point correction requires a non pressurized pressure por...

Страница 25: ...e at 900 mbar rel The reference pressure level for the upper offset can also be freely chosen To ensure that the adjustment is as precise as possible the upper and lower adjustment should be performed...

Страница 26: ...f decimal places Backlight Switch backlight on off Table 14 Display menue 6 5 5 1 Submenue Units You can select the unit of every value shown on the display These settings do not affect the internal c...

Страница 27: ...ight unit The unit in which the measured weight should be displayed can be selected from the fol lowing list Unit Description g Gramme 1 g 0 001 kg kg Kilogramme 1 kg 1000 g 0 001 t t Tonne 1 t 1000 k...

Страница 28: ...i Pound force per square inch 1 psi 68 9 mbar atm Atmospheric pressure 1 atm 1013 mbar mmH2O Millimetre water column 1 mmH2O 0 0981 mbar mH2O Metre water column 1 mH2O 98 1 mbar inH2O Inch water colum...

Страница 29: ...In addition you select and parameterise the measurand to be shown at the current output Menue entry Description Damping Setting the damping of the output signal Measuring rate Setting the measuring ra...

Страница 30: ...ed and the current is calculated and imprinted in the current loop When a particularly fast measuring rate is required for instance to detect pressure peaks you can increase the measuring rate to 100...

Страница 31: ...asured value display in the device data see 6 3 1 Figure 25 Display and resetting of the Min Max values for pressure 6 5 7 2 The maintenance timer Using the maintenance timer the device can signal the...

Страница 32: ...tion menue 6 5 9 1 HART address This address corresponds with the short address which is used for the HART Communication It can be set within a range of 0 to 63 Please note that setting the short addr...

Страница 33: ...display module You can transfer the data back to the device or to another device Transferring a configu ration to another device requires a compatible target device The same nominal range is not neces...

Страница 34: ...BA_078_en_10 01 Level transmitter PASCAL Ci4 LEVEL Page 34 36...

Страница 35: ...BA_078_en_10 01 Level transmitter PASCAL Ci4 LEVEL Page 35 36 6 5 11 Overview with menue tree and device functions...

Отзывы: